Yokogawa Data Acquisition with PID Control CX2000 User Manual

Browse online or download User Manual for Sensors Yokogawa Data Acquisition with PID Control CX2000. Yokogawa Data Acquisition with PID Control CX2000 User Manual [en]

  • Download
  • Add to my manuals
  • Print
  • Page
    / 321
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews

Summary of Contents

Page 1 - Communication Interface

User’sManualYokogawa Electric CorporationDAQSTATION CX1000/CX2000Communication InterfaceIM 04L31A01-17E6th Edition

Page 2 - 6th Edition : June 2010 (YK)

ixIM 04L31A01-17ESetup Procedure Using Operation KeysBelow is the basic flow of operations when changing the settings of the CX2000 usingthe front pan

Page 3 - Revisions

4-6 IM 04L31A01-17E• Commu. Data (First, Last)Specify which communication input data will be assigned the data that is read fromthe slave device (C01

Page 4 - Safety Precautions

4-7IM 04L31A01-17E4Modbus Protocol• UINT32_BSpecify this type when a “32-bit unsigned integer” is assigned to the Modbusregister in the order upper 16

Page 5 - Exemption from Responsibility

4-8 IM 04L31A01-17EProcedureFor the basic flow of operation, see “Setup Procedure Using Operation Keys” on pageix. For the procedure of entering char

Page 6 - How to Use This Manual

4-9IM 04L31A01-17E4Modbus ProtocolSelecting the Number of Retrials9. Use the arrow keys to move the cursor to the [Retrials] box.10. Press one of the

Page 7

4-10 IM 04L31A01-17E• Setting the register number of the slave device20. Use the arrow keys to move the cursor to the [Registers] box.21. Press the [I

Page 8 - Using the Operation Keys

4-11IM 04L31A01-17E4Modbus Protocol4.4 Checking the Operation Status of the ModbusMaster FunctionExplanation”MODBUS STATUS” DisplayYou can check the o

Page 9 - Rear Panel

4-12 IM 04L31A01-17EProcedureDisplaying the “Modbus Master Status” Screen1. Press the FUNC key. The FUNC menu appears. The structure of the FUNCmenu

Page 10 - The parameter box containing

4-13IM 04L31A01-17E4Modbus Protocol4.5 Communications as a Modbus SlaveThis section explains the command messages used when setting the CX to Modbussl

Page 11 - The setup item boxes that

4-14 IM 04L31A01-17EBroadcast RequestBroadcast request is a function used to write the same data collectively to the holdregisters of all the Modbus s

Page 12 - Contents

4-15IM 04L31A01-17E4Modbus Protocol• ResponseSlaveaddressFunctioncodeBytecounterRegistercontent(Low)Registercontent(High)Registercontent(Low)Errorchec

Page 13 - Chapter 4 Modbus Protocol

x IM 04L31A01-17ENames and Uses of Parts and Setup Procedures Using the Operation Keys6. The operation varies depending on whether you wish to confirm

Page 14 - Chapter 6 Command

4-16 IM 04L31A01-17E4.6 Modbus Slave Error ResponsesMessage Format for ErrorsIf an invalid command other than those determined as communication error

Page 15 - Chapter 7 Response

5-1IM 04L31A01-17E5Ladder Communication Protocol5.1 Ladder Communication ProtocolSpecificationsThe ladder communication protocol can be used over the

Page 16 - Chapter 8 Status Reports

5-2 IM 04L31A01-17E5.2 Setting the Ladder Communication ProtocolExplanationThe CX supports the ladder communication protocol. Multiple CXs can be con

Page 17 - Appendix

5-3IM 04L31A01-17E5Ladder Communication ProtocolProcedureFor the basic flow of operation, see “Setup Procedure Using Operation Keys” on page ix.1. Pre

Page 18

5-4 IM 04L31A01-17E10. Press one of the soft keys from [1] to [32] to select the address.This value is the station number of the ladder communication

Page 19 - E-mail Transmission

5-5IM 04L31A01-17E5Ladder Communication Protocol5.3 Communications with PLCsWhen performing ladder communications, make sure the PLC (host) first send

Page 20 - Web Server

5-6 IM 04L31A01-17E•0This position is fixed to 0.•5th digitThe most significant digit when using 5-digit notation.• R/WSpecifies whether the command i

Page 21 - FTP Client

5-7IM 04L31A01-17E5Ladder Communication ProtocolResponse against a write commandNumber of BCD Digits Command Element22411114Station numberCPU number (

Page 22 - FTP Server

5-8 IM 04L31A01-17E5.4 Communication Program for FA-M3Below is a program example for communications between the CX and the FA-M3Sequencer by YOKOGAWA.

Page 23 - Instrument Information Server

5-9IM 04L31A01-17E5Ladder Communication Protocol(0006)(0007)(0009)(0010)(0008)00008NSet the communication modeCharacter code = 8Stop bit = 1Parity bit

Page 24 - DAQSTANDARD for CX

xiIM 04L31A01-17E123456789AppIndexContentsSafety Precautions ...

Page 25 - Other Functions

5-10 IM 04L31A01-17E(0020)(0022)(0021)00033NRead measurementinputIO in executionProcess for alternating data read and data write operationsX00303 I004

Page 26 - Green Series Communications

5-11IM 04L31A01-17E5Ladder Communication Protocol(0032)(0034)(0033)00061NNumber of transmittedcharacters = 10STN = 01, CPU = 01Read data of CX2000 com

Page 27 - Serial communications

5-12 IM 04L31A01-17E(0046)(0048)(0047)00090NNumber of transmittedcharacters = 10 byteWrite destination = 01Command = WriteTransmission destinationSTN

Page 28 - Modbus Slave

5-13IM 04L31A01-17E5Ladder Communication Protocol5.5 Communication Program for MELSECBelow is a program example for communications between the CX and

Page 29

5-14 IM 04L31A01-17EProgram Example• Transmission interval processingC0SM10384IntervalcounterIntervalcounter<Reset counter>RST C0On for 1 scanon

Page 30 - Communication with PCs

5-15IM 04L31A01-17E5Ladder Communication Protocol• Read command transmission processing: If M601 is ON, send a command tolead CH1 to 4.M601 X27 Y27113

Page 31 - Basic Specifications

5-16 IM 04L31A01-17E• Reception processing: Receive data of CH1 to 4.X2A341FROMP H2 H0A00 D100 K1FROMP H2 H0A01 D101 K0Z0MOVP D100 Z0ReadrequestflagCP

Page 32

5-17IM 04L31A01-17E5Ladder Communication Protocol• Write processing: If M602 is set, write the CH1 data to communication register C1.M602 X27 Y27627MO

Page 33

5-18 IM 04L31A01-17E• Read command transmission processing: If M603 is ON, send a command tolead CH5 to 8.M603 X27 Y27866MOVP H5 D0MOVP H102 D1MOVP H5

Page 34

5-19IM 04L31A01-17E5Ladder Communication Protocol• Reception processing: Receive the data of CH5 to CH8.X2A1084FROMP H2 H0A00 D200 K1FROMP H2 H0A01 D2

Page 35 - user’s manual IM

xii IM 04L31A01-17EChapter 3 Serial Interface3.1 Serial Interface Specifications ...

