User’sManualYokogawa Electric CorporationEJX510B and EJX530BAbsolute and Gauge PressureTransmittersIM 01C27F01-01ENIM 01C27F01-01EN8th Edition
<2. Handling Cautions>2-2IM 01C27F01-01EN2.4 Selecting the Installation Location The transmitter is designed to withstand severe environme
<2. Handling Cautions>2-3IM 01C27F01-01EN2.5 Pressure ConnectionWARNING • Never loosen the process connector bolts when an instrument is
<2. Handling Cautions>2-4IM 01C27F01-01ENNOTEWhen storing the instrument with a battery pack, it is recommended to put the instrument in De
<2. Handling Cautions>2-5IM 01C27F01-01ENNote 2. Installation• Installation should be in accordance with ANSI/ISA-RP12.06.01 and the Nati
<2. Handling Cautions>2-6IM 01C27F01-01ENTransmitter[Intrinsically Safe]Group IIC, Zone 0Class I, II, III, Division 1,Groups A,B,C,D,E,F,G[
<2. Handling Cautions>2-7IM 01C27F01-01EN(2) OperationWARNING Take care not to generate mechanical sparking when access to the instrument
<2. Handling Cautions>2-8IM 01C27F01-01ENNote 4. Battery Pack• Use only YOKOGAWA battery pack F9915MA or F9915NS.Note 5. Special conditi
<2. Handling Cautions>2-9IM 01C27F01-01EN(3) OperationCAUTION• The temperature and pressure of uid should be maintained at levels that a
<2. Handling Cautions>2-10IM 01C27F01-01ENNOTEThis equipment has been tested and found to comply with the limits for a Class A digital devi
<3. Component Names>3-1IM 01C27F01-01EN3. Component NamesF0301.aiYES (Note 2)(Write disabled)NO(Write enabled)Zero-adjustmentscrewGround t
iIM 01C27F01-01ENEJX510B and EJX530BAbsolute and Gauge Pressure TransmittersIM 01C27F01-01EN 8th Edition8th Edition: Jan. 2014 (YK)All Rights Reserve
<4. Installation>4-1IM 01C27F01-01EN4. Installation4.1 Precautions Before installing the transmitter, read the cautionary notes in sectio
<4. Installation>4-2IM 01C27F01-01ENIMPORTANTTighten the hexagonal nut part of the capsule assembly. See Figure 4.3.F0403.aiCapsule assembl
<4. Installation>4-3IM 01C27F01-01EN4.5 Changing the direction of the antennaAdjust the direction of the antenna to be in the upright posi
<5. Installing Impulse Piping>5-1IM 01C27F01-01EN5. Installing Impulse Piping5.1 Impulse Piping Installation PrecautionsThe impulse pipin
<5. Installing Impulse Piping>5-2IM 01C27F01-01EN(3) Impulse Piping SlopeThe impulse piping must be routed with only an upward or downward
<6. Wiring>6-1IM 01C27F01-01EN6. Wiring6.1 Mounting Antenna and WiringFor Amplier housing code 8 and 9, an antenna is not attached to th
<6. Wiring>6-2IM 01C27F01-01EN6.1.2 Mounting External Antenna and Wiring Antenna Extension Cable6.1.2.1 Mounting of External AntennaMount
<6. Wiring>6-3IM 01C27F01-01ENTransmitter bodyGrounding cableProtect by self-bonding tapeF0604.aiAntenna extension cable 2: 10 mAntennaAnte
<6. Wiring>6-4IM 01C27F01-01EN6.1.2.3 Mounting of Arrester and WiringMount an arrester between the extension cables and connect the ground
<7. Operation>7-1IM 01C27F01-01EN7. Operation7.1 Preparation for Starting OperationThis section describes the operation procedure for the
iiIM 01C27F01-01EN5. Installing Impulse Piping ... 5-15.1 Impulse Piping Insta
<7. Operation>7-2IM 01C27F01-01EN Verify and Change Transmitter Parameter Setting and ValuesThe parameters related to the following items
<7. Operation>7-3IM 01C27F01-01EN7.4 Connecting to the Field Wireless Network Preparation work prior to connecting to a Field Wireless N
<7. Operation>7-4IM 01C27F01-01EN Connecting to a eld wireless networkThe action after installing the battery pack varies depending on t
<7. Operation>7-5IM 01C27F01-01ENNOTEIf the transmitter searches the Field Wireless Network for long time at low ambient temperature condit
<8. Setting Parameters>8-1IM 01C27F01-01EN8. Setting ParametersThis transmitter can remotely handle range changes, Tag No. setup, monitori
<8. Setting Parameters>8-2IM 01C27F01-01ENTable 8.1 Parameter Usage and SelectionItem DescriptionTag No Sets the tag No. as Device Tag (So
<8. Setting Parameters>8-3IM 01C27F01-01EN(a) Integral antenna type (Amplier housing code: 7)• Configuration• Diagnostics/Alerts• Power S
