User’sManualYokogawa Electric CorporationAXFA14G/CMagnetic Flowmeter Remote Converter[Hardware Edition/Software Edition]AXFMagnetic FlowmeterIntegral
IM 01E20C02-01E2-12. HANDLING PRECAUTIONS2. HANDLING PRECAUTIONSThis instrument has been inspected carefully at thefactory before shipment. When the
IM 01E20C02-01E10-410. MAINTENANCE10.3 TroubleshootingAlthough magnetic flowmeters rarely require maintenance, failures may occur when theinstrument
IM 01E20C02-01E10-510. MAINTENANCE10.3.2 Unstable ZeroSTARTCheck for the presence of valve leakage.• Confirm the flowmeter grounding. • Confirm wheth
IM 01E20C02-01E10-610. MAINTENANCE10.3.3 Disagreement Between Indication and Actual FlowNONONONOYESNONOYESYESYESNOYESYESNONOYESSet the parameters cor
IM 01E20C02-01E11-111. OUTLINE STANDARD SPECIFICATIONSRefer to IM 01E20F02-01E for FOUNDATION Fieldbuscommunication type and IM 01E20F12-01E forPROF
IM 01E20C02-01E11-211. OUTLINEFunctions “”How to Set Parameters (*2):The indicator’s LCD and three infra-red switches enableusers to set parameters
IM 01E20C02-01E11-311. OUTLINEAccuracy (Combined with AXF Remote Flowtube)Pulse Output:PFA/Ceramics Lining:Size mm (in.)V 0.3 (1)1.0 mm/s0.5 mm/s
IM 01E20C02-01E11-411. OUTLINESafety Requirement Standards:EN61010-1• Altitude at installation site: Max. 2000 m above sea level• Installation catego
IM 01E20C02-01E11-511. OUTLINESignal Cable:Model Suffix Code DescriptionAXFCTerminationCable LengthOptionMagnetic FlowmeterDedicated Signal cable for
IM 01E20C02-01E11-611. OUTLINE OPTIONAL SPECIFICATIONS FOR AXFA14 REMOTE CONVERTER “”Burn Out DownLightning ProtectorDC Noise CutCircuitA lightning
IM 01E20C02-01E11-711. OUTLINET05_02.EPSFour flameproof packing adaptersFlameproof packing adapter for TIIS Flameproof Type– G14Three flameproof pa
IM 01E20C02-01E2-22. HANDLING PRECAUTIONS2.4 Installation LocationPrecautionsSelect the installation location with consideration to thefollowing item
IM 01E20C02-01E11-811. OUTLINE EXTERNAL DIMENSIONS● Remote Converter AXFA14G/C103(4.06)31(1.22)ø128(5.04)66(2.6)28(1.1)197(7.76)*1180(7.09)49(1.92)2
IM 01E20C02-01E11-911. OUTLINE● Flameproof packing adapter for TIIS Flameproof type (optional code G14 or G13)T1T2L18(0.71)GFDC16.5(0.65)*Packing(Cho
IM 01E20C02-01E12-112. EXPLOSION PROTECTED TYPE INSTRUMENT12. EXPLOSION PROTECTED TYPEINSTRUMENTIn this section, further requirements and differences
IM 01E20C02-01E12-212. EXPLOSION PROTECTED TYPE INSTRUMENT(3) InstallationWARNING• All wiring shall comply with local installationrequirements and lo
IM 01E20C02-01E12-312. EXPLOSION PROTECTED TYPE INSTRUMENT(3) OperationWARNING• “OPEN CIRCUIT BEFORE REMOVING COV-ERS.”• “SEAL ALL CONDUITS WITHIN 18
IM 01E20C02-01E12-412. EXPLOSION PROTECTED TYPE INSTRUMENT(3) OperationFor CSA C22.2 SeriesWARNINGWARNING :OPEN CIRCUIT BEFORE REMOV-ING COVER.OUVRIR
IM 01E20C02-01E12-512. EXPLOSION PROTECTED TYPE INSTRUMENT(3) OperationWARNING• After de-energizing, delay 20 minutes beforeopening.• Take care not t
IM 01E20C02-01E12-612. EXPLOSION PROTECTED TYPE INSTRUMENT• Apply a nonhardening sealant to the terminal boxconnection port and to the threads on the
EX-B03E1INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROOF EQUIPMENTINSTALLATION AND OPERATING PRECAUTIONS FORTIIS FLAMEPROOF EQUIPMENTApparat
EX-B03E2INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROOF EQUIPMENT4. Installation of Flameproof Ap-paratus(1) Installation AreaFlameproof ap