Page 36

6-1IM 04L31A01-17ECommand66.1 Command SyntaxCommand SyntaxThe syntax of the setting/basic setting/control/output commands (see sections 6.4 to6.12) us

Page 37

6-2 IM 04L31A01-17E• Channel number01 to 20: Measurement channels (01 to 06 on the CX1000)31 to 60: Computation channels (31 to 42 on the CX1000)101 t

Page 38

6-3IM 04L31A01-17ECommand6ResponseThe CX returns a response (affirmative/negative response) to a command that isdelimited by a single terminator.* Th

Page 39 - Indicator

6-4 IM 04L31A01-17E6.2 A List of CommandsSetting Commands (Control)Command Command Function Execution mode ADMINISTRATOR USER PageType NameControl Inp

Page 40

6-5IM 04L31A01-17ECommand6Command Command Function Execution mode ADMINISTRATOR USER PageType NameEvent SettingET Sets the time event Operation mode Y

Page 41 - IM04L31A01-03E

6-6 IM 04L31A01-17ESetting Commands (Measurement)Command Command Function Execution mode ADMINISTRATOR USER PageType NameSettingsSR Sets the input ran

Page 42 - IM04L31A01-01E

6-7IM 04L31A01-17ECommand6Note• There are two execution modes on the CX. If you attempt to execute a command in a modethat is different from the spec

Page 43

6-8 IM 04L31A01-17EBasic Setting Commands (Measurement)• In order to activate the settings that are changed using the basic setting commands,the setti

Page 44

6-9IM 04L31A01-17ECommand6Command Function Execution mode ADMINISTRATOR USER PageNameYO Loads setup data Basic setting mode Yes No 6-46YC Clears the m

Page 45

6-10 IM 04L31A01-17ECommand Command Function Execution mode ADMINISTRATOR USER PageType NameExternal Loop Setting (Basic Setting)GJ Specifies external

Page 46 - 2.6 FTP Test

xiiiIM 04L31A01-17E123456789AppIndexChapter 6 Command6.1 Command Syntax ...

Page 47 - Ethernet Communications

6-11IM 04L31A01-17ECommand6Command Command Function Execution mode ADMINISTRATOR USER PageType NameSetup, Measurement, and computation Data OutputFC O

Page 48

6-12 IM 04L31A01-17EMaintenance/Test Commands (Available when using the maintenance/test serverfunction via Ethernet communications)Command Name Funct

Page 49

6-13IM 04L31A01-17ECommand66.3 Input Range ParameterThe following tables show which measurement ranges of the instrument correspond tothe input types

Page 50

6-14 IM 04L31A01-17E6.3 Input Range ParameterON/OFF input (DI)Measurement Range Parameter for the Upper and Lower Upper and Lower LimitsCR/SR Command

Page 51

6-15IM 04L31A01-17E6Command6.4 Setting Commands (Control)Control Input RangeCR Set the control rangeWhen p1 = 1 to 6 (When internal loop is specified)

Page 52 - Log Screens

6-16 IM 04L31A01-17EWith the switching method of loop 2 set to“PVHigh,” set the items as follows: PV rangelower limit: –10000, upper limit: 20000, PVs

Page 53

6-17IM 04L31A01-17E6CommandMF FilterWhen the PV/SP Computation Function is OFFSyntax MF p1,p2,p3,p4<terminator>p1: Loop number (1 to 6) (1 or 2

Page 54

6-18 IM 04L31A01-17EHH Sets the SP ramp-up-rateSyntax HH p1,p2,p3<terminator>p1: Loop number (1 to 6) (1 or 2 on the CX1000)p2: Enable/disable S

Page 55

6-19IM 04L31A01-17E6CommandNo ON/OFF ControlSyntax HO p1,p2,p3,p4,p5,p6,p7<terminator>p1: Loop number (1 to 6) (1 or 2 on the CX1000)p2: PID num

Page 56

6-20 IM 04L31A01-17EWhen PV/SP Computation Function is ONSyntax HE p1,p2,p3,p4<terminator>p1: Control input channel numbers (CI01–CI10,or CI01–C

Page 57

xiv IM 04L31A01-17E6.8 Basic Setting Commands (Control) ... 6-49Control Acti

Page 58 - CX1000 Web setting display

6-21IM 04L31A01-17E6CommandPT Sets the segment timeSyntax PT p1,p2<terminator>p1: Segment number (1 to 99)p2: Segment time (hh:mm:ss fixed forma

Page 59

6-22 IM 04L31A01-17EDescription • When p3 is set to On1, p4 and p5 are handledas On-time and Off-time, respectively.• When p3 is set to On2, p4 is han

Page 60

6-23IM 04L31A01-17E6CommandDetail Settings (Control FunctionSettings)HF Sets the setpointSyntax HF p1,p2,p3,p4,p5<terminator>p1: Loop number (1

Page 61

6-24 IM 04L31A01-17Ep4: Internal switch number (SW001-SW036, orSW001-SW018 for the CX1000)p5: ON DO number (DI001-DI006, DI101-DI106, DI201-DI206, RI0

Page 62 - Refresh the data

6-25IM 04L31A01-17E6CommandDetailed Settings (DI/DO Label Settings)DW Sets the DI/DO labelSyntax DW p1,p2,p3<terminator>p1: DI/DO typesCTRL1-DO,

Page 63 - Select the log

6-26 IM 04L31A01-17EExternal Loop PID Parameter SettingsDT Sets the external loop PIDparameterSyntax DT p1,p2,p3,p4<terminator>p1: Loop number (

Page 64 - CX2000 screen example

6-27IM 04L31A01-17E6CommandRL: Select remote/local0: Local operation1: Remote operation (cannot beselected in the following cases.UT420/UT450/UT520/UT

Page 65

6-28 IM 04L31A01-17Ep4: Measurement rangep5: Span lower limitp6: Span upper limitp7: Reference channel: 01 to 20 (01 to 06 onthe CX1000)Query SR[ p1]?

Page 66

6-29IM 04L31A01-17E6CommandExample Set the computation channel to 31, thecomputation to ON, the computing equation tothe sum of channel 01 and 02, spa

Page 67

6-30 IM 04L31A01-17E• For computation channels, the alarm typesthat can be specified are only H (high limitalarm), L (low limit alarm), T (delay high

Page 68

xvIM 04L31A01-17E123456789AppIndex7.3 Output Format of BINARY Data ...

Page 69

6-31IM 04L31A01-17E6Command• This command cannot be specified if thepartial expanded display range does not exist(when the span width is set to 1, for

Page 70

6-32 IM 04L31A01-17E6.5 Setting Commands (Measurement)Example Set the display direction of the trend waveform tohorizontal, the direction of the bar g

Page 71

6-33IM 04L31A01-17E6Command6.5 Setting Commands (Measurement)SY Sets the 4 screen display(CX2000 only)Syntax SY p1,p2,p3,p4,p5,p6,p7,p8,p9,p10<term

Page 72

6-34 IM 04L31A01-17E6.5 Setting Commands (Measurement)• This command cannot be specified whilemeasurement/computation is in progress orwhile a report

Page 73

6-35IM 04L31A01-17E6CommandExample Set the summer time to the 23rd hour of June 30,2000.SSSUMMER,ON,00/06/30 23(The 23rd hour of June 30, 2000 is set

Page 74

6-36 IM 04L31A01-17E6.6 Setting Commands (Operation)6.6 Setting Commands(Operation)UD Switches the screenWhen switching the screen back to the screen

Page 75

6-37IM 04L31A01-17E6Commandp8: Display item on the lower right screen(screen 4) (same selections as p2)p9: Number of the group to be displayed on thel

Page 76

6-38 IM 04L31A01-17E6.6 Setting Commands (Operation)Description • EV3 is valid when display data are beingacquired to the internal memory, and the CXi

Page 77 - 2.12 E-mail Transmission Test

6-39IM 04L31A01-17E6CommandLI Saves the setup dataSyntax LI p1<terminator>p1: File name (up to 8 characters)Example Save the setup data of both

Page 78

6-40 IM 04L31A01-17E6.7 Basic Setting Commands (Measurement)6.7 Basic Setting Commands(Measurement)• To activate the settings that are changed using t

Page 79

xvi IM 04L31A01-17EAppendixAppendix 1 ASCII Character Codes ... App-1Ap

Page 80 - Switch Communication Buffer

6-41IM 04L31A01-17E6CommandXV Sets the scan intervalSyntax XV p1<terminator>p1: Scan interval1S, 2SQuery XV?Example Set the scan interval to 1 s

