Yokogawa Touch Screen GP20 User Manual Page 56

  • Download
  • Add to my manuals
  • Print
  • Page
    / 446
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 55
1-42
IM 04L51B01-01EN
1.4 Configuring DO Channels (Digital output
channels)
Set the DO channels’ input range and display conditions.
In addition to alarm output, DO output is possible through touch operation (manual
operation).
1.4.1 Setting the Range
Path
GX/GP: MENU key > Browse tab > Setting > Setting menu DO channel settings > Range
Web browser: Config. tab > DO channel settings > Channel range (display example: 0701-
0706)
Hardware configurator: DO channel settings > Channel range (display example:0701-0706)
Description
Setup Item Selectable Range or Options Default Value
First-CH DO channel
Last-CH DO channel
First-CH, Last-CH
Set the target channels. The channels that you can specify appear depending on the module
configuration.
Range
Setup Item Selectable Range or Options Default Value
Type Alarm, Manual Alarm
Span Lower 0, 1 0
Span Upper 0, 1 1
Unit
Character string (up to 6 characters,
A
a
#
1
)
Type
Set the input type.
To output through touch operation (manual operation), “Changing each value from
monitoring” must be set to On.
Refer to page 1-72 in section 1.6.5, “Setting Basic Screen
Items”
For the procedure, see page 2-9 in section 2.2.1, “Displaying Measured Data as Waveforms,
Numeric Values, or a Bar Graph (Trend, digital, and bar graph displays)”.
Options Description
Alarm Alarm output
Manual Manual output
Span Lower, Span Upper
Specify 0 or 1. You cannot set the same value to Span Lower and Span Upper.
Unit
Set the unit.