IM 01E20C02-01E3-13. INSTALLATION3. INSTALLATIONWARNINGInstallation of the magnetic flowmeter must beperformed by expert engineer or skilled person-n
EX-B03E3INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROOF EQUIPMENT6. Maintenance of FlameproofApparatusTo maintain the flameproof apparatus,
IM 01E20C02-01EREVISION RECORDTitle: AXFA14G/C Magnetic Flowmeter Remote Converter[Hardware Edition/Software Edition]AXF Magnetic Flowmeter Integral F
IM 01E20C02-01EEdition Date Page Revised Item9th Jan. 2008 1-1 Added the postscript about PROFIBUS PA protocol type.1-2 1.1 Added the warning note on
IM 01E20C02-01EEdition Date Page Revised Item10th June 2012 1-3 Added the "Trademarks".2-1 2.2 Deleted the fuse from item of accessories.4-2
IM 01E20C02-01E4-14. WIRING4. WIRINGThis chapter describes the wiring on the converter sideonly. For information relating to wiring on theflowtube s
IM 01E20C02-01E4-24. WIRINGFinished diameter: 10.5 mm (0.413")Maximum length: 100 m (330 ft)Maximum temperature: 80°C (176°F)IMPORTANTIf the cab
IM 01E20C02-01E4-34. WIRINGNOTE• For excitation and power cables, always use acrimp terminal with an insulation cover.• Use crimp tools from the manu
IM 01E20C02-01E4-44. WIRING(3) Conduit WiringWhen wiring the conduits, pass the conduit through thewiring connection port, and utilize the waterproof
IM 01E20C02-01E4-54. WIRING4.4.3 Precautions for Wiring of PowerSupply CablesWhen connecting to the power supply, observe thepoints below. Failure t
IM 01E20C02-01E4-64. WIRING4.4.5 GroundingCAUTIONBe sure to connect the protective grounding ofthe AXFA14 with a cable of 2mm2 or larger crosssection
IM 01E20C02-01E4-74. WIRING(2) Connection with the Remote Flowtube(Explosion proof Type, Size 2.5 to 400 mm(0.1 to 16 in.))In case of explosion proof
iCONTENTSIM 01E20C02-01E10th Edition: June 2012All Rights Reserved, Copyright © 2003, Yokogawa Electric CorporationContents1. INTRODUCTION ...
IM 01E20C02-01E4-84. WIRINGF0417.EPSProtective diodePULSE OUTPULSE OUTAXFA14AXFA14DO+DO-DO+DO-Output voltage: 24 V DC 20%• Current: 150 mA or less
IM 01E20C02-01E5-15. BASIC OPERATING PROCEDURES5.BASIC OPERATING PROCEDURES (USING THE DISPLAY UNIT)The modification of data settings from the displa
IM 01E20C02-01E5-25. BASIC OPERATING PROCEDURES5.1 Operating PanelConfiguration andFunctions(1) Data display area1st line (Display Select1), 2nd line
IM 01E20C02-01E5-35. BASIC OPERATING PROCEDURES5.2 Display Unit Setting MethodsNOTEBefore changing any settings, be sure to check the corresponding s
IM 01E20C02-01E5-45. BASIC OPERATING PROCEDURESA screen is displayed to confirm whether or not thesystem is to enter Setting Mode.Press the switch a
IM 01E20C02-01E5-55. BASIC OPERATING PROCEDURES5.2.2 Setting ModeWhen the Setting Mode has been activated using the procedure from Section 5.2.1, par
IM 01E20C02-01E5-65. BASIC OPERATING PROCEDURESSub-item Parameter Search Mode has been accessedin this screen.Touch the switch to move the cursor to
IM 01E20C02-01E5-75. BASIC OPERATING PROCEDURES5.3.2 Setting Example for Numeric-Type Data: Flow rate spanThis example describes the setting of the f
IM 01E20C02-01E5-85. BASIC OPERATING PROCEDURESWhen the switch is touched, the entiredisplay flashes on and off. Confirm that the settinghas been c
IM 01E20C02-01E5-95. BASIC OPERATING PROCEDURESUpon selection of C: Basic Setup, the cursor willbe positioned at C10: Tag No. (Sub-item selectionscre
iiCONTENTSIM 01E20C02-01E6. PARAMETER DESCRIPTION ... 6-16.1 Parameters ...