Page 81 - RS-422/485 Specifications

6-42 IM 04L31A01-17E6.7 Basic Setting Commands (Measurement)XR Sets the remote actionSyntax XR p1,p2<terminator>p1: Remote number (1 to 8)p2: Re

Page 82 - Connection Procedure

6-43IM 04L31A01-17E6CommandFor hourly, daily, hourly + daily and daily +monthly reportsSyntax RO p1,p2,p3<terminator>p1: Report type (HOUR, DAY,

Page 83 - Handshaking

6-44 IM 04L31A01-17E6.7 Basic Setting Commands (Measurement)XO Selects the communicationinterface used to output dataresiding in the internal memory(d

Page 84

6-45IM 04L31A01-17E6CommandYA Sets the IP address, subnetmask, and default gatewaySyntax YA p1,p2,p3<terminator>p1: IP address (0.0.0.0 to 255.2

Page 85 - Interface

6-46 IM 04L31A01-17E6.7 Basic Setting Commands (Measurement)YO Loads setup dataSyntax YO p1<terminator>p1: File name (up to 8 characters)Example

Page 86

6-47IM 04L31A01-17E6Commandp6: First register number (30001 to 39999,40001 to 49999, 300001 to 365535, 400001to 465535)p7: Type of data assigned to th

Page 87

6-48 IM 04L31A01-17EExample Send report generation notification e-mailmessages including the source URL to recipient1. The subject is “Report”, and t

Page 88 - (for a four-wire system)

6-49IM 04L31A01-17E6Command6.8 Basic Setting Commands(Control)Control Action, Input SettingGB Sets the PID group numberSyntax GB p1<terminator>p

Page 89

6-50 IM 04L31A01-17E6.8 Basic Setting Commands (Control)MK Burnout settingsSyntax MK p1,p2<terminator>p1: Control input channel numbers (CI01–CI

Page 90

1-1IM 04L31A01-17EFunctional Explanation11.1 Overview of the Communication FunctionsThe CX comes with the Ethernet Interface as standard. A serial in

Page 91 - Memory out) setting display

6-51IM 04L31A01-17E6CommandGS Sets remote inputSyntax GS p1,p2<terminator>p1: Loop number (1 to 6) (1 or 2 on the CX1000)p2: Remote input(Off, R

Page 92

6-52 IM 04L31A01-17E6.8 Basic Setting Commands (Control)Tuning SettingGU Turns Off/On the tuning itemSyntax GU p1,p2,p3,p4,p5,p6,p7,p8,p9<terminato

Page 93

6-53IM 04L31A01-17E6CommandGH External loop parameter 1,control span lower/upper limitSyntax GH p1,p2,p3<terminator>p1: Loop number (Ext1 to Ext

Page 94

6-54 IM 04L31A01-17E6.9 Control CommandsControl CommandsCA Switches between auto, manual,and cascade controlSyntax CA p1,p2<terminator>p1: Switc

Page 95

6-55IM 04L31A01-17E6Command6.10 Output Commands(Measurement-Control)BO Sets the byte output orderSyntax BO p1<terminator>p1: Byte order0: Output

Page 96

6-56 IM 04L31A01-17EFD Outputs the newest measured/computed/control dataSyntax FD p1,p2,p3<terminator>p1: Output data type0 Output the newest me

Page 97

6-57IM 04L31A01-17E6CommandFS Outputs alarm kind and alarmsetting value for measurement/computation/control channelSyntax FS p1,p2<terminator>p1

Page 98

6-58 IM 04L31A01-17EMI Outputs display data and eventdata in the internal memorySyntax MI p1,p2,p3,p4<terminator>p1: Operation typeDIR Put the d

Page 99

6-59IM 04L31A01-17E6Command6.12 Output Commands(Measurement-RS-422/485Dedicated Commands)ESC O Opens the deviceESC is the character 1BH expressed usin

Page 100 - Communication input

6-60 IM 04L31A01-17E6.13 Output Commands (Control)FJ Outputs program patterninformation that is currently inexecution.Syntax FJ<terminator>Examp

Page 101 - 04L31A01-03E

1-2 IM 04L31A01-17E1.2 Ethernet Communication FunctionThe CX comes with an Ethernet interface as standard. The interface can be used toconnect to a p

Page 102 - IM 04L31A01-03E

6-61IM 04L31A01-17E6CommandFV Outputs the status of theprogram control end signal.Syntax FV p1<terminator>p1: Program parameter numbers (1–30)1–

Page 103 - Operation Keys” on page ix

6-62 IM 04L31A01-17Eeth Outputs Ethernet statisticalinformationSyntax eth<terminator>ExampleethEA00/00/00 12:34:56Ethernet StatisticsName In Pkt

Page 104

6-63IM 04L31A01-17E6Command6.15 Instrument Information Output Commands6.15 Instrument InformationOutput Commands(Available when using theinstrument in

Page 105 - Master Function

7-1IM 04L31A01-17E7Response7.1 Response SyntaxThe following table shows the types of responses for the various commands described inthe previous chapt

Page 106 - IM 04L31A01-17E

7-2 IM 04L31A01-17EASCII OutputThe following types of ASCII data are available. For a description of the data formats,see section 7.2.Setting/basic s

Page 107 - Command Message Construction

7-3IM 04L31A01-17E7ResponseFlagFlagBit Name (Abbreviation) Meaning of the Flag017BO MSB LSB Output byte order6CSNoYes Presence of checksum5– ––4– ––3–

Page 108 - Function Code

7-4 IM 04L31A01-17ECalculating the Sum ValueIf you set the parameter of the CS command to “1 (enabled),” the checksum value isoutput only during seria

Page 109

7-5IM 04L31A01-17E7ResponseRS-422/485 Dedicated Commands and ResponsesThe following table shows dedicated commands for the RS-422/485 interface and th

Page 110 - Response Error Codes

7-6 IM 04L31A01-17E7.2 Output Format of ASCII DataThe following types of ASCII data are available. The format for each type is described inthis secti

Page 111 - Specifications

7-7IM 04L31A01-17E7ResponseSetting Data/Basic Setting Data• The FE command is used to output the data.• The setting/basic setting data are output in t

Page 112 - Address NO

iIM 04L31A01-17EThank you for purchasing the CX1000/CX2000 (CX).This user’s manual contains useful information about the communication function(Ethern

Page 113

1-3IM 04L31A01-17EFunctional Explanation1EthernetE-mailtransmissionE-mailreceptionPortable phonePCFTP serverInternetCXNote• For the procedure in setti

Page 114

7-8 IM 04L31A01-17EDecimal Point Position/Unit Information• The FE command is used to output the data.SyntaxThe data is output for each channel in the

Page 115 - 5.3 Communications with PLCs

7-9IM 04L31A01-17E7ResponseMeasured/Computed/Control Data• The FD command is used to output the data.SyntaxThe measured/computed/control data is outpu

Page 116 - Response

7-10 IM 04L31A01-17Euuuuuu Unit information (6 characters, left-justified)mV____: mVV_____: V^C____: °Cxxxxxx: (User-defined character string)f Sign (

Page 117 - Response When Errors Occur

7-11IM 04L31A01-17E7ResponseControl Mode Output• Output data using an FM command for internal loops, or a DR command for externalloops..• The status o

Page 118 - (F3RZ81-0N, F3RZ91-0N)

7-12 IM 04L31A01-17EProgram Operatin Mode Output• The FH command is used to output the data.• The status of the program operation mode is output. The

Page 119

7-13IM 04L31A01-17E7ResponsePTNO Pattern number in operation x1 (1 to 30)SEGNO Segment number in operation x2 (1 to 99)PRE_SEGNO Segment number used p

Page 120 - 5-10 IM 04L31A01-17E

7-14 IM 04L31A01-17EExampleEAPTNO 5SEGNO 10PRE_SEGNO 2SEGUSE 7SEGTM 11:05:22WAITTM 00:06:00RCYMOD 1ALL_RCY 20REM_RCY 2RST 3REN 6PTN_START_DATE 02/01/0

