User’sManualModel DYVortex Flowmeter(Integral Type, Remote Type)Model DYAVortex Flow Converter(Remote Type)IM 01F06A00-01EN16th Edition
<2. HANDLING PRECAUTIONS>2-1IM 01F06A00-01EN2. HANDLING PRECAUTIONSThe Model DY Vortex Flowmeter and Model DYA Vortex Flow Converter are th
<11. MAINTENANCE>11-2IM 01F06A00-01EN11.1 Changing the Converter and the Terminal Box OrientationThe converter and the terminal box can be
<11. MAINTENANCE>11-3IM 01F06A00-01EN11.3 Amplifi er Unit RemovalIMPORTANTDo not turn the amplifi er unit for removal or assembling. The conn
<11. MAINTENANCE>11-4IM 01F06A00-01EN11.5 Vortex Shedder RemovalCAUTION• Disassemble work should be done only for error occurrence.• Onl
<11. MAINTENANCE>11-5IM 01F06A00-01ENFlow directionIntegral TypeRemote TypeF1104.aiColor WireRedWhiteABVortex shedder Mounting BoltVortex s
<11. MAINTENANCE>11-6IM 01F06A00-01ENF1105.aiUpstreamNumber of bolts: 2Number of bolts: 4Number of bolts: 6UpstreamNumber of bolts: 10Upstr
<11. MAINTENANCE>11-7IM 01F06A00-01EN(2) Flow Conversion Factor (Uk)Flow conversion factor Uk is obtained by carrying out the following co
<11. MAINTENANCE>11-8IM 01F06A00-01ENWhere M : Mass fl ow Qn : Volumetric fl ow rate at standard condition Qf : Volumetric fl ow rate at opr
<12. TROUBLESHOOTING>12-1IM 01F06A00-01EN12. TROUBLESHOOTINGCAUTIONPlease avoid replacing the amplifi er unit from the case, and the vortex
<12. TROUBLESHOOTING>12-2IM 01F06A00-01EN12.3 No Output When The Fluid is FlowingIs the output signal currentpresent?Refer to Section 10.1
<12. TROUBLESHOOTING>12-3IM 01F06A00-01EN12.4 Output is Indicated at Zero FlowIs fluid flowing?Are parameters configuredcorrectly at opera
<3. INSTALLATION>3-1IM 01F06A00-01EN3. INSTALLATIONWARNING This instrument must be installed by expert engineer or skilled personnel. The p
<12. TROUBLESHOOTING>12-4IM 01F06A00-01EN12.5 Multi-Variable Type (/MV)Are the power polarities Correct?Are the load resistance and supply
<13. GENERAL SPECIFICATIONS>13-1IM 01F06A00-01EN13. GENERAL SPECIFICATIONS13.1 Standard Specifi cations Communication function includes FOU
<13. GENERAL SPECIFICATIONS>13-2IM 01F06A00-01ENWeight:Refer to Section 13.7 “External Dimensions”.Mounting:Integral type and Remote type d
<13. GENERAL SPECIFICATIONS>13-3IM 01F06A00-01ENStatus Output Function*:Flow Switch: In case fl ow rate decreases under the fl ow set value,a
<13. GENERAL SPECIFICATIONS>13-4IM 01F06A00-01ENR=E - 10.50.023625060010.5 16.4 24.7 42Power Supply Voltage E(V)Communicationapplicable
<13. GENERAL SPECIFICATIONS>13-5IM 01F06A00-01EN13.2 Model And Suffi x CodesDY Vortex Flowmeter (Integral Type, Remote Type detector)Model S
<13. GENERAL SPECIFICATIONS>13-6IM 01F06A00-01ENTable 13.1 Body, Shedder Bar and Gasket MaterialBody MaterialStandard(Note1)Anti-Corrosion
<13. GENERAL SPECIFICATIONS>13-7IM 01F06A00-01ENGasket MaterialStandardAnti-corrosion Version II (/HY)High Process Temperature Version (/HT
<13. GENERAL SPECIFICATIONS>13-8IM 01F06A00-01EN13.3 Option Specifi cationsItem Specifi cationApplicable ModelCodeMulti-Variable Type (Note 5
