Yokogawa YFGW510 User Manual Page 77

  • Download
  • Add to my manuals
  • Print
  • Page
    / 89
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 76
<F2. Status Indication and Responsive Measures>
F2-1
IM 01W02E01-01EN
F2. Status Indication and Responsive
Measures
There are six status indicator LEDs installed on the front of YFGW510: [ACT], [LAN], [ISA],
[WLAN-C1], [WLAN-C2] and [WLAN-AP].
n YFGW510 operational status indication
The following is the LED that indicates the YFGW510 operational status.
LED Power off Starting up
Connect-
ing
Normal
Mainte-
nance
Abnormal
ACT OFF Orange
Orange
blink
Green Red blink Red
The LED blinks red when the device mode is changed to Edit mode via the infrared adapter using
the setup tool to congure YFGW510.
If the LED lights red, check the eld wireless backbone network cable connection and commu-
nication devices such as the Layer 2 switch, etc., and x any abnormalities. If there is no abnor-
mality found in cable connection, check the backbone router status information described in F1.
Status Information and device information by the Monitor. Any abnormality found may indicate
the breakdown of YFGW510. For details of the YFGW510 device replacement method, see the
YFGW410 Users Manual (IM 01W02D01-01EN).
n Communication status indication
The following are the LEDs that indicate communication status.
LED Power off
Starting
up
Signal
search
Link
down
Link up
Commu-
nicating
Mainte-
nance
Abnor-
mal
LAN OFF OFF N/A OFF Green
Green
blink
OFF Red
ISA OFF OFF N/A N/A Green
Green
blink
OFF Red
WLAN-C1 OFF OFF
Orange
blink
OFF
Green
blink
Green OFF Red
WLAN-C2 OFF OFF
Orange
blink
OFF
Green
blink
Green OFF Red
WLAN-AP
n [LAN] LED
If the LED turns off during operation, it may indicate that communication between YFGW510 and
the YFGW410eld wireless backbone network has been terminated. Investigate the commu-
nication cable connection and the status of communication devices such as the Layer 2 switch,
etc., and re-establish communication.
If the LED lights red, it may indicate the breakdown of the communication function of YFGW510.
Replace the main body or consult with Yokogawa Electric Corporation.