Page 121 - Ladder Communication Protocol

7-15IM 04L31A01-17E7ResponseStatus of the Program Control End Signal• The FV command is used to output the data.• The program control end signal is t

Page 122

7-16 IM 04L31A01-17Emmm...m Message (up to 20 characters)• The communication log contains only the error number and not theerror message section.• Nor

Page 123

7-17IM 04L31A01-17E7ResponseFTP Log• The FL command is used to output the data.• The FTP client log is output. Up to 50 file transfer logs are retain

Page 124 - Program Example

1-4 IM 04L31A01-17EEthernetHTTPcommunicationsPCWeb browserWeb serverCXThe information that is displayed on the Web browser can be updated manually ora

Page 125

7-18 IM 04L31A01-17EOperation Error Log• The FL command is used to output the data.• The operation error log is output. Up to 50 operation error logs

Page 126 - 5-16 IM 04L31A01-17E

7-19IM 04L31A01-17E7ResponseExampleEA99/05/11 12:20:00 In 01 administrator99/05/11 12:30:00 Out99/05/11 12:20:00 In 03 user99/05/11 12:30:00 OutENWe

Page 127

7-20 IM 04L31A01-17E• When ffffff = MSGyy/mo/dd_hh:mi:ss_ffffff_eee_nn_mmm...CRLFnn Message number (01 to 08)mmm... Message (up to 16 characters)_ Spa

Page 128 - 5-18 IM 04L31A01-17E

7-21IM 04L31A01-17E7ResponseAlarm Summary• The FL command is used to output the data.• The alarm summary is output. Up to 120 alarm information sets

Page 129

7-22 IM 04L31A01-17EMessage Summary• The FL command is used to output the data.• The message summary is output. Up to 100 messages are retained. Mes

Page 130 - 6.1 Command Syntax

7-23IM 04L31A01-17E7ResponseFile List• The ME command is used to output the data.• The file list and the file data sizes of the specified directory on

Page 131

7-24 IM 04L31A01-17EData List• The MI/MO command is used to output the data.• The number of blocks and file names of the specified data in the interna

Page 132

7-25IM 04L31A01-17E7ResponseUser Level• The FU command is used to output the data.• User name, user level, and other information are output.SyntaxEACR

Page 133 - 6.2 A List of Commands

7-26 IM 04L31A01-17E7.3 Output Format of BINARY DataThis section describes the output format of the BINARY data that is disclosed.For information on o

Page 134

7-27IM 04L31A01-17E7Response• FlagThe meaning of the flags are given on the table below. The flags are valid duringFIFO data output. The flags are u

Page 135 - 6-6 IM 04L31A01-17E

1-5IM 04L31A01-17EFunctional Explanation1FTP serverPrimary SecondaryEthernetTransfer destination(FTP server)informationTransfer log(FTP log)Data file

Page 136

7-28 IM 04L31A01-17EDisplay Data• The MI command is used to output the FIFO data.• The ID number of the output format is “11.” See “Identifier” on pa

Page 137

7-29IM 04L31A01-17E7ResponseBlock2 bytesMeasured data. . .. . .Computed data. . .. . .2 bytes4 bytes4 bytesMIN valueMAX valueComputed data. . .. . .Me

Page 138

7-30 IM 04L31A01-17EEvent Data• The MI command is used to output the FIFO data.• The ID number of the output format is “12.” See “Identifier” on page

Page 139 - Output Commands (Measurement)

7-31IM 04L31A01-17E7ResponseDI/DO Data and Internal Switch Status (Style Number S3 Or Later)• DI/DO data and the internal switch status can be output

Page 140 - Output Commands (Control)

7-32 IM 04L31A01-17EExpansion DI01–3 (4 bytes)bit0: DI 0 (1:ON, 0:OFF)bit1: DI 1 (1:ON, 0:OFF):bit11: DI 11 (1:ON, 0:OFF)bit12–bit 15:0bit16: DO 0 (1:

Page 141 - 6-12 IM 04L31A01-17E

7-33IM 04L31A01-17E7ResponseCX1000DIO1-6DIO1DIO7DIO1-6DIO1-6DIO1-6DIO7-12DIO2DIO8DIO7-12DIO7-12DIO7-12DIO3DIO9DIO4DIO10DIO5DIO11DIO6DIO121 byte 1 byte

Page 142 - 6.3 Input Range Parameter

7-34 IM 04L31A01-17EInput Status of DIO Operation MonitoringDI01–6 (1 byte)bit0: Input status of DIO operation monitoring 1 (0: OFF, 1: ON).bit1: Inpu

Page 143

7-35IM 04L31A01-17E7ResponseNumber and Operation Status of the Currently Running Program Patterns (StyleNumber 3 or Later)• The number, operation stat

Page 144 - CR Set the control range

7-36 IM 04L31A01-17ECX1000bit0: Loop 1 (1:assigned, 0: unassigned)bit1: Loop 2 (1:assigned, 0: unassigned)bit2–bit7: 0Measurement/Computation/Control

Page 145 - MP Control setting range

7-37IM 04L31A01-17E7ResponseNote• Information for skipped measurement channels, computation channels whencomputation is turned OFF, and control channe

Page 146

1-6 IM 04L31A01-17ESetting/Measurement ServerThe settings on the CX can be changed or the data on the CX can be output to your PC,by sending commands

Page 147 - 6-18 IM 04L31A01-17E

7-38 IM 04L31A01-17EDecimal point positionThe decimal point position of each channel’s input spanLower limit of spanThe lower limit value of each chan

Page 148 - HD Sets the derivative time

7-39IM 04L31A01-17E7Response7.4 Output Format of Instrument InformationThis section describes the instrument information output format of the instrume

Page 149

8-1IM 04L31A01-17E8Status Reports8.1 Status Information and FilterThe following figure depicts the status information and filter on the CX.Status info

Page 150 - Query PW[ p1]?

8-2 IM 04L31A01-17E8.2 Bit Structure of the Status InformationThe following four groups of status information are output in response to a statusinform

Page 151 - 6-22 IM 04L31A01-17E

9-1IM 04L31A01-17E9Green Series Communications9.1 Specifications of the Green SeriesCommunication FunctionCommunication ProtocolMODBUS communication R

Page 152

9-2 IM 04L31A01-17EVarious Setting Displays for the Green Series Communication FunctionParameters can be entered on various displays including Externa

Page 153 - When set to DIO-12 or DIO-12P

9-3IM 04L31A01-17E9Green Series CommunicationsExternal Loop Setting (Tuning Setting) DisplayYou can set up to 21 turning parameters.• When the connect

Page 154

9-4 IM 04L31A01-17E9.2 Setup Procedure of the Green SeriesCommunication FunctionSet up the Green Series communications in the following order.1. Conne

Page 155 - 6-26 IM 04L31A01-17E

9-5IM 04L31A01-17E9Green Series Communications9.3 Setting the Modbus MasterSetting the ProtocolTo perform Green Series communications, set the protoco

Page 156 - (Measurement)

9-6 IM 04L31A01-17E9.4 External Loop Setting > Basic SettingExplanationExternal loop control refers to operating and monitoring of control loops of

Page 157 - 6-28 IM 04L31A01-17E

1-7IM 04L31A01-17EFunctional Explanation1DAQSTANDARD for CXBy using the DAQSTANDARD for CX, you can easily use the setting/measurementserver, maintena

Page 158

9-7IM 04L31A01-17E9Green Series CommunicationsExecuting Auto Reading• When the connecting model is UT Series• Various setup information can be automat

Page 159 - SZ Sets the zone

9-8 IM 04L31A01-17E• Control mode• If the connecting model is UT series, select from the below. However, the selectableitems vary depending on the co