<13. GENERAL SPECIFICATIONS>13-9IM 01F06A00-01EN(Note 5) Refer to Subsection 13.3.1 “Option Multi-Variable (Built-In Temperature Sensor) T
<3. INSTALLATION>3-2IM 01F06A00-01ENTable 3.1 (a) Straight pipe length and recommendations (1)D: Nominal diameter (mm)Description FigureRe
<13. GENERAL SPECIFICATIONS>13-10IM 01F06A00-01EN13.3.1 Option Multi-Variable (Built-In Temperature Sensor) Type (/MV) This options is the
<13. GENERAL SPECIFICATIONS>13-11IM 01F06A00-01EN13.3.2 Option Reduced Bore Type (/R1, /R2)This option is the same as standard specifi cati
<13. GENERAL SPECIFICATIONS>13-12IM 01F06A00-01EN Range of measurable fl ow velocityTable 13.6 Range of measurable fl ow velocityFluidModel
<13. GENERAL SPECIFICATIONS>13-13IM 01F06A00-01EN13.5 Detailed AccuracyAccuracy is the value in range of fi xed accuracy fl ow velocity. Refe
<13. GENERAL SPECIFICATIONS>13-14IM 01F06A00-01ENMass fl ow or Volumetric fl ow rate at Normal/Standard condition:for Multi-Variable Type and
<13. GENERAL SPECIFICATIONS>13-15IM 01F06A00-01EN Calculation formula How to calculate volume fl ow rate at operating conditions.• Qf = 3
<13. GENERAL SPECIFICATIONS>13-16IM 01F06A00-01ENTable 13.9 Range of Measurable Air Flow Rate at Selected Process PressuresModel CodeFlow
<13. GENERAL SPECIFICATIONS>13-17IM 01F06A00-01ENTable 13.10 Range of Measurable Saturated Steam Flow Rate at Selected Process PressuresMo
<13. GENERAL SPECIFICATIONS>13-18IM 01F06A00-01EN ReferenceTable 13.11 Inner Diameter and Nominal valueModel CodeInner Diameter mmNominal
<13. GENERAL SPECIFICATIONS>13-19IM 01F06A00-01EN Cavitation(Minimum Back Pressure, Liquid service only):Cavitation occurs when the fl ow l
<3. INSTALLATION>3-3IM 01F06A00-01ENTable 3.1 (b) Straight pipe length and recommendations (2)D: Nominal diameter (mm)Description FigureFl
<13. GENERAL SPECIFICATIONS>13-20IM 01F06A00-01EN13.6 Option Specifi cations (For Explosion Protected Type)Item Specifi cation CodeTIIS Certi
<13. GENERAL SPECIFICATIONS>13-21IM 01F06A00-01ENItem Specifi cation Code Canadian Standards Association (CSA)CSA Explosion proof ApprovalAp
<13. GENERAL SPECIFICATIONS>13-22IM 01F06A00-01EN13.7 External Dimensions Wafer type (DY015 to DY100)103.5 (4.07)H1H125 (4.92)LøD87.5 (3.4
<13. GENERAL SPECIFICATIONS>13-23IM 01F06A00-01EN Flange type (DY015 to DY100)125 (4.92)87.5 (3.44)103.5 (4.07)H1øDHN-øGøJøC4.5(0.18)59 (
<13. GENERAL SPECIFICATIONS>13-24IM 01F06A00-01EN Flange type (DY150 to DY400)H125 (4.92)øCøJN - øG74 (2.91)ø94 (3.70)59 (2.32) 59 (2.32)
<13. GENERAL SPECIFICATIONS>13-25IM 01F06A00-01ENn High Process Temperature Version (/HT): DY025/HT to DY100/HTn Cryogenic Version (/LT): D
<13. GENERAL SPECIFICATIONS>13-26IM 01F06A00-01EN High Process Temperature Version (/HT): DY025/HT to DY100/HT Cryogenic Version (/LT): D
<13. GENERAL SPECIFICATIONS>13-27IM 01F06A00-01EN High Process Temperature Version (/HT): DY150/HT to DY300/HT Flange typeOnly for the fo
<13. GENERAL SPECIFICATIONS>13-28IM 01F06A00-01EN Reduced Bore Type (/R1): DY025/R1 to DY150/R1 Flange typeN- øGøCWITH INDICATOR87.5 (3.4