IM 01E20C02-01E6-16. PARAMETER DESCRIPTION6. PARAMETER DESCRIPTION6.1 ParametersWith the exception of parameters that were specifiedby the customer u
IM 01E20C02-01E6-26. PARAMETER DESCRIPTION6.3 Parameter List Overview(1) Item A (Menu A): Display itemsMenu A contains the instantaneous flow rate, t
IM 01E20C02-01E6-36. PARAMETER DESCRIPTIONItemNameDisplay unit(BRAIN)Data rangeDisplay unit/BRAINDefault value(*): Indicated itemUnitsR/WPosition of
IM 01E20C02-01E6-46. PARAMETER DESCRIPTION(3) Item C (Menu C): Basic Setting itemsMenu C principally contains the basic setting items for the flowtub
IM 01E20C02-01E6-56. PARAMETER DESCRIPTIONT0604-2.EPSItemNameDisplay unit(BRAIN)Data rangeDisplay unit/BRAINDefault value(*): Indicated itemUnitsR/WP
IM 01E20C02-01E6-66. PARAMETER DESCRIPTION(5) Item E (Menu E): Pulse Setting itemsMenu E contains items relevant to pulse output. This is used to set
IM 01E20C02-01E6-76. PARAMETER DESCRIPTIONT0607-2.EPSItemNameDisplay unit(BRAIN)Data rangeDisplay unit/BRAINDefault value(*): Indicated itemUnitsR/WP
IM 01E20C02-01E6-86. PARAMETER DESCRIPTIONT0608-2.EPSItemNameDisplay unit(BRAIN)Data rangeDisplay unit/BRAINDefault value(*): Indicated itemUnitsR/WP
IM 01E20C02-01E6-96. PARAMETER DESCRIPTION(8) Item H (Menu H): Display Setting itemsMenu H contains setting items that are relevant to display on the
IM 01E20C02-01E6-106. PARAMETER DESCRIPTIONT0610-2.EPSItemNameDisplay unit(BRAIN)Data rangeDisplay unit/BRAINDefault value(*): Indicated itemUnitsR/W
iiiCONTENTSIM 01E20C02-01E9. ACTUAL OPERATION ... 9-19.1 Pre-ope
IM 01E20C02-01E6-116. PARAMETER DESCRIPTION(12) Item N (Menu N): Loop Test Setting itemsMenu N contains items that are relevant to the execution of l
IM 01E20C02-01E6-126. PARAMETER DESCRIPTION6.4 Parameter Description(1) Menu B: Easy Setup itemsThose parameters with a high frequency of use havebee
IM 01E20C02-01E6-136. PARAMETER DESCRIPTIONnumber of 2 or greater for the next digit to theright, regardless of the position of the decimalpoint.Exam
IM 01E20C02-01E6-146. PARAMETER DESCRIPTIONExample 1: To count in 1 Ml (mega-liter) stepswith flow rate span = 100 m3/hSince 1 Ml = 103 x m3, k Unit/
IM 01E20C02-01E6-156. PARAMETER DESCRIPTIONB41/H11: Display Select2 and B42/H12: DisplaySelect3 as described below. (For more details, refer toChapte
IM 01E20C02-01E6-166. PARAMETER DESCRIPTIONNOTE· When this product is used in combination withany flowtube that does not support enhanceddual frequen
IM 01E20C02-01E6-176. PARAMETER DESCRIPTION[C45: Density Unit] Setting of the density units formass flow rateThis parameter selects the units for den
IM 01E20C02-01E6-186. PARAMETER DESCRIPTION[D20: Total Execution] Operation setting for thetotalization functionThis parameter sets “Start” and “Stop
IM 01E20C02-01E6-196. PARAMETER DESCRIPTION(4) Menu E: Pulse Setting itemsMenu E contains items relevant to pulse output.NOTEFor pulse output from th