Page 160

9-9IM 04L31A01-17E9Green Series Communications• Control output type• If the connecting model is UT series, select from the following:Control Output Ty

Page 161

9-10 IM 04L31A01-17EProcedureFor the basic flow of operation, see “Setup Procedure Using Operation Keys” on page ix.1. Press the MENU key.The Setting

Page 162 - SU Sets the USER key

9-11IM 04L31A01-17E9Green Series CommunicationsSetting the Modbus Address10. Use the arrow keys to move the cursor to the [Modbus address] box.11. Pre

Page 163

9-12 IM 04L31A01-17E21. Press the DISP/ENTER key. On the CX1000, select [ENT] and then press theDISP/ENTER key.The characters that you entered are di

Page 164

9-13IM 04L31A01-17E9Green Series Communications25. If you selected a UT Series controller for the connecting model, set the controlmode, control outpu

Page 165 - (Operation)

9-14 IM 04L31A01-17E9.5 External Loop Setting > Parameter AddressSettingExplanationYou can set the register address of the setup information that i

Page 166

9-15IM 04L31A01-17E9Green Series CommunicationsProcedureFor the basic flow of operation, see “Setup Procedure Using Operation Keys” on page ix.1. Pres

Page 167 - 6-38 IM 04L31A01-17E

9-16 IM 04L31A01-17EExecuting the Auto Setting(Applicable only to UT Series.)8. Use the arrow keys to move the cursor to the [Auto setting] box.9. Pre

Page 168

1-8 IM 04L31A01-17EOther FunctionsWhen carrying out communications via the Ethernet interface, the following additionalfunctions can be used.User Cont

Page 169 - 6.7 Basic Setting Commands

9-17IM 04L31A01-17E9Green Series Communications9.6 External Loop Setting > Tuning SettingExplanationYou can set up to 21 turning parameters.NoteTo

Page 170

9-18 IM 04L31A01-17ESetting (Correcting) the Detail Information• If the data is not set correctly using auto setting, you can set (correct) the itemsu

Page 171 - RO Sets the report type and

9-19IM 04L31A01-17E9Green Series CommunicationsProcedureFor the basic flow of operation, see “Setup Procedure Using Operation Keys” on page ix.1. Pres

Page 172 - RM Sets the report channel

9-20 IM 04L31A01-17EExecuting the Auto Setting(Applicable only to UT Series.)8. Use the arrow keys to move the cursor to the [Auto setting] box.9. Pre

Page 173 - 6-44 IM 04L31A01-17E

9-21IM 04L31A01-17E9Green Series CommunicationsConfirming or Canceling the Settings13. To confirm the new settings, press the DISP/ENTER key. To canc

Page 174

9-22 IM 04L31A01-17E9.7 Checking the Operating Conditions of theGreen Series Communication FunctionExplanation“EXTLOOP STATUS” DisplayYou can check th

Page 175

9-23IM 04L31A01-17E9Green Series CommunicationsProcedureOpening the “EXTLOOP STATUS” Display1. Press the FUNC key. The FUNC menu appears. The struct

Page 176

9-24 IM 04L31A01-17E9.8 Starting the OperationNoteStart the operation after completing the following settings and checking the operating conditionsof

Page 177 - 6-48 IM 04L31A01-17E

9-25IM 04L31A01-17E9Green Series Communications9.9 Operations That You Can Carry Out duringControl OperationDuring control operation, you can show the

Page 178 - (Control)

9-26 IM 04L31A01-17E(Continuing from the previous page)Alarm Type 1-Character Indication 3-Character IndicationDeviation high-limit alarm (energize/ho

Page 179 - GT Registers contact inputs

1-9IM 04L31A01-17EFunctional Explanation11.3 Serial Communication FunctionIf you specified the RS-422/485 or RS-232 serial interface for the communica

Page 180

App-1IM 04L31A01-17EAppAppendixAppendixAppendix 1 ASCII Character Codes0123456789ABCDEF0LFCR1ESC2SP#%&()*+–./30123456789:4@ABCDEFGHIJKLMNO5PQRSTUV

Page 181 - 6-52 IM 04L31A01-17E

App-2 IM 04L31A01-17EAppendix 2 Output Flow of Internal Memory DataDisplay Data ExampleMIDIR,DISPLAYNO*1YESPut the internal memory data in standby for

Page 182

App-3IM 04L31A01-17EAppAppendixEvent data (Set *1, *2, and *3 in the previous figure to the following commands)*1: MIDIR,EVENT Output the list.*2: MIG

Page 183 - 6.9 Control Commands

App-4 IM 04L31A01-17EAppendix 3 Output Flow of the File or the File Liston the External Storage MediumExample in Which the File 10101000.CDS in the DA

Page 184

App-5IM 04L31A01-17EAppAppendixExample in Which the File List Belonging to Directory DATA0 Is Output 10 Files at aTimeMEDIR,/DATA0/,10MEDIRNEXTNOSTART

Page 185 - FF Outputs FIFO data

App-6 IM 04L31A01-17EAppendix 4 Output Flow of FIFO DataOverview of the FIFO BufferThe CX has a dedicated internal memory for outputting measured/comp

Page 186

App-7IM 04L31A01-17EAppAppendixExample in Which the FIFO Acquisition Interval on the CX Is Set to 1 s and theMeasured/Computed/Control Data from CH1 t

Page 187 - MO Outputs TLOG data, manual

App-8 IM 04L31A01-17EAppendix 5 Data Dropout during Modbus MasterIf the response to the previous command is not complete when the CX attempts to issue

Page 188 - 6.13 Output Commands

App-9IM 04L31A01-17EAppAppendixAppendix 6 Register AssignmentsRegister Assignments during Modbus SlaveThe register assignments of the Modbus slave fun

Page 189 - 6-60 IM 04L31A01-17E

App-10 IM 04L31A01-17E4060140602406034060440605406064060740608 :4083340834408354083640837408384083940840Alarm value of computation channel 1Higher 2 b

Page 190 - FV Outputs the status of the

1-10 IM 04L31A01-17EModbus MasterYou can connect other instruments to the CX as Modbus slaves and load measured dataand other data. The loaded data c

Page 191 - 6-62 IM 04L31A01-17E

App-11IM 04L31A01-17EAppAppendixParameters Related to Loop 1410014100241003410044100541006410074100841009410104101141012410134101441015410164101741018

Page 192

App-12 IM 04L31A01-17E4110141102411034110441105411064110741108411094111041111411124112541126411274112841131-4114241155-4115841161-41172PID parameters

Page 193 - 7.1 Response Syntax

App-13IM 04L31A01-17EAppAppendix41185-4118841191-4120241215-4121841221-4123241245-4124841251-4126241275-4127841281-4129241305-4130841311-4132241335-41

Page 194 - BINARY Output

App-14 IM 04L31A01-17EParameters Related to Loop 241501-4151941601-4161241625-4162841631-4164241655-4165841661-4167241685-4168841691-4170241715-417184

Page 195 - Identifier

App-15IM 04L31A01-17EAppAppendixParameters Related to Loop 342001-4201942101-4211242125-4212842131-4214242155-4215842161-4217242185-4218842191-4220242

Page 196 - (1) (2) (3) (4)

App-16 IM 04L31A01-17EParameters Related to Loop 442501-4251942601-4261242625-4262842631-4264242655-4265842661-4267242685-4268842691-4270242715-427184

Page 197

App-17IM 04L31A01-17EAppAppendixParameters Related to Loop 543001-4301943101-4311243125-4312843131-4314243155-4315843161-4317243185-4318843191-4320243

Page 198

App-18 IM 04L31A01-17EParameters Related to Loop 643501-4351943601-4361243625-4362843631-4364243655-4365843661-4367243685-4368843691-4370243715-437184

Page 199

App-19IM 04L31A01-17EAppAppendix• Control Channel Bias and Filter Values When PV/SP Computation is ONWhen PV/SP computation is ON, the bias and filter