<13. GENERAL SPECIFICATIONS>13-29IM 01F06A00-01EN Reduced Bore Type (/R1): DY200/R1 Flange type87.5 (3.44)103.5 (4.07)HH1125 (4.29)TLøD59
<3. INSTALLATION>3-4IM 01F06A00-01ENTable 3.1 (c) Straight pipe length and recommendations (3)Description FigureHeat-Insulation:When an in
<13. GENERAL SPECIFICATIONS>13-30IM 01F06A00-01EN High Process Temperature Version Reduced Bore Type (/HT/R1): DY040/HT/R1 up to DY150/HT
<13. GENERAL SPECIFICATIONS>13-31IM 01F06A00-01EN High Process Temperature Version Reduced Bore Type (/HT/R1): DY200/HT/R1 Flange typeøDN
<13. GENERAL SPECIFICATIONS>13-32IM 01F06A00-01EN Reduced Bore Type (/R2): DY040/R2 to DY200/R2 Flange typeN- øG125 (4.92)74 (2.91)H4.5(0
<13. GENERAL SPECIFICATIONS>13-33IM 01F06A00-01EN High Process Temperature Version Reduced Bore Type (/HT/R2): DY050/HT/R2 to DY200/HT/R2
<13. GENERAL SPECIFICATIONS>13-34IM 01F06A00-01EN Stainless Steel Housing: DY015/E1 to DY100/E1 Wafer TypeELECTRICAL CONNECTIONOnly for
<13. GENERAL SPECIFICATIONS>13-35IM 01F06A00-01EN Stainless Steel Housing: DY015/E1 to DY100/E1 Flange typeELECTRICAL CONNECTIONOnly for
<13. GENERAL SPECIFICATIONS>13-36IM 01F06A00-01EN Stainless Steel Housing: DY150/E1 to DY400/E1 Flange typeELECTRICAL CONNECTIONOnly for
<13. GENERAL SPECIFICATIONS>13-37IM 01F06A00-01EN Stainless Steel Housing Reduced Bore Type (/R1/E1): DY025/R1/E1 to DY150/R1/E1 Flange t
<13. GENERAL SPECIFICATIONS>13-38IM 01F06A00-01EN Stainless Steel Housing Reduced Bore Type (/R1/E1): DY200/R1/E1 Flange typeELECTRICAL C
<13. GENERAL SPECIFICATIONS>13-39IM 01F06A00-01EN Stainless Steel Housing Reduced Bore Type (/R2/E1): DY040/R1/E1 to DY200/R2/E1 Flange t
<3. INSTALLATION>3-5IM 01F06A00-01EN• Piping for Avoiding BubblesFlows containing both gas and liquid cause problems. Avoid gas bubbles in
<13. GENERAL SPECIFICATIONS>13-40IM 01F06A00-01EN Remote Type Converter (DYA)WITH INDICATOR4.5(0.18)59 (2.32) 59 (2.32)125 (4.92)103.5 (4.
<13. GENERAL SPECIFICATIONS>13-41IM 01F06A00-01EN Flameproof Packing Adapter (/G11, /G12)T1T2L18(0.71)GFDC16.5(0.65)*Packing(Choose from t
<14. EXPLOSION PROTECTED TYPE INSTRUMENT>14-1IM 01F06A00-01EN14. EXPLOSION PROTECTED TYPE INSTRUMENTIn this chapter, further requirements
<14. EXPLOSION PROTECTED TYPE INSTRUMENT>14-2IM 01F06A00-01EN(Integral Type Vortex Flowmeter)Temperature Class Ambient Temperature Process
<14. EXPLOSION PROTECTED TYPE INSTRUMENT>14-3IM 01F06A00-01EN(3) OperationWARNING • Wait 3 min. after power is turned off, before opening
<14. EXPLOSION PROTECTED TYPE INSTRUMENT>14-4IM 01F06A00-01EN(7) Name Plate[Integral type, Flameproof]Ú2[Remote type detector, Flameproof]Ú
<14. EXPLOSION PROTECTED TYPE INSTRUMENT>14-5IM 01F06A00-01EN• Intrinsically SafeApplicable Standard: FM3600 1998, FM3610 2010, FM3611
<14. EXPLOSION PROTECTED TYPE INSTRUMENT>14-6IM 01F06A00-01EN(5) Installation DiagramIntrinsically Safe (and WARNING)F1404.ai+-+-+-+-+-+-+-
<14. EXPLOSION PROTECTED TYPE INSTRUMENT>14-7IM 01F06A00-01EN14.3 IECExWARNING • Only trained persons use this instrument in industrial lo
