Yokogawa Electric CorporationUser’sManualIM 01E20F12-01EAXFPROFIBUS PA Communication TypeMagnetic FlowmeterIM 01E20F12-01E1st Edition
IM 01E20F12-01E3-33. GETTING STARTED3.4 Bus and AXF Power ONAddress setting SwitchA setup of bus address is possible by the change with aparameter, o
IM 01E20F12-01E3-43. GETTING STARTED3.5 Setting of Write ProtectSwitchA write protection is a function to forbid changing ofparameters. It is possibl
IM 01E20F12-01E3-53. GETTING STARTED3.6 Engineering ToolsEngineering of the AXF PROFIBUS PA can beperformed with the following two tools.3.6.1 FieldM
IM 01E20F12-01E3-63. GETTING STARTED3.7 Starting FieldMateThe following section describes how to run DTM withFieldMate R1.03.For the detailed informa
IM 01E20F12-01E3-73. GETTING STARTEDStarting DTM WorksIn the FieldMate window (as shown in the Figure3.7.1), click the icon of the device at its Main
IM 01E20F12-01E4-14. CONFIGURATION4. CONFIGURATIONThis chapter describes the basic parameters for thethree block types and explains how to set and ch
IM 01E20F12-01E4-24. CONFIGURATIONTARGET_MODE:Indicates the AI block mode: Out of Service (O/S),MAN, or AUTO. Target Mode indicates what mode ofopera
IM 01E20F12-01E4-34. CONFIGURATIONNOMINAL_SIZE:Specifies the size of the flow tube.NOMINAL_SIZE_UNITS:Specifies the unit of the flow tube size.LOW_MF
IM 01E20F12-01E4-44. CONFIGURATIONDISPLAY_SELECT1,2,3:Table 4.2 DISPLAY_SELECT1, 2, 3DISPLAY_SELECT 1 DISPLAY_SELECT 2 DISPLAY_SELECT 3 The display
IM 01E20F12-01E4-54. CONFIGURATION4.1.4 Totalizer Block ParametersDisableEnableF0404.EPSOperator∆ tFAIL_TOTMODE_TOTSET_TOTUNIT_TOTPRESET_TOT Operator
iCONTENTSIM 01E20F12-01E1st Edition: Mar. 2008(KP)All Rights Reserved, Copyright © 2008, Yokogawa Electric CorporationCONTENTS1. INTRODUCTION...
IM 01E20F12-01E4-64. CONFIGURATIONFAIL_TOT:This is the parameter which defines the fail safe modeof the Totalizer block. This parameter determines th
IM 01E20F12-01E4-74. CONFIGURATIONTable 4.4 TOTALQuality (bit 6-7) Sub-status (bit 2-5) Limit (bit 0-1) Alarm ValueT0404.EPS2:Good (NC) 0:Ok 0:
IM 01E20F12-01E4-84. CONFIGURATION4.1.5 DI Block ParametersF0405.EPSDisableValueOperatorOperatorMANDI BlockSimulationValue andStatusTransducerBlockMe
IM 01E20F12-01E4-94. CONFIGURATIONCHANNEL:This is the parameter to specify the value of thetransducer block to be input to the DI block. Each DIblock
IM 01E20F12-01E4-104. CONFIGURATIONOUT_D:OUT_D is the output of the function block. The valueis specified by the operator in MODE MAN.The relationshi
IM 01E20F12-01E5-15. EXPLANATION OF BASIC ITEMS5. EXPLANATION OF BASIC ITEMS5.1 OutlineThis section describes basic parameter setting by use ofFieldM
IM 01E20F12-01E5-25. EXPLANATION OF BASIC ITEMSTable 5.2.1Navigation tree structure of online parametersT0501.epsLevel of node1st level 2nd level 3rd
IM 01E20F12-01E5-35. EXPLANATION OF BASIC ITEMS(a) Process VariablesFigure 5.2.2 Process Variables(b) Device StatusFigure 5.2.3 Device StatusNote: Th
IM 01E20F12-01E5-45. EXPLANATION OF BASIC ITEMS5.3 Bus Address SetupThis section describes how to set the bus address byFieldMate R1.03. The AXF also
IM 01E20F12-01E5-55. EXPLANATION OF BASIC ITEMS(2) Bus Address change for DTMA message as “The communication DTM sent abort” inthe DTM Works is appea
iiCONTENTSIM 01E20F12-01E6. IN-PROCESS OPERATION ... 6-16.1 Mode Transition ...