Page 200

App-20 IM 04L31A01-17E• Program Control Parameters440014400244003440044400544006440074400844009440104401144012440134401444015-440204402144022440234402

Page 201

1-11IM 04L31A01-17EFunctional Explanation1Modbus SlaveThe CX can be connected as a Modbus slave device to a Modbus master device.Modbus master devices

Page 202 - SP Number and PID Number

App-21IM 04L31A01-17EAppAppendix*4 Each register bit (16 bits) indicates the event status corresponding to each event number. Whenthe setting is “1,”

Page 203 - Control Mode Output

App-22 IM 04L31A01-17E• Program Individual Control Parameters38101381023810338104381053810638107 to 3811238113 to 3811838119 to 38124 38125 to 3813038

Page 204 - Program Operatin Mode Output

App-23IM 04L31A01-17EAppAppendix381553815638157:38170381713817238173 to 3818038181to 38186 38187 to 3819238193 to 3819838199 to 3820438205 to 38210382

Page 205

App-24 IM 04L31A01-17E• Write Registers for DO/internal switches44501445024450344504445054450644507 to 4451244513 to 4451844519 to 4453044531 to 44600

Page 206 - 101112131415

App-25IM 04L31A01-17EAppAppendix• Input Registers30001 :3002031001 :310203200132002 :320593206033001 :3303034001 :340183500135002 :35035350363600

Page 207 - Communication Log

App-26 IM 04L31A01-17E*5 The figure below shows the alarm status of the measured data and computed data. Eachregister contains data in the following

Page 208

App-27IM 04L31A01-17EAppAppendix*8 The control data alarm statuses of registers 36014 and 36015 indicate the statuses of alarmnumbers 1 to 4 of each l

Page 209

App-28 IM 04L31A01-17E*9 Registers 37001–37003 (status of control module DI), 37004 (status of expansion module DI),37011–37013 (status of control mod

Page 210

App-29IM 04L31A01-17EAppAppendixRegister Assignments during Ladder CommunicationsThe register assignments of the Modbus slave function are shown below

Page 211 - Web Operation Log

App-30 IM 04L31A01-17ED0601D0602D0603D0604D0605D0606D0607D0608 :D0833D0834D0835D0836D0837D0838D0839D0840Alarm value of computation channel 1Upper 5 di

Page 212 - E-mail Log

1-12 IM 04L31A01-17ELadder CommunicationsYou can connect the CX to a host such as a PLC and use the ladder communicationprotocol to read and write dat

Page 213 - Alarm Summary

App-31IM 04L31A01-17EAppAppendixParameters Related to Loop 1D1001D1002D1003D1004D1005D1006D1007D1008D1009D1010D1011D1012D1013D1014D1015D1016D1017D1018

Page 214 - Status Information

App-32 IM 04L31A01-17ED1101D1102D1103D1104D1105D1106D1107D1108D1109D1110D1111D1112D1125D1126D1127D1128D1131-D1142D1155-D1158D1161-D1172PID parameter o

Page 215 - File List

App-33IM 04L31A01-17EAppAppendixD1185-D1188D1191-D1202D1215-D1218D1221-D1232D1245-D1248D1251-D1262D1275-D1278D1281-D1292D1305-D1308D1311-D1322D1335-D1

Page 216 - Data List

App-34 IM 04L31A01-17EParameters Related to Loop 2D1501-D1519D1601-D1612D1625-D1628D1631-D1642D1655-D1658D1661-D1672D1685-D1688D1691-D1702D1715-D1718D

Page 217 - User Level

App-35IM 04L31A01-17EAppAppendixParameters Related to Loop 3D2001-D2019D2101-D2112D2125-D2128D2131-D2142D2155-D2158D2161-D2172D2185-D2188D2191-D2202D2

Page 218

App-36 IM 04L31A01-17EParameters Related to Loop 4D2501-D2519D2601-D2612D2625-D2628D2631-D2642D2655-D2658D2661-D2672D2685-D2688D2691-D2702D2715-D2718D

Page 219

App-37IM 04L31A01-17EAppAppendixParameters Related to Loop 5D3001-D3019D3101-D3112D3125-D3128D3131-D3142D3155-D3158D3161-D3172D3185-D3188D3191-D3202D3

Page 220

App-38 IM 04L31A01-17EParameters Related to Loop 6D3501-D3519D3601-D3612D3625-D3628D3631-D3642D3655-D3658D3661-D3672D3685-D3688D3691-D3702D3715-D3718D

Page 221

App-39IM 04L31A01-17EAppAppendixAppendix 6 Register Assignments• Control Channel Bias and Filter Values When PV/SP Computation is ONWhen PV/SP comput

Page 222

App-40 IM 04L31A01-17EAppendix 6 Register Assignments• Program Control ParametersD4001D4002D4003D4004D4005D4006D4007D4008D4009D4010D4011D4012D4013D40

Page 223

ii IM 04L31A01-17ETrademarks• vigilantplant, DAQSTATION, and Daqstation are registered trademarks of YokogawaElectric Corporation.• Microsoft and Wind

Page 224

1-13IM 04L31A01-17EFunctional Explanation1Communication with PCsWhen using the setting/measurement server by connecting the CX and a PC, the serialint

Page 225

App-41IM 04L31A01-17EAppAppendix0123456789101112131415123456789101112131415160: Event OFF, 1: Event ON0: Event OFF, 1: Event ON0: Event OFF, 1: Event

Page 226

App-42 IM 04L31A01-17EAppendix 6 Register Assignments• Program Individual Control ParametersD8101D8102D8103D8104D8105D8106D8107 to D8112D8113 to D811

Page 227

App-43IM 04L31A01-17EAppAppendixD8155D8156D8157:D8170D8171D8172D8173 to D8180D8181 to D8186 D8187 to D8192D8193 to D8198D8199 to D8204D8205 to D8210D8

Page 228

App-44 IM 04L31A01-17EAppendix 6 Register Assignments• Write Registers for DO/internal switchesD4501D4502D4503D4504D4505D4506D4507 to D4512D4513 to D

Page 229

App-45IM 04L31A01-17EAppAppendix• Read-only ParametersD5001 :D5020D5501 :D5520D6001D6002 :D6059D6060D6501 :D6530D7001 :D7018D7501D7502 :D7535D7536D760

Page 230

App-46 IM 04L31A01-17EAppendix 6 Register Assignments*5 The figure below shows the alarm status of the measured data and computed data. The register

Page 231 - Output Example

App-47IM 04L31A01-17EAppAppendix*8 The control data alarm statuses of registers D7614 and D7615 indicate the statuses of alarm numbers 1to 4 of each l

Page 232

App-48 IM 04L31A01-17E*9 Registers D7801–D7803 (status of control module DI), 37004 (status of expansion module DI), D7811–D7813 (status of control mo

Page 233

App-49IM 04L31A01-17EAppAppendixAppendix 7 MessagesMessages related mainly to the communications of the CX and their corrective actionsare given. Err

Page 234 - Communication Function

App-50 IM 04L31A01-17EAppendix 7 MessagesOperation Errors• Errors Related to the External Storage MediumCode Message Explanation/Countermeasures/Ref.

Page 235

2-1IM 04L31A01-17EEthernet Interface22.1 Ethernet Interface SpecificationsBasic SpecificationsElectrical and mechanical specifications Conforms to IEE

Page 236

App-51IM 04L31A01-17EAppAppendix• Errors Related to FTP ClientThe detail code does not appear in the error message on the screen. You can view thecod

Page 237

App-52 IM 04L31A01-17EAppendix 7 MessagesCode MessageCharacter String and DetailsSERVERThe server is not in a condition to provide the service.Check

Page 238 - 9.3 Setting the Modbus Master

App-53IM 04L31A01-17EAppAppendixCode Message285 FTP data connection error.Further details are provided by the character string that appears after erro

Page 239

App-54 IM 04L31A01-17EAppendix 7 MessagesCommunication Errors• Errors during Setting and Basic Setting Modes, Output Communication CommandExecution,

Page 240

App-55IM 04L31A01-17EAppAppendix• Other Communication ErrorsAn English error message is returned via the communication interface. It is notdisplayed

Page 241

App-56 IM 04L31A01-17EAppendix 8 Login ProcedureYou log into the CX from your PC to use the functionality of the setting/measurementserver and the mai

Page 242

App-57IM 04L31A01-17EAppAppendixWhen Not Using the Login Function of the CXLogin as “admin” or “user.”• The user name “admin” can be used to login to

Page 243 - (when Comm. is set to On)

Index-1IM 04L31A01-17EIndexIndexIndexIndexAaccount ... 2-11address ...