<14. EXPLOSION PROTECTED TYPE INSTRUMENT>14-8IM 01F06A00-01EN(3) OperationWARNING • Wait 3 min. after power is turned off, before opening
<3. INSTALLATION>3-6IM 01F06A00-01EN3.4 Cryogenic and High Process Temperature Version InsulationWhen you are using Cryogenic and High Pro
<14. EXPLOSION PROTECTED TYPE INSTRUMENT>14-9IM 01F06A00-01EN14.4 CSA(1) Technical Data• Explosion ProofApplicable Standard: C22.1-98, C22
<14. EXPLOSION PROTECTED TYPE INSTRUMENT>14-10IM 01F06A00-01EN(Integral Type Vortex Flowmeter and Remote Type Vortex Flow Detector)Temperat
<14. EXPLOSION PROTECTED TYPE INSTRUMENT>14-11IM 01F06A00-01EN(5) Installation Diagram Intrinsically Safe (and Note)Intrinsically safe+-+-
<14. EXPLOSION PROTECTED TYPE INSTRUMENT>14-12IM 01F06A00-01EN14.5 SAAWARNING Only trained persons use this instrument in industrial locati
<14. EXPLOSION PROTECTED TYPE INSTRUMENT>14-13IM 01F06A00-01EN(5) Installation DiagramIntrinsically SafeF1410.ai+-++-++-+-+-+-+-+-+-+-[Remo
<14. EXPLOSION PROTECTED TYPE INSTRUMENT>14-14IM 01F06A00-01EN14.6 TIISCertifi cate:Model Shedder bar Material Integral Type Flowmeter Remot
<15. PED (PRESSURE EQUIPMENT DIRECTIVE)>15-1IM 01F06A00-01EN15. PED (PRESSURE EQUIPMENT DIRECTIVE)This chapter is described further requir
<INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROOF EQUIPMENT>1IM 01F06A00-01ENINSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROO
<INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROOF EQUIPMENT>2IM 01F06A00-01EN(5) Gaps between joint surfacesThe physical distance bet
<INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROOF EQUIPMENT>3IM 01F06A00-01EN6. Maintenance of Flameproof Apparatus To maintain th
<3. INSTALLATION>3-7IM 01F06A00-01EN• Four collars are supplied for 1/2 inch (15mm) to 1- 1/2inch (40mm), 2 inch of JIS 10K or ANSI class
iIM 01F06A00-01ENRevision Information Title: Model DY Vortex Flowmeter Model DYA Vortex Flow Converter Manual No.: IM 01F06A00-01EEdition Data
iiIM 01F06A00-01ENEdition Data Page Revised Item8th Nov. 2005 2-7 3-5 4-21-25 4-24 5-15 5-16 8-2 9-5 9-6 9-7 9-8 9-10 9-11 9-12 9-14 9-19 9-20 9-22 9-
iiiIM 01F06A00-01ENEdition Data Page Revised Item12th Mar. 2010 1-1 2-5 2-7 3-2 3-3 3-4 4-9 4-13 to 21 5-4 5-8 5-12 5-15 6-1 6-3 9-2 9-5 to 9-6 9-7 to
ivIM 01F06A00-01ENEdition Data Page Revised Item15th Aug. 2012 2-32-53-7, 3-85-2, 5-4, 5-5, 5-157-57-78-7, 8-88-158-188-1910-210-410-612-312-512-612-8
<3. INSTALLATION>3-8IM 01F06A00-01ENTable 3.3 (a) Installation of Wafer Type Vortex FlowmeterWafer typeDescriptionWhen Installation Collar
<3. INSTALLATION>3-9IM 01F06A00-01ENTable 3.3 (b) Installation of Flange Type Vortex FlowmeterHorizontal InstallationVertical Installation
iIM 01F06A00-01ENModel DY Vortex Flowmeter(Integral Type, Remote Type)Model DYA Vortex Flow Converter(Remote Type)IM 01F06A00-01EN 16th Edition16th E
<4. WIRING>4-1IM 01F06A00-01EN4. WIRINGWARNING The wiring of the vortex fl owmeter must be performed by expert engineer or skilled personnel.