IM 01E20F12-01E5-65. EXPLANATION OF BASIC ITEMS5.4 Easy SetupEasy Setup tracks parameters that often need to beconfigured or changed.Click [Easy Setu
IM 01E20F12-01E5-75. EXPLANATION OF BASIC ITEMS5.5 Function Blocks SettingThis section describes the procedure taken to set andchange the parameters
IM 01E20F12-01E5-85. EXPLANATION OF BASIC ITEMS5.5.2 AI Block Parameters SetupThe AI block outputs the flow rate signals.There are 4 kinds of submenu
IM 01E20F12-01E5-95. EXPLANATION OF BASIC ITEMS5.5.3 Transducer Block Parameters SetupThere are 8 kinds of submenus as [Flow Tube], [DISet], [AUX], [
IM 01E20F12-01E5-105. EXPLANATION OF BASIC ITEMS5.5.4 Totalizer Block Parameters SetupThere are 3 kinds of submenus as [Batch Information],[Totalizer
IM 01E20F12-01E5-115. EXPLANATION OF BASIC ITEMS(4) Resetting or Presetting Total ValueSelect type and entry the adequate numeric in each[Totalizer R
IM 01E20F12-01E5-125. EXPLANATION OF BASIC ITEMS(3) Invert settingSelect a use of invert at [Invert Input Value] in each[Discrete Input] menu.Figure
IM 01E20F12-01E5-135. EXPLANATION OF BASIC ITEMSFlow Rate (%)100.0%FRF0505.epsDecimal point is always to the first place.Out ValueFlow rate is displa
IM 01E20F12-01E5-145. EXPLANATION OF BASIC ITEMSUnit of Out Value on LCDApplicable Unit of Out Value is shown by the following tables corresponding t
IM 01E20F12-01E5-155. EXPLANATION OF BASIC ITEMSTable 5.6.3Display Unit Codes 3Units Codes Unit on Display [/min] 1521:Ml/min Ml/min 1348:m3/min
IM 01E20F12-01E1-11. INTRODUCTION1. INTRODUCTIONThis manual contains a description of the ADMAGAXF Series Magnetic Flowmeter ConverterPROFIBUS PA Com
IM 01E20F12-01E5-165. EXPLANATION OF BASIC ITEMSFlow Rate (Bar)Bi Direction is set "Unidirectional"3 4 5 6 7M l8D T L1 2-0 100F0508.epsBi D
IM 01E20F12-01E5-175. EXPLANATION OF BASIC ITEMS5.6.2 Display ModesADMAG AXF has following display modes.- Normal Display- Alarm Display- Warning Dis
IM 01E20F12-01E5-185. EXPLANATION OF BASIC ITEMSAlarm Message / Countermeasure MessageOn the Integral LCD indicator, following messages are displayed
IM 01E20F12-01E5-195. EXPLANATION OF BASIC ITEMSWarning MessageOn the Integral LCD indicator, following messages aredisplayed when warning is generat
IM 01E20F02-01E6-16. IN-PROCESS OPERATION6. IN-PROCESS OPERATIONThis chapter describes the procedure performed whenchanging the operation of the func
IM 01E20F02-01E6-2Table 6.1 Status of each parameter in failure mode (1/2)System Alarms10:uP Fault Uncertain; Substitude Value, okUncertain; Last Usag
IM 01E20F02-01E6-36. IN-PROCESS OPERATIONTable 6.1 Status of each parameter in failure mode (2/2)40:PB O/S ModeO/S Mode Alarms41:TB O/S Mode42:AI FB
IM 01E20F02-01E6-4Table 6.2 Status of each parameter in warning modeWarning 80:Adhesion Wng Good (NC); Maintenance required, okGood (NC); Maintenance
IM 01E20F02-01E6-56. IN-PROCESS OPERATION6.3 Simulation FunctionThe AXF has a simulation function and it is possible toconduct testing for the downst
IM 01E20F02-01E6-66.3.1 Transducer BlockThe configuration of transducer block for this function is shown at Figure 6.3.2. It is necessary to set param
IM 01E20F12-01E1-21. INTRODUCTIONPROFIBUS is a registered trademark of ProfibusNutzerorganisation e.v., Karlsruhe, Germany.1.1 Using the Magnetic Flo
IM 01E20F02-01E6-76. IN-PROCESS OPERATION6.3.2 AI / TOT / DI BlocksWhen the parameters are set in the transducer block, it is necessary to set parame
IM 01E20F02-01E6-8Table 6.3.3Alarm parameters as simulation function in the Physical blockT0605.EPSIndex Parameters Explanation52 DIAGNOSIS_SIM_MODEWh
IM 01E20F02-01E6-96. IN-PROCESS OPERATION6.3.4 Simulation Parameter Setup byFieldMate R1.03This section describes the procedure taken to set andchang
IM 01E20F02-01E6-10(4) Simulation Setup in the DI BlockSelect the adequate type at [Simulation Value],[Simulation Quality], [Simulation] and [Status]