Page 244

Index-2 IM 04L31A01-17EHQ ... 6-49HR ...

Page 245

Index-3IM 04L31A01-17EIndexIndexcommunication input data ... 4-6communication log ...

Page 246

2-2 IM 04L31A01-17E2.2 Connecting of the Ethernet InterfaceWhen Connecting Only the CX and Your PCConnect the CX and your PC using a hub as shown belo

Page 247

Index-4 IM 04L31A01-17ELladder communication module ... 5-8ladder communication protocol ...

Page 248

Index-5IM 04L31A01-17EIndexIndexIndexsetup procedure using operation keys ... ixsignal names ...

Page 249

2-3IM 04L31A01-17EEthernet Interface22.3 Configuring of the Ethernet InterfaceExplanationTo use the Ethernet communication functions of the CX, the fo

Page 250

2-4 IM 04L31A01-17E• Domain suffixWhen the IP address corresponding to the server name with the domain nameof the previous section is not found, the s

Page 251

2-5IM 04L31A01-17EEthernet Interface2ProcedureFor the basic flow of operation, see “Setup Procedure Using Operation Keys” on pageix. For the procedur

Page 252

2-6 IM 04L31A01-17E11. Enter the subnet mask for the network to which the CX is to be connected.12. Press the DISP/ENTER key. On the CX1000, select [

Page 253

2-7IM 04L31A01-17EEthernet Interface221. Enter the address of the primary DNS server in the dialog box.22. Press the DISP/ENTER key. On the CX1000, s

Page 254

2-8 IM 04L31A01-17E35. Enter the primary domain suffix in the entry box.36. Press the DISP/ENTER key. On the CX1000, select [ENT] and then press theD

Page 255 - Communication condition

2-9IM 04L31A01-17EEthernet Interface22.4 Checking the Ethernet Interface ConnectionChecking the Connection on the Rear Panel of the CXYou can check th

Page 256

iiiIM 04L31A01-17ESafety PrecautionsAbout This Manual• Please pass this manual to the end user.• Read this manual thoroughly and have a clear understa

Page 257 - 9.8 Starting the Operation

2-10 IM 04L31A01-17E2.5 Setting the FTP Client (Setting the AutomaticTransfer of Display, Event, and Report Data Files)ExplanationBy setting this func

Page 258

2-11IM 04L31A01-17EEthernet Interface2• Port numberEnter the port number of the file transfer destination FTP server in the range of 1 to65535. The d

Page 259

2-12 IM 04L31A01-17EProcedureFor the basic flow of operation, see “Setup Procedure Using Operation Keys” on pageix. For the procedure of entering cha

Page 260

2-13IM 04L31A01-17EEthernet Interface2Setting the Primary FTP ConnectionOn the CX1000, if you confirmed the settings in step 8, press the ESC key to r

Page 261 - Display Data Example

2-14 IM 04L31A01-17E21. Enter the login name for accessing the primary FTP server in the entry box.22. Press the DISP/ENTER key. On the CX1000, selec

Page 262

2-15IM 04L31A01-17EEthernet Interface234. Press the [Input] soft key. An entry box appears.35. Enter the file transfer destination directory in the e

Page 263 - App-4 IM 04L31A01-17E

2-16 IM 04L31A01-17E2.6 FTP TestExplanationYou can test whether files can be transferred via the Ethernet interface by transferring atest file from th

Page 264

2-17IM 04L31A01-17EEthernet Interface22.7 Setting the Login and Timeout Functions ofEthernet CommunicationsExplanationBy setting these functions, you

Page 265 - Overview of the FIFO Buffer

2-18 IM 04L31A01-17ENote• The relationship between the login function and the user name for accessing the CX is asfollows.• When the login function is

Page 266

2-19IM 04L31A01-17EEthernet Interface2ProcedureFor the basic flow of operation, see “Setup Procedure Using Operation Keys” on pageix. For the procedu

Page 267 - App-8 IM 04L31A01-17E

iv IM 04L31A01-17EWARNINGPower SupplyEnsure that the source voltage matches the voltage of the power supply before turning ON the power.Protective Gro

Page 268 - • Hold Registers

2-20 IM 04L31A01-17E• Selecting whether to register (On/Off)9. Use the arrow keys to move the cursor to the [On/Off] box under Level.10. Press the [On

Page 269

2-21IM 04L31A01-17EEthernet Interface2• Setting the application time out22. Use the arrow keys to move the cursor to the [Time] box.23. Press the [Inp

Page 270 - Parameters Related to Loop 1

2-22 IM 04L31A01-17E2.8 Displaying the Error, Communication, and FTPLog ScreensExplanationDisplaying the Error Log ScreenThe error log screen shows a

Page 271 - App-12 IM 04L31A01-17E

2-23IM 04L31A01-17EEthernet Interface2Displaying the Web Browser Operation Log ScreenThe Web browser operation log screen shows a log of the past 50 W

Page 272

2-24 IM 04L31A01-17EProcedureDisplaying the Error Log Screen1. Press the FUNC key.The FUNC menu appears. The structure of the FUNC menu varies depend

Page 273 - Parameters Related to Loop 2

2-25IM 04L31A01-17EEthernet Interface2Displaying the Web Browser Operation Log Screen1. Press the FUNC key.The FUNC menu appears. The structure of th

Page 274 - Parameters Related to Loop 3

2-26 IM 04L31A01-17E2.9 Setting the Web Server FunctionExplanationTo use the Web server function, set the following parameters in addition to thosedes

Page 275 - Parameters Related to Loop 4

2-27IM 04L31A01-17E2Ethernet Interface• Selecting whether to use command input•OnEnables the use of message setting/writing commands.• OffDisables the

Page 276 - Parameters Related to Loop 5

2-28 IM 04L31A01-17EProcedureFor the basic flow of operation, see “Setup Procedure Using Operation Keys” on pageix. For the procedure of entering cha

Page 277 - Parameters Related to Loop 6

2-29IM 04L31A01-17E2Ethernet InterfaceSetting the Operator Page• Turning On/Off the operator page9. Use the arrow keys to move the cursor to the [On/O

Page 278

vIM 04L31A01-17EHow to Use This ManualStructure of the ManualThis user’s manual consists of the following sections.Chapter 1 Functional ExplanationDes

Page 279 - • Program Control Parameters

2-30 IM 04L31A01-17E20. Press the [Input] soft key. An entry box appears.21. Enter the password in the entry box.22. Press the DISP/ENTER key. On th

Page 280

2-31IM 04L31A01-17E2Ethernet Interface2.10 Using the Monitor Page and Operator PageExplanationThis section describes how to display the monitor page a

Page 281 - App-22 IM 04L31A01-17E

2-32 IM 04L31A01-17E• Screen displayed by the CX• If the CX is in the operation mode,* the monitor screen displayed on the CX(control, trend, digital,

Page 282

2-33IM 04L31A01-17E2Ethernet Interface• Displaying the logYou can display the communication command log, error message log, FTP filetransfer log, logi

Page 283 - App-24 IM 04L31A01-17E

2-34 IM 04L31A01-17EWeb Browser OperationContents of the Operator PageCX2000 screen exampleDisplay switchingoperation sectionArrow keys and theDISP/EN

