Configuring the GX/GP
1
2
3
4
5
App
1.7 Setting Measurement Conditions (Scan interval,
A/D integrate, etc.)
Set the scan interval, A/D integrate, measurement groups, etc.
1.7.1 Setting the Scan Interval
Path
GX/GP: MENU key > Browse tab > Setting > Setting menu Measurement settings
Web browser: Config. tab > Measurement settings > Scan interval
Hardware configurator: Measurement settings > Scan interval
Description
Scan interval
Setup Item Selectable Range or Options Default Value
Scan interval 100ms
*1
, 200ms
*1
, 500ms
*1
, 1s, 2s, 5s 1s
*2
*1 Cannot be specified if an electromagnetic relay scanner type (Type suffix code: -T1) analog
input module is in use (configure).
*2 2 s if an electromagnetic relay scanner type analog input module is in use.
Scan interval
Set the scan interval. The scan intervals that you can set are displayed depending on the
installed modules.
1.7.2 Setting the Over-range Detection Method
Path
GX/GP: MENU key > Browse tab > Setting > Setting menu Measurement settings
Web browser: Config. tab > Measurement settings > Over-range
Hardware configurator: Measurement settings > Over-range
Description
Over-range
Setup Item Selectable Range or Options Default Value
Value on over-range Free, Over Over
Value on over-range
Set how to detect over-range values on linearly scaled or square-rooted I/O channels.
In either case, +over range occurs if the value excluding the decimal point exceeds 99999
and –over range if it falls below –999999.
Options Description
Free The value is set to –over range if the value is less than –5% of the measurable
span range and +over range if the value is greater than 105%.
Over The value is set to –over range if the value is less than –5% of the span setting
(Linear scaling or , Square root span) and +over range if the value is greater
than 105%.
Example: If the linear scaling scale is 0.0 to 200.0, a value less than –10.0
results in a –over range, and a value greater than 210.0 results in a +over
range.