<4. WIRING>4-2IM 01F06A00-01ENR=E–10.50.023625060010.5 16.4 24.730 42Power Supply Voltage E (V)CommunicationApplicable rangeBRAIN and HARTLo
<4. WIRING>4-3IM 01F06A00-01ENTable 4.1 (a) The wiring example for the analog and pulse and status, alarm output.Connection DescriptionAnal
<4. WIRING>4-4IM 01F06A00-01ENTable 4.1 (b) The wiring example for the simultaneous analog and pulse output, the calculation formula of the
<4. WIRING>4-5IM 01F06A00-01EN4.4 Connection of DYC Signal CableThe remote type signal cable is shown in Figure 4.3 and Figure 4.4, and the
<4. WIRING>4-6IM 01F06A00-01EN4.5 End Processing Method of DYC Signal Cable4.5.1 For Vortex Flowmeter (DY-N)123456789Do not short-circuit
<4. WIRING>4-7IM 01F06A00-01EN4.5.2 For Vortex Flow Converter (DYA)123456789Do not short-circuit the conductive layer and the terminals (A,
<4. WIRING>4-8IM 01F06A00-01EN4.6 Wiring Procedures and PrecautionsNOTEOnce all wiring is complete, check the connections before applying p
<4. WIRING>4-9IM 01F06A00-01EN(5) Perform attachment of fl ameproof packing adaptor in the following ways. Refer to Figure 4.11.(a) Loosen
<5. BASIC OPERATING PROCEDURES>5-1IM 01F06A00-01EN5. BASIC OPERATING PROCEDURESData setting can be performed with the three keys on the fr
iiIM 01F06A00-01EN6. PARAMETERS ... 6-16.1 digitalYEWFLO Parame
<5. BASIC OPERATING PROCEDURES>5-2IM 01F06A00-01EN5.2 Display ContentsThe display content items are classifi ed in the following three items
<5. BASIC OPERATING PROCEDURES>5-3IM 01F06A00-01EN5.3 Display ModeThe display mode is a mode in which instantaneous fl ow rates or totalized
<5. BASIC OPERATING PROCEDURES>5-4IM 01F06A00-01EN5.3.1 Changes to Engineering Display Unit from % DisplayThe display mode can be changed
<5. BASIC OPERATING PROCEDURES>5-5IM 01F06A00-01EN5.3.2 Indicate the Total Rate in the Data Display(Lower)The display mode can be changed
<5. BASIC OPERATING PROCEDURES>5-6IM 01F06A00-01EN5.4 Setting ModeThe setting mode is used for checking parameters and rewriting data. The
<5. BASIC OPERATING PROCEDURES>5-7IM 01F06A00-01EN5.4.2 Data Setting Method Input method of numeric dataExample 1: Change the span from 1
<5. BASIC OPERATING PROCEDURES>5-8IM 01F06A00-01EN Input method of selection itemsExample 2: Change the pulse output to alarm output.The s
<6. PARAMETERS>6-1IM 01F06A00-01EN6.1 digitalYEWFLO ParametersThe parameters are set before factory shipment. Set the required parameter of
<6. PARAMETERS>6-2IM 01F06A00-01EN(1) Item A : IndicationThese items are for the indication of fl owrate and total.Item Name R / W Data Ran
<6. PARAMETERS>6-3IM 01F06A00-01EN(3) Item C : BASIC SETUPThese items are for the basic parameters with setting before shipment.The parame
iiiIM 01F06A00-01EN9.10.4 Multidrop Mode ... 9-89.10.5 Loop Test, Simu
<6. PARAMETERS>6-4IM 01F06A00-01ENItem Name R / W Data Range UnitDecimalPointRemarkInitialValueDisp. U / D (*1)C37 STD/NOR UNIT W Nm3 k Nm3
<6. PARAMETERS>6-5IM 01F06A00-01EN(4) Item D : Additional SetupThese items are for Auxiliary Setup.A value in “( )” is the data correspon
<6. PARAMETERS>6-6IM 01F06A00-01EN(5) Item E : Detector SetupThese items are for detector that has been already set before.A value in “(
<6. PARAMETERS>6-7IM 01F06A00-01EN(6) Item F: Thermometer (Only for Multi-Variable Type)These items is for thermometer setting when.A Valu
<6. PARAMETERS>6-8IM 01F06A00-01ENItem Name R / W Data Range UnitDecimalPointRemarkInitialValueDisp. U / D (*1)F29 TEMP b W -999.9 to 999.9
<6. PARAMETERS>6-9IM 01F06A00-01EN(7) Item H : Adjust.These items are for setting of adjustment.A value in “( )” is the data correspondin
<6. PARAMETERS>6-10IM 01F06A00-01EN(9) Item K : MaintenanceThese items are for maintenance.Item Name R / W Data Range UnitDecimalPointRema
<6. PARAMETERS>6-11IM 01F06A00-01EN6.4 Parameters Description(1) Item A : DisplayThese items are for the indication of fl owrate and total.