Page 284 - • Input Registers

2-35IM 04L31A01-17E2Ethernet InterfaceOn the operator page, the following operations can be carried out in addition to theinformation available on the

Page 285 - High byte Low byte

2-36 IM 04L31A01-17EZooming in or out of the Display7. Click [Zoom] to specify [100%] or [75%] ([200%] on the CX1000).Displaying the Alarm Summary8. C

Page 286

2-37IM 04L31A01-17E2Ethernet InterfaceClick the selection button to choosethe message.Response from the CX for themessage setting/writing operation.En

Page 287 - App-28 IM 04L31A01-17E

2-38 IM 04L31A01-17E2.11 Setting the E-mail Transmission FunctionExplanationTo use the e-mail transmission function, set the following parameters in a

Page 288

2-39IM 04L31A01-17E2Ethernet Interface• SubjectSet the subject of the e-mail message using up to 32 alphanumeric characters.The default value is “(CX)

Page 289 - App-30 IM 04L31A01-17E

vi IM 04L31A01-17EConventions Used in This ManualUnit•k:Denotes “1000.” Example: 5 kg, 100 kHz•K:Denotes “1024.” Example: 640 KB (storage capacity o

Page 290

2-40 IM 04L31A01-17ESettings When Transmitting E-mail Messages at the Time of Recovery from aPower Failure (System E-Mail Settings)• Recipient 1, Reci

Page 291

2-41IM 04L31A01-17E2Ethernet InterfaceProcedureFor the basic flow of operation, see “Setup Procedure Using Operation Keys” on pageix. For the procedu

Page 292

2-42 IM 04L31A01-17E10. Press the [Input] soft key. An entry box appears.11. Enter the port number in the entry box.12. Press the DISP/ENTER key. On

Page 293 - App-34 IM 04L31A01-17E

2-43IM 04L31A01-17E2Ethernet InterfaceSetting [Alarm], [Scheduled], [System], and [Report]24. Press the ESC key to return to the Web, E-mail setting m

Page 294

2-44 IM 04L31A01-17E• Setting the e-mail subject (contents of the transmitted e-mail)33. Use the arrow keys to move the cursor to the [Subject] box.34

Page 295 - App-36 IM 04L31A01-17E

2-45IM 04L31A01-17E2Ethernet Interface• Setting the Ref.time45. Use the arrow keys to move the cursor to the [Ref.time] box.46. Press the [Input] soft

Page 296

2-46 IM 04L31A01-17E• Confirming or Canceling the Settings58. To confirm the new settings, press the DISP/ENTER key. To cancel thesettings, press the

Page 297 - App-38 IM 04L31A01-17E

2-47IM 04L31A01-17E2Ethernet Interface2.12 E-mail Transmission TestExplanationYou can transmit test e-mail messages to recipient 1 or recipient 2 that

Page 298

2-48 IM 04L31A01-17E2.13 Starting/Stopping E-mail TransmissionsExplanationStarting/Stopping E-mail Transmissions• If the e-mail transmission is starte

Page 299

2-49IM 04L31A01-17E2Ethernet InterfaceProcedureStarting the E-mail Transmission1. Press the FUNC key.The FUNC menu appears. The structure of the FUNC

Page 300

viiIM 04L31A01-17ENames and Uses of Parts and Setup ProceduresUsing the Operation KeysFront PanelCX1000DISP/ENTERMENUESCFUNCUSERSTARTSTOPLCDSoft keysP

Page 301 - App-42 IM 04L31A01-17E

2-50 IM 04L31A01-17E2.14 Processing during Recovery of the DO/InternalSwitch Communication BufferSet the operation to be performed for recovery of the

Page 302

3-1IM 04L31A01-17ESerial Interface33.1 Serial Interface SpecificationsThe specifications of the two types of serial interfaces (options), RS-232 and R

Page 303 - App-44 IM 04L31A01-17E

3-2 IM 04L31A01-17E3.2 Connector Pin Arrangement and SignalNames, Connection Procedure, andHandshaking Methods of the RS-232 InterfaceConnector Pin Ar

Page 304 - • Read-only Parameters

3-3IM 04L31A01-17ESerial Interface3Connection ExamplesSDRDRSCSSGSDRDRSSG• OFF-OFF/XON-XONPC CXSDRDRSCSSGSDRDRSSG• XON-RS(XON-RTS)PC CXSDRDRSCSSGSDRDRS

Page 305 - App-46 IM 04L31A01-17E

3-4 IM 04L31A01-17EXON-XON• Data Transmission ControlSoftware handshaking is performed between the CX and the PC. When an “X-OFF” code is received wh

Page 306

3-5IM 04L31A01-17ESerial Interface33.3 Terminal Arrangement and Signal Names andthe Connection Procedure of the RS-422/485InterfaceTerminal Arrangemen

Page 307 - App-48 IM 04L31A01-17E

3-6 IM 04L31A01-17EConnection Example with the Other InstrumentsYou can connect the CX as a host to multiple Green series controllers or connect the C

Page 308 - IM 04L31A01-01E

3-7IM 04L31A01-17ESerial Interface3Two-Wire SystemConnect the transmission and reception signals with the same polarity on the RS-422/485terminal bloc

Page 309 - Operation Errors

3-8 IM 04L31A01-17ESerial Interface ConverterRecommended converterSYSMEX RA CO.,LTD./MODEL RC-770X, LINE EYE/SI-30FA, YOKOGAWA/ML2CAUTIONSome converte

Page 310 - Appendix 7 Messages

3-9IM 04L31A01-17ESerial Interface33.4 The Bit Structure of One Character and theOperation of the Receive BufferThe Bit Structure of One CharacterThe

Page 311 - App-52 IM 04L31A01-17E

viii IM 04L31A01-17ERear PanelCX1000RS-232 interface connector (option)A serial communication connector.RS-422/485 interface terminal(option)Serial co

Page 312

3-10 IM 04L31A01-17E3.5 Configuring the Serial InterfaceExplanationSelecting the Baud RateSelect the baud rate from the following:1200, 2400, 4800, 96

Page 313

3-11IM 04L31A01-17ESerial Interface3ProcedureFor the basic flow of operation, see “Setup Procedure Using Operation Keys” on page ix.1. Press the MENU

Page 314 - • Status Messages

3-12 IM 04L31A01-17ESelecting the Parity Check9. Use the arrow keys to move the cursor to the [Parity] box.10. Press one of the soft keys from [Odd] t

Page 315 - Appendix 8 Login Procedure

3-13IM 04L31A01-17ESerial Interface3Selecting the Communication Type Used to Output the Data in the Internal Memoryand Files on the External Storage M

Page 316

3-14 IM 04L31A01-17E3.6 Automatic Recovery SettingsExplanationYou can select whether or not to automatically recover communications with modbusmice an

Page 317

4-1IM 04L31A01-17E4Modbus Protocol4.1 Modbus Protocol SpecificationsThe Modbus protocol can be used over the serial interface (RS-232 or RS-422/485).T

Page 318 - Index-2 IM 04L31A01-17E

4-2 IM 04L31A01-17E4.2 Configuring the Modbus ProtocolExplanationSelecting the Baud RateSelect the baud rate from the following:1200, 2400, 4800, 9600

Page 319

4-3IM 04L31A01-17E4Modbus ProtocolProcedureFor the basic flow of operation, see “Setup Procedure Using Operation Keys” on page ix.1. Press the MENU ke

Page 320 - Index-4 IM 04L31A01-17E

4-4 IM 04L31A01-17ESelecting the Slave Address (valid when operating as a Modbus slave)9. Use the arrow keys to move the cursor to the [Address] box.1

Page 321

4-5IM 04L31A01-17E4Modbus Protocol4.3 Setting the Modbus Master FunctionExplanationSelecting the Read CycleThe cycle at which data is read from other

Comments to this Manuals

No comments