Input Type Range Measurement accuracy (digital display) Max. resolution
of digital display
A/D integration time: 16.7ms or more A/D integration time: 1.67ms (fast sampling mode)
RTD Pt100 -200.0 to 850.0 °C ±(0.15 % of rdg + 0.3 °C) ±(0.3 % of rdg + 1.5 °C) 0.1 °C
-150.00 to 150.00 °C 0.01 °C
JPt100 -200.00 to 550.00 °C 0.1 °C
-150.00 to 150.00 °C 0.01 °C
Cu10 GE -200.0 to 300.0 °C ±(0.2 % of rdg + 2.0 °C)
guaranteed range
Cu10 GE: -70.0 to 170.0 °C
Cu10 L&N: -75.0 to 150.0 °C
Cu10 WEED: -200.0 to 260.0 °C
Other range: -200.0 to 300.0 °C
±(0.4 % of rdg + 6.0 °C)
guaranteed range
Cu10 GE: -70.0 to 170.0 °C
Cu10 L&N: -75.0 to 150.0 °C
Cu10 WEED: -200.0 to 260.0 °C
Other range: -200.0 to 300.0 °C
0.1 °C
Cu10 L&N -200.0 to 300.0 °C
Cu10 WEED -200.0 to 300.0 °C
Cu10 BAILEY -200.0 to 300.0 °C
Cu10 (20 °C)
alpha=0.00392
-200.0 to 300.0 °C
Cu10 (20 °C)
alpha=0.00393
-200.0 to 300.0 °C
Cu25 (0 °C)
alpha=0.00425
-200.0 to 300.0 °C ±(0.3 % of rdg + 0.8 °C) ±(0.5 % of rdg + 3.0 °C) 0.1 °C
Cu53 (0 °C)
alpha=0.00426035
-50.0 to 150.0 °C ±(0.15 % of rdg + 0.8 °C) ±(0.3 % of rdg + 4.0 °C) 0.1 °C
Cu100 (0 °C)
alpha=0.00425
-50.0 to 150.0 °C ±(0.2 % of rdg + 1.0 °C) ±(0.4 % of rdg + 5.0 °C) 0.1 °C
J263B 0.0 to 300.0 K ±1.0 K
Less than 40.0 K: ±3.0 K
±3.0 K
Less than 40.0 K: ±9.0 K
0.1 K
Ni100 (SAMA) -200.0 to 250.0 °C ±(0.15 % of rdg + 0.4 °C) ±(0.3 % of rdg + 2.0 °C) 0.1 °C
Ni100 (DIN) -60.0 to 180.0 °C
Ni120 -70.0 to 200.0 °C
Pt25 -200.0 to 550.0 °C ±(0.15 % of rdg + 0.8 °C) ±(0.3 % of rdg + 4.0 °C) 0.1 °C
Pt50 -200.0 to 550.0 °C ±(0.3 % of rdg + 0.6 °C) ±(0.6 % of rdg + 3.0 °C) 0.1 °C
Pt200 WEED -100.0 to 250.0 °C
Cu10 GOST -200.0 to 200.0 °C ±(0.2 % of rdg + 2.0 °C) ±(0.4 % of rdg + 6.0 °C) 0.1 °C
Cu50 GOST -200.0 to 200.0 °C ±(0.15 % of rdg + 0.6 °C) ±(0.3 % of rdg + 4.0 °C) 0.1 °C
Cu100 GOST -200.0 to 200.0 °C ±(0.15 % of rdg + 0.3 °C) ±(0.3 % of rdg + 1.5 °C) 0.1 °C
Pt46 GOST -200.0 to 550.0 °C ±(0.3 % of rdg + 0.8 °C) ±(0.6 % of rdg + 4.0 °C) 0.1 °C
Pt100 GOST -200.0 to 600.0 °C ±(0.15 % of rdg + 0.3 °C) ±(0.3 % of rdg + 2.0 °C) 0.1 °C
DI Level Threshold level (Vth=2.4 V) Accuracy: ±0.1 V -
Contact Less than 1 kΩ: 1(ON), More than 100 : 0(OFF) (parallel capacitance of 0.01 μF or less) -
Measurement accuracy at scaling: measurement accuracy at scaling (digits) = measurement accuracy (digits) x scaling
span (digits)/measurement span (digits) + 2 digits
* Rounding up decimal places
Burnout detection: Burnout upscale, downscale,
or OFF selectable (for each channel).
Available input: TC, RTD, Standard signal
TC; Normal: 2 kΩ or less., Burnout: 200 kΩ
or more (parallel capacitance of 0.01 μF or
less)
Detection current: Approx. 10 μA
RTD; Normal: wiring resistance or less,
Burnout: 200 kΩ or more (parallel
capacitance of less than 0.01 μF or less)
Standard signal: Normal: Within measuring
range, Burnout: -10% or less or 110% or
more of the specied span.
Input external resistance:
DC voltage, thermocouple input: 2 kΩ or
below
Resistance temperature detector input: 10 Ω
or below in each wire (Same resistance in
three wires)
Input bias current: ±10 nA or less (when burnout
function does not work)
Measured current (for RTD): Approx. 1 mA
Input resistance:
10 MΩ or more for TC/DC voltage (1 V range or
less) input
Approx. 1 MΩ for DC voltage (2 V range or
more)/standard signal input
Allowable signal source resistance: 2 kΩ or less
for TC/DC voltage (1 V range or less) input
Effect of signal source resistance:
±10 μV/1kΩ or less for TC/DC voltage (1 V range
or less) input
±0.15 %/1kΩ or less for DC voltage (2 V range or
more)/standard signal input
Allowable wiring resistance: Max. 10 Ω per line
for RTD input (conductor resistance between the
three lines shall be equal)
Effect of wiring resistance: ±0.1°C/10 Ω for RTD
input (conductor resistance between the three
lines shall be equal)
Allowable input voltage:
±10 V DC for TC/DC voltage (1 V range or less)/
RTD/DI input
±60 V DC for DC voltage (2 V range or more) input