<6. PARAMETERS>6-12IM 01F06A00-01EN[B22:FREQ AT 100%] Pulse numbers of 100% at one second Set pulse number at 100% for one second when “FRE
<6. PARAMETERS>6-13IM 01F06A00-01EN(3) Item C : BASIC SETUPThese items are for the basic parameters with setting before shipment. The para
ivIM 01F06A00-01EN14. EXPLOSION PROTECTED TYPE INSTRUMENT ... 14-114.1 ATEX ...
<6. PARAMETERS>6-14IM 01F06A00-01EN[C40:TIME UNIT] TIME UNITSelect time unit from “/s(0), /m(1), /h(2), /d(3)”[C45:FLOW SPAN] Flowrate span
<6. PARAMETERS>6-15IM 01F06A00-01EN(5) Item E (METER SETUP)These items are for detector set up that has already been set before shipment.A
<6. PARAMETERS>6-16IM 01F06A00-01EN[F16 MASS UNIT] Mass fl ow unitSelect mass fl ow unit from kg(0), t(1), lb(2), k lb(3).The following items
<6. PARAMETERS>6-17IM 01F06A00-01EN(7) Item H (ADJUST)This item for setting of adjustment.NOTEIn case that Reynolds adjustment (H25), Gas
<6. PARAMETERS>6-18IM 01F06A00-01EN• Defi nition of error varies with the type of fl owmeter. Be careful of the difference in signs in the er
<6. PARAMETERS>6-19IM 01F06A00-01ENNOTE• In case of multi-variable type (option code: /MV), output value is calculated by setting density
<6. PARAMETERS>6-20IM 01F06A00-01ENIndication Diagnostic Message Error Name Problem Cause Current Output % Output Pulse Output Engineerin
<7. OPERATION FOR THE BRAIN TERMINAL (BT200)>7-1IM 01F06A00-01EN7. OPERATION FOR THE BRAIN TERMINAL (BT200)This chapter describes the oper
<7. OPERATION FOR THE BRAIN TERMINAL (BT200)>7-2IM 01F06A00-01EN7.2 BT200 Screen and Displaying Flow RateFlowrate data can be displayed on
<7. OPERATION FOR THE BRAIN TERMINAL (BT200)>7-3IM 01F06A00-01EN7.3 Setting Parameters using BT200This section describes the setting metho
<1. INTRODUCTION>1-1IM 01F06A00-01EN1. INTRODUCTIONThank you for purchasing the digitalYEWFLO vortex fl owmeter.To ensure correct use of the
<7. OPERATION FOR THE BRAIN TERMINAL (BT200)>7-4IM 01F06A00-01EN(2) Setting OutputExample: Change the pulse output to alarm outputF0705.aiE
<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>8-1IM 01F06A00-01EN8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)NOTEIn this User’s
<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>8-2IM 01F06A00-01EN8.3 Setting Parameters using DTMWhen confi gure the parameters using
<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>8-3IM 01F06A00-01EN8.6 Parameter SettingThe parameter structure of the HART confi guratio
<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>8-4IM 01F06A00-01EN8.10.2 Multidrop Mode“Multidropping” devices refers to the connection
<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>8-5IM 01F06A00-01ENNOTEWhen using a Fieldmate, close the main display of FieldMate.b. Re
<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>8-6IM 01F06A00-01EN8.11 Menu Tree (HART 5)Menu tree is different from DD and DTM. Refe
<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>8-7IM 01F06A00-01ENF0807.aiBasic setup(RW) [C10]Tag *Easy setup Contact output * OffPuls
<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>8-8IM 01F06A00-01ENF0808.ai(R)Base unit * [D41][D42][D43]User's unit *Conversion fa
<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>8-9IM 01F06A00-01ENF0809.aiSignal processing(RW)PV Damp(RW)Low cut *Temp unitTemp setupP
<1. INTRODUCTION>1-2IM 01F06A00-01EN1.1 Using This Instrument Safety(1) InstallationWARNING • Installation of the vortex fl owmeter must
<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>8-10IM 01F06A00-01ENF0810.aiDevice informationManufacturer (R)(RW)Tag *Descriptor * (RW)
<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>8-11IM 01F06A00-01ENF0811.aiModelManufacturerDistributorTagDescriptorMessageDateDev idWr
<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>8-12IM 01F06A00-01EN• DTM (HART 5) Menu TreeABCDEFGF0812.ai3URFHVVYDULDEOHV'HY
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-1IM 01F06A00-01EN9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)NOTEIn this User’s
