User’s ManualYokogawa Electric CorporationMW100Setting for Data Communications via Modbus ProtocolIM MW100-72E1st Edition1st Edition : June 2006(YK)A
2IM MW100-72ESetup ExampleData is sent and received between the MW100 client and MW100 server. The MW100 client loads and displays measured data from
3IM MW100-72E2. Computed data from MATH channels A001 to A004 of the MW100 client are written to communication input channels C001 to C004 of the MW1
4IM MW100-72EClient Setting 2Enter settings for the destination server. Enter the IP address of the serverEnter the IP address or host name of the d
5IM MW100-72EClient/Server Settings for WRITEServer-Side SettingsServer SettingsSet the MW100 server as the server device. These are the same as the s
6IM MW100-72EStarting CommunicationStarting Measurement and ComputationMATH channels must be displayed to show transmitted data. After starting measur
7IM MW100-72EChecking the Communication StatusYou can view log information to check the status of Modbus communications. Modbus communication log in