<8. Setting Parameters>8-4IM 01C27F01-01ENOnline Menu (continued)• Block Info• Block Mode• Dynamic Variables• Configuration• Calibration• O
<8. Setting Parameters>8-5IM 01C27F01-01ENOnline Menu (continued)• Block Info• Block Mode• Dynamic Variables• Configuration• Others(AI2 SP)
<8. Setting Parameters>8-6IM 01C27F01-01EN• Block Info• Block Mode• Dynamic Variables• Configuration• Others(AI3 Temp)• Tag Description(Blo
iiiIM 01C27F01-01EN8.4 Self-Diagnostics ...8-238.4.1 Iden
<8. Setting Parameters>8-7IM 01C27F01-01EN(b) Detachable antenna type (Amplier housing code: 8 or 9)• Configuration• Diagnostics• Alerts•
<8. Setting Parameters>8-8IM 01C27F01-01EN• Block Info• Block Mode• Dynamic Variables• Configuration• Calibration• Others(AI1 DP)• Tag Desc
<8. Setting Parameters>8-9IM 01C27F01-01EN• Block Info• Block Mode• Dynamic Variables• Configuration• Others(AI2 SP)• Tag Description(Block
<8. Setting Parameters>8-10IM 01C27F01-01EN• Block Info• Block Mode• Dynamic Variables• Configuration• Others(AI3 Temp)• Tag Description(Bl
<8. Setting Parameters>8-11IM 01C27F01-01EN(2) Menu TreeThe menu tree of the device conguration tool of our recommendation is shown below
<8. Setting Parameters>8-12IM 01C27F01-01EN• Configure/Setup(AI2 SP)F0803-2.ai• Tag Description(Block Info)• Upper Limit• Lower Limit• PV R
<8. Setting Parameters>8-13IM 01C27F01-01EN• Transducer Value. Status• Transducer Value. Value• UAPMO(Diagnostic)F0803-3.ai• Device Diagn
<8. Setting Parameters>8-14IM 01C27F01-01EN(b) Detachable antenna type (Amplier housing code: 8 or 9)• UAPMO• TRANSDUCER• AI1 DP• AI2 SP•
<8. Setting Parameters>8-15IM 01C27F01-01EN• Configure/Setup(AI2 SP)F0803-5.ai• Tag Description(Block Info)• Upper Limit• Lower Limit• PV R
<8. Setting Parameters>8-16IM 01C27F01-01EN• Transducer Value. Status• Transducer Value. Value• UAPMOMenu (Online)(continued)(Diagnostic)
<1. Introduction>1-1IM 01C27F01-01EN1. IntroductionThank you for purchasing the DPharp EJX Pressure transmitter.Your EJX Pressure Transmit
<8. Setting Parameters>8-17IM 01C27F01-01EN8.3.3 Parameters for Wireless Communication(1) Network InformationConcentrator object block: C
<8. Setting Parameters>8-18IM 01C27F01-01ENNOTEWhen the device detects AL01 and AL02, the LCD display stays on regardless of the status in
<8. Setting Parameters>8-19IM 01C27F01-01ENThe low cut point has hysterisis so that the output around the point is behaved as below gure.&
<8. Setting Parameters>8-20IM 01C27F01-01EN(1) Zero Point Adjustmenta. To set 0% at current input, perform following procedure.This metho
<8. Setting Parameters>8-21IM 01C27F01-01EN(2) Span AdjustmentSpan Adjustment is function to change the input and output characteristic th
<8. Setting Parameters>8-22IM 01C27F01-01EN8.3.12 Switching to Deep Sleep ModeWhen the instrument will not be used for a long time, switch
<8. Setting Parameters>8-23IM 01C27F01-01EN8.4 Self-Diagnostics8.4.1 Identify Problems by Using the Device Conguration ToolFirst, check
<8. Setting Parameters>8-24IM 01C27F01-01EN8.4.2 Alert ReportEJX generates alert information related to Diagnostic Status and automaticall
<8. Setting Parameters>8-25IM 01C27F01-01ENTable 8.4 Diagnostic Results SummaryDiagnostic Status ContentsAlertTypeNAMUR NE107 CategoryDiag
<8. Setting Parameters>8-26IM 01C27F01-01EN8.4.3 Checking with Integral IndicatorNOTEIf an error is detected by running self-diagnostics,
<1. Introduction>1-2IM 01C27F01-01ENFunctional grounding terminalCautionThis symbol indicates that the operator must refer to an explanatio
<9. Maintenance>9-1IM 01C27F01-01EN9. Maintenance9.1 OverviewWARNING Since the accumulated process uid may be toxic or otherwise harmfu
<9. Maintenance>9-2IM 01C27F01-01ENTable 9.1 Instruments Required for CalibrationName Yokogawa-recommended Instrument RemarksProvisioning
<9. Maintenance>9-3IM 01C27F01-01ENPReference pressurePressure generatorSupply pressurePReference pressurePrecision digital manometerPressu
<9. Maintenance>9-4IM 01C27F01-01EN9.4.1 Replacing the Integral IndicatorThis subsection describes the procedure for replacing an integral
