Yokogawa Touch Screen GP20 User Manual Page 334

  • Download
  • Add to my manuals
  • Print
  • Page
    / 446
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 333
4-14
IM 04L51B01-01EN
Hold Register
Type GX/GP Register
Number Data Type
I/O channel I/O data 400001 to 401000 32-bit signed integer
401001 to 402000 32-bit floating point
402001 to 402500 16-bit signed integer
Status information 402501 to 403000 16-bit signed integer
I/O channel
(continuous area)
I/O data 404001 to 404200 32-bit signed integer
404201 to 404400 32-bit floating point
404401 to 404500 16-bit signed integer
Status information 404501 to 404600 16-bit signed integer
Communication
channel
Communication data 405001 to 405600 32-bit signed integer
406001 to 406600 32-bit floating point
407001 to 407300 16-bit signed integer
Status information 407501 to 407800 16-bit signed integer
Internal switch 408001 to 408100 16-bit signed integer
GX/GP operation setting 409001 to 410000 16-bit signed integer
Client/Master device
ReadWrite
Coil
Type GX/GP Register
Number Data Type
I/O channel I/O data 1 to 500 Bit string
Status information 501 to 1000
Communication
channel
Communication data 1001 to 1300
Status information 1501 to 1800
Internal switch 2001 to 2100
Client/Mastre device
ReadWrite
Input Relay
Type GX/GP Register
Number Data Type
I/O channel I/O data 10001 to 10500 Bit string
Status information 10501 to 11000
Math channel Math data 11001 to 11100
Status information 11501 to 11600
Client/Master device
Read
4.5 Modbus Function and Register Assignments
Page view 333
1 2 ... 329 330 331 332 333 334 335 336 337 338 339 ... 445 446

Comments to this Manuals

No comments