15
<<Contents>> <<Index>>
All Rights Reserved. Copyright © 2012-2013, Yokogawa Electric Corporation
GS 04L51B01-01EN May. 7, 2013-00
DIGITAL INPUT MODULE (Model
GX90XD or Options /CRx1)
GX90XD
• Application: Remote control input, etc
• Number of inputs: 16
• Measurement interval: 100 ms (shortest)
• Input type: Open collector or Voltage-free contact
• Insulation type: Photocoupler, Trance (power
supply)
• Contact rating: 12 V DC, 20 mA or more
• Input resistance: Approx. 1 kΩ
• Allowable input voltage: 10 V
• ON/OFF detection
Open collector contact input:
Voltage in ON state: 0.5 V DC or less
Leakage current in OFF state: 0.5 mA or less
Voltage-free contact input:
Contact resistance in ON state: 200 Ω or less
Contact resistance in OFF state: 50 kΩ or
more
• Number of common: 2 (1 point/8 channels)
• Terminal type: M3 screw terminal or Clamp
terminal
(In case of Options /CRx1, a digital input module
has M3 screw terminals.)
• Withstand voltage
Between the input terminals and the internal
circuit: 1500 V AC for one minute
• Insulation resistance:
Between the input terminals and the internal
circuit: 20 MΩ or greater at 500 VDC
Safety and EMC Standards
• CSA: CSA22.2 No.61010-1, installation category
II (*1), pollution degree 2 (*2)
• UL: UL61010-1 (CSA NRTL/C)
• CE:
EMC directive
EN61326-1 compliance, Class A Table 2
EN61000-3-2 compliance
EN61000-3-3 compliance
EN55011 Class A Group 1
Low voltage directive
EN61010-1
Installation category II (*1)
Pollution degree 2 (*2)
Not included in the measurement category
• C-Tick: EN55011 compliance, Class A Group 1
• KC marking: Electromagnetic wave interference
prevention standard, electromagnetic wave
protection standard compliance
*1 Installation category (overvoltage category) II:
Describes a number which denes a transient
overvoltage condition.
Implies the regulation for impulse withstand
voltage.
“II” applies to electrical equipment which
is supplied from the xed installation like a
distribution board.
*2 Pollution degree 2:
Describes the degree to which a solid, liquid,
or gas which deteriorates dielectric strength or
surface resistivity is adhering.
“2” applies to normal indoor atmosphere.
Normally, only non-conductive pollution occurs.
• WEEE Directive: Compliant
Construction
• Front panel (terminal): Water and dust-proof,
Complies with IEC529-IP20
• Material: Polycarbonate
• Color;
Front: Charcoal grey light (CC28)
Bezel: Smoke blue (CC53)
• Dimensions: 45 mm(W) x 100 mm(H) x 133
mm(D) (D: including terminal cover)
• Weight: Approx. 0.3 kg
Power Supply
Suppy from GX main unit.
• Power consumption: 0.7W or less
Terminal arrangements
M3 screw terminal/Clamp terminal
No. Symbol No. Symbol
21 DI9 11 DI1
22 DI10 12 DI2
23 DI11 13 DI3
24 DI12 14 DI4
25 DI13 15 DI5
26 DI14 16 DI6
27 DI15 17 DI7
28 DI16 18 DI8
29 COM 19 COM
30 - 20 -