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-2IM 01F06A00-01EN9.4 Interconnection between digitalYEWFLO and HART Confi guration Tool
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-3IM 01F06A00-01EN9.6 Parameter SettingThe parameter structure of the HART confi guratio
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-4IM 01F06A00-01ENTable 9.1 Burst parametersCommand parameter Burst CommandBurst Msg T
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-5IM 01F06A00-01EN(2) Burst mode setting procedure• Procedure to call up the displayDD
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-6IM 01F06A00-01ENa. Burst CommandSelect the transmission data at Burst Command paramet
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-7IM 01F06A00-01ENe. Burst ModeWhen the Burst mode is set to Wired HART Enabled, the
<1. INTRODUCTION>1-3IM 01F06A00-01EN(5) Explosion Protected Type InstrumentWARNING • The instruments are products which have been certifi
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-8IM 01F06A00-01ENb) Acknowledge Event Notifi cationExecute Acknowledge Event Notifi cat
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-9IM 01F06A00-01EN(3) Communication when set in the multidrop mode.• The HART confi gu
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-10IM 01F06A00-01ENQVPV SV TVFlow rate computingProcess temperature computingProcess de
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-11IM 01F06A00-01EN• Simulation Setting and Correlation of Output Value<Case A>:
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-12IM 01F06A00-01EN(3) Squawk (Effective only when setting to HART 7)This feature can b
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-13IM 01F06A00-01ENNOTEA new HART revision number is displayed on the integral indicato
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-14IM 01F06A00-01EN9.11 Menu Tree (HART 7) DTM (HART 7) Menu Tree''+$5
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-15IM 01F06A00-01ENF0911.aiDiag/ServiceSelf test/Status(M)(MV)Self testStatusStatus gro
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-16IM 01F06A00-01ENF0912.aiBasic setup(RW)(RW)Tag *Long Tag *Easy setup Contact output
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-17IM 01F06A00-01ENF0913.aiBasic setupTagsEasy setupDevice informationOthersTagLong tag
<1. INTRODUCTION>1-4IM 01F06A00-01EN1.3 ATEX DocumentationThis is only applicable to the countries in European Union.GBDKIENLSFPFDSLTLVPLES
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-18IM 01F06A00-01ENF0914.ai(R)Base unit *User's unit *Conversion factor * (RW)(RW)
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-19IM 01F06A00-01ENF0915.ai(R) PV assign enum(R) Dyn var assign enum(R) Dyn var assign
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-20IM 01F06A00-01ENF0916.aiSignal processingD2(RW)Flow rate damping value(RW)Low cut *T
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-21IM 01F06A00-01ENDevice informationD3Manufacturer (R)(RW)(RW)Tag *Descriptor * (RW)(R
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-22IM 01F06A00-01ENF0918.aiModelManufacturerDistributorCfg chng countMax dev varsTagLon
<10. OPERATION>10-1IM 01F06A00-01ENAfter you have installed the fl owmeter into the process piping, wired the input/output terminals, set up
<10. OPERATION>10-2IM 01F06A00-01EN10.1.4 Totalizer Start and Totalizer ResetWhen using the Totalizer Function, the start setup should be
<10. OPERATION>10-3IM 01F06A00-01EN10.1.7 Setting of Write Protect SwitchBy setting the write protect function to “Protect”, it is possibl
<10. OPERATION>10-4IM 01F06A00-01EN1. Tuning method(1) Ensure the condition of fl owrateThe necessary condition for tuning function is zero
<11. MAINTENANCE>11-1IM 01F06A00-01EN11. MAINTENANCECAUTION• Disassemble work should be done only for error occurrence.• Maintenance work