<G1. YFGW410>
G1-1
IM 01W02D01-01EN
Part G Specications
G1. YFGW410
G1.1 Standard Specication
n Communication Interface
Item Field Network Specications
Field Wireless
Backbone
Specications
Maintenance/Diagnostic
Network Specications
Communication
Interface
Standard 100BASE-TX
*2
RS-485
100BASE-TX
*2
100BASE-TX
*4
RS-232C
*4 *5
Transmission
Speed
100Mbps 38.4Kbps 100Mbps 100Mbps 115.2kbps
Connector RJ-45 Proprietary RJ-45 RJ-45 RJ-11
Cable Type Category 5 AWG24~12 Category 5 Category 5 Proprietary
Maximum
Length
100m 1200m 100m 100m 15m
Number of
Ports
3 ports 1 port 4 ports 1 port 1 port
Port Name F1, F2, F3 B1, B2, B3, B4 M1
Protection Surge Isolated, Surge Surge
Communication
Protocol
Modbus Modbus/TCP Modbus/RTU
OPC
*1
Proprietary
*3
Management,
conguration,
etc.
HTTP
NTP/SNTP
Proprietary
*3
HTTP
IEEE1588PTP v2
Proprietary
*3
HTTP
Proprietary
*3
*1: OPC interface connection is available by Field Wireless Device OPC Server (SSS7100). For details of this product, see related
products General Specications.
*2: In outdoor wiring to Field Network or 100BASE-TX of Field Wireless Backbone, use optical ber cables with a nonmetallic ten-
sion member, combining with YFGW610.
*3: TCP based custom protocol used for communication between this product, “Field Wireless OPC Server”, “FieldMate Versatile
Device Management Wizard”, “Plant Resource Manager (PRM)”, and YFGW510. For details of each product, see related prod-
ucts General Specications.
*4: Maintenance/Diagnostic Network (100BASE-TX, RS-232C) are not available for outdoor wiring.
*5: These are the serial ports for a maintenance which only our company use.
n OPTIONAL SPECIFICATIONS (For Explosion Protected Types)
Item Specication Code
Factory Mutual (FM) Nonincendive Approval
*1
ATEX Type n Declaration
*2
Canadian Standards Association (CSA) Nonincendive Approval
*1
IECEx Type n Approval
*2
*1: To be compliant with these standards, the YFGW410 hardware needs to be installed in a lockable metal cabinet.
*2: To be compliant with these standards, the YFGW410 hardware needs to be installed in a lockable metal cabinet of IP54 or higher
protection rating.
Page view 189