IM 01E20C02-01E6-206. PARAMETER DESCRIPTION(5) Menu F: Status Functions Setting itemsMenu F contains setting items relevant to status Input/Output fu
IM 01E20C02-01E1-11. INTRODUCTION1. INTRODUCTIONThis instrument has been adjusted at the factory beforeshipment.To ensure correct use of the instrume
IM 01E20C02-01E6-216. PARAMETER DESCRIPTION[F21: DIO Function] Setting of the function for the DIO status input/output terminalThis parameter sets th
IM 01E20C02-01E6-226. PARAMETER DESCRIPTION[F22: DO Active Mode] Setting of the active modefor DO terminalOperations are performed in accordance with
IM 01E20C02-01E6-236. PARAMETER DESCRIPTIONNOTE Multiple ranges settingParameters from F30 to F41 are used with theautomatic multiple ranges and the
IM 01E20C02-01E6-246. PARAMETER DESCRIPTIONParameter setting sequence(for automatic multiple ranges switching)F0605.EPSF20: DO FunctionSelect a funct
IM 01E20C02-01E6-256. PARAMETER DESCRIPTIONMultiple Ranges Setting 2:Multiple ranges switching via externalstatus input For both the forward and rev
IM 01E20C02-01E6-266. PARAMETER DESCRIPTION(6) Menu G: Alarm Setting items(Refer to Section 6.5: Alarm Functions for moredetails.)Menu G principally
IM 01E20C02-01E6-276. PARAMETER DESCRIPTIONOutput Example 2The high alarm (H) is set to 80% or more of the flowrate span; the low-low alarm (LL), to
IM 01E20C02-01E6-286. PARAMETER DESCRIPTION[G14: H/L Alarm Hys] Setting of upper/lower alarmvalue hysteresis widthThis parameter sets the hysteresis
IM 01E20C02-01E6-296. PARAMETER DESCRIPTION[G33: Alm-HH/LL] Alarm recognition of “HH/LL Alarm”(Refer to the descriptions of G12 and G13 for moredetai
IM 01E20C02-01E6-306. PARAMETER DESCRIPTION[G45: Alm Record3] Alarm record3This parameter is used to display the third most-recentalarm, and the alar
IM 01E20C02-01E1-21. INTRODUCTIONIMPORTANTAn IMPORTANT sign denotes that attention isrequired to avoid damage to the instrument orsystem failure.NOTE
IM 01E20C02-01E6-316. PARAMETER DESCRIPTIONNOTEIf “2.4mA or less” has been set for G21:4-20mAAlarm Out, 2.4mA or less will be output upon analarm occ
IM 01E20C02-01E6-326. PARAMETER DESCRIPTIONExample 1: Step inputF0614.EPS10%1%Step signalFlow rate valueafter rate limitprocessing63.2%100 225Dead ti
IM 01E20C02-01E6-336. PARAMETER DESCRIPTION[J40: Memo 1] Setting of memo 1[J41: Memo 2] Setting of memo 2[J42: Memo 3] Setting of memo 3These paramet
IM 01E20C02-01E6-346. PARAMETER DESCRIPTION(11) Menu N: Loop Test Setting itemsMenu N contains items that are relevant to loop testing.[N10: Test Mod
IM 01E20C02-01E6-356. PARAMETER DESCRIPTIONF0617.EPSDefault setting (Enable)P20:Write Protect NoP20:Write Protect YesF0618.EPSWrite protection (Prote
IM 01E20C02-01E6-366. PARAMETER DESCRIPTION6.5.2 Alarm SelectionThe display and output differs depending on the alarmlