<4. Installation>
4-2
IM 01C25F01-01E
IMPORTANT
Tighten the hexagonal nut part of the capsule
assembly. See Figure 4.3.
F0403.ai
Capsule assembly
Figure 4.3 Tightening Transmitter
4.3 Rotating Transmitter Section
The transmitter section can be rotated
approximately 360° (18 to either direction or
between -9 and +270° from the original position
at shipment, depending on the conguration of
the instrument.) It can be xed at any angle within
above range.
1) Remove the two setscrews that fasten the
transmitter section and capsule assembly,
using the Allen wrench.
2) Rotate the transmitter section slowly and stop it
at designated position. For the EJ530 and
EJX630A whose capsule code is A, B or C, the
pipe of the atmospheric opening may interfere
with the stopper and disturb further rotation.
In that case, screw off the pipe rst, rotate the
housing, and then screw in the pipe by hand
again.
3) Tighten the two setscrews to a torque of
1.5 N·m.
IMPORTANT
Do not rotate the transmitter section more than
the above limit.
F0404.ai
Setscrew
Transmitter section
Pressure-detector section
Stopper
Figure 4.4 Rotating Transmitter Section
4.4 Changing the Direction of
Integral Indicator
IMPORTANT
Always turn OFF power, release pressure and
remove a transmitter to non-hazardous area
before disassembling and reassmbling an
indicator.
An integral indicator can be installed in the
following three directions. Follow the instructions in
section 8.4 for removing and attaching the integral
indicator.
F0405.ai
Figure 4.5 Integral Indicator Direction