IM 01E20F12-01E7-17. DIAGNOSTIC INFORMATION7. DIAGNOSTIC INFORMATION7.1 DEVICE STATUSDiagnostic information and failures of the AXF are indicated by
IM 01E20F12-01E7-27. DIAGNOSTIC INFORMATIONTable 7.2 List of DIAGNOSIS_EXTENSIONT0702.EPS 0 10:uP Fault Microprocessor error 1 11:EEPRO
IM 01E20F12-01E8-18. GENERAL SPECIFICATIONS8. GENERAL SPECIFICATIONS8.1STANDARD SPECIFICATIONSFor items other than those described below,refer to IM
IM 01E20F12-01E8-28. GENERAL SPECIFICATIONSEnhanced dual frequency excitation(Option code HF2): Standard accuracy ±1 mm/sRepeatability:± 0.1% of Rate
IM 01E20F12-01E8-38. GENERAL SPECIFICATIONS8.3 TERMINAL CONNECTIONIntegral Flowmeter AXFTerminal configurationF01.EPS+SUPPLYPBPOWERL/+ N/--Terminal
IM 01E20F12-01E9-19. PARAMETER LISTS9. PARAMETER LISTSNote The Write Mode column indicates the mode in which the parameter is write enabled.O/S: Writ
IM 01E20F12-01E1-31. INTRODUCTION• Problems or damage resulting from repairs ormodifications not performed by Yokogawa orsomeone authorized by Yokoga
IM 01E20F12-01E9-29. PARAMETER LISTST0901-2.EPSIndex Parameter Valid Range Initial Value Description WriteMode36 DESCRIPTOR User definition text (a s
IM 01E20F12-01E9-39. PARAMETER LISTS9.2 AI Block Parameter List (Slot 1)T0902-1.EPSIndex Parameter Valid Range Initial Value Description WriteModeInf
IM 01E20F12-01E9-49. PARAMETER LISTST0902-2.EPSIndex Parameter Valid Range Initial Value Description WriteMode33 FSAFE_TYPEDefines reaction of device
IM 01E20F12-01E9-59. PARAMETER LISTS9.3 Transducer Block Parameter List (Slot 7)T0903-1.EPSIndex Parameter Valid Range Initial Value Description Writ
IM 01E20F12-01E9-69. PARAMETER LISTST0903-2.EPSIndex Parameter Valid Range Initial Value Description WriteMode33 VOLUME_FLOW(DS-33)Indicates the curr
IM 01E20F12-01E9-79. PARAMETER LISTST0903-3.EPSIndex Parameter Valid Range Initial Value Description WriteMode77 MASS_FLOW_DENSITY Setting of the den
IM 01E20F12-01E9-89. PARAMETER LISTST0903-4.EPSIndex Parameter Valid Range Initial Value Description WriteMode92 SWITCH_2_VALUE_D(DS-34)Indicate the
IM 01E20F12-01E9-99. PARAMETER LISTST0903-5.EPSIndex Parameter Valid Range Initial Value Description WriteMode111 DISPLAY_SELECT1 This parameter is u
IM 01E20F12-01E9-109. PARAMETER LISTS9.4 Totalizer Block Parameter List (TOT1: Slot2, TOT2: Slot3,TOT3: Slot4)T0904-1.EPSIndex Parameter Valid Range
IM 01E20F12-01E9-119. PARAMETER LISTST0904-2.EPSIndex Parameter Valid Range Initial Value Description WriteMode32 PRESET_TOT This parameter is used i
IM 01E20F12-01E2-12. ABOUT PROFIBUS PA2. ABOUT PROFIBUS PA2.1 OutlinePROFIBUS PA is a widely used bi-directional digitalcommunication protocol that e
IM 01E20F12-01E9-129. PARAMETER LISTS9.5 DI Block Parameter List (DI1: Slot5, DI2: Slot6)T0905-1.EPSIndex Parameter Valid Range Initial Value Descrip
IM 01E20F12-01E10-110. MAINTENANCE10. MAINTENANCEFor maintenance items, please refer to user’smanual IM 01E20D01-01E or IM 01E20C02-01E.
IM 01E20F12-01EA-1APPENDIX 1. LIST OF DTM MENUAPPENDIX 1. LIST OF DTM MENULabel for node and parameter 1st row parameter 2nd row parameter
IM 01E20F12-01EA-2APPENDIX 1. LIST OF DTM MENU Output Analog Input Static Revision No. Target Mode Actual Mode
IM 01E20F12-01EA-3APPENDIX 2. LIST OF PDM (EDDL) MENUAPPENDIX 2. LIST OF PDM (EDDL) MENU AXF PA Easy Setup TAG
IM 01E20F12-01EA-4APPENDIX 2. LIST OF PDM (EDDL) MENU Lower Limit Warning Upper Limit Warning Upper Limit Alarm Hyst
IM 01E20F12-01EREVISION RECORDTitle: ADMAG AXF Series PROFIBUS PA Communication Type Magnetic FlowmeterManual No.: IM 01E20F12-01EREVISION RECORD.EPSE
IM 01E20F12-01E3-13. GETTING STARTED3. GETTING STARTEDFieldbus is fully dependent upon digital communica-tion protocol and differs in operation from
IM 01E20F12-01E3-23. GETTING STARTED3.2 Master SettingsTo activate PROFIBUS PA, the following bus param-eters must be set for the master.IMPORTANTDo