<9. Maintenance>9-5IM 01C27F01-01EN4) Use a socket driver (width across ats, 5.5 mm) to loosen the two bosses.5) Carefully pull the CPU
<9. Maintenance>9-6IM 01C27F01-01EN Reassembling the Capsule Assembly1) Reattach the transmitter section to the pressure-detector sectio
<9. Maintenance>9-7IM 01C27F01-01EN Assembling1) Insert new batteries into the battery case. Be careful of the orientation of the batter
<9. Maintenance>9-8IM 01C27F01-01EN How to replace and dispose of the batteries:This is an explanation about the new EU Battery Directive
<9. Maintenance>9-9IM 01C27F01-01EN9.5.2 Troubleshooting FlowchartsCheck display of the error code.Check self-diagnostics by the device co
<9. Maintenance>9-10IM 01C27F01-01ENConnect the device configuration tool and check self-diagnostics.Contact Yokogawa service personnel.F09
<1. Introduction>1-3IM 01C27F01-01EN1.2 Radio WaveIMPORTANT- This instrument is equipped with a wireless module which is designated as a
<9. Maintenance>9-11IM 01C27F01-01EN9.5.3 Errors and CountermeasuresVarious diagnostics of the Al2 object and the static pressure is not s
<9. Maintenance>9-12IM 01C27F01-01ENIntegral indicatorFactory NAMUR categoryBitDiagnostic StatusDiagnostic Status Detail CauseRelease/recov
<9. Maintenance>9-13IM 01C27F01-01ENIntegral indicatorFactory NAMUR categoryBitDiagnostic StatusDiagnostic Status Detail CauseRelease/recov
<9. Maintenance>9-14IM 01C27F01-01ENTable 9.4 Error Message Summary (Output Actions)Integral IndicatorFactory NAMUR categoryBitDiagnostic
<9. Maintenance>9-15IM 01C27F01-01ENIntegral IndicatorFactory NAMUR categoryBitDiagnostic StatusDiagnostic Status DetailOutput actionsPress
<9. Maintenance>9-16IM 01C27F01-01ENIntegral IndicatorFactory NAMUR categoryBitDiagnostic StatusDiagnostic Status DetailOutput actionsPress
<10. Parameter Summary>10-1IM 01C27F01-01EN10. Parameter SummaryThe setting of differential pressure (Al2 block) is invalid in this instru
<10. Parameter Summary>10-2IM 01C27F01-01ENObjectIDAttribute IDLabel DescriptionDefaultvalueHandling1.UAPMO block(continued)104 Reset Energ
<10. Parameter Summary>10-3IM 01C27F01-01ENObjectIDAttribute IDLabel DescriptionDefaultvalueHandling1.UAPMO block(continued)120 Callibratio
<10. Parameter Summary>10-4IM 01C27F01-01ENObjectIDAttribute IDLabel DescriptionDefaultvalueHandling3.COblock(continued)3 COMM_CONTRACTIndi
<1. Introduction>1-4IM 01C27F01-01EN1.5 ATEX DocumentationThis is only applicable to the countries in European Union.GBDKIENLSFPFDSLTLVPLE
<10. Parameter Summary>10-5IM 01C27F01-01ENObjectIDAttribute IDLabel DescriptionDefaultvalueHandling4.TRANSDUCERblock(continued)10 Special
<10. Parameter Summary>10-6IM 01C27F01-01ENObjectIDAttribute IDLabel DescriptionDefaultvalueHandling5.AI1 block (continued)29 Transducer Va
<10. Parameter Summary>10-7IM 01C27F01-01ENObjectIDAttribute IDLabel DescriptionDefaultvalueHandling5.AI1 block (continued)106 H/L Swap All
<10. Parameter Summary>10-8IM 01C27F01-01ENObjectIDAttribute IDLabel DescriptionDefaultvalueHandling6.AI2 block (continued)51 Upper Limit I
<10. Parameter Summary>10-9IM 01C27F01-01ENObjectIDAttribute IDLabel DescriptionDefaultvalueHandling7.AI3 block1 Process Value Al3 is a tem
<10. Parameter Summary>10-10IM 01C27F01-01ENTable 10.2 Diagnostic Status Detail [0]Bit Diagnostic Status Detail DescriptionDiagnostic Stat
<11. General Specications>11-1IM 01C27F01-01EN11. General Specications11.1 Standard SpecicationsCommunication protocol: ISA100.11a pro
<11. General Specications>11-2IM 01C27F01-01ENWorking Pressure Limits (Silicone oil): Maximum Pressure LimitsPressureCapsule EJX510B EJX5
<11. General Specications>11-3IM 01C27F01-01EN11.2 Model and Sufx CodesModel Sufx Codes DescriptionEJX510BEJX530B . . . . . . . . . . .
<11. General Specications>11-4IM 01C27F01-01EN11.3 Optional Specications OPTIONAL SPECIFICATIONS (For Explosion Protected type) Item D
<2. Handling Cautions>2-1IM 01C27F01-01EN2. Handling CautionsThis chapter provides important information on how to handle the transmitter.
<11. General Specications>11-5IM 01C27F01-01EN11.4 DimensionsUnit: mm (approx. inch)72(2.83)282*5 (11.10)162 (6.38)202 (7.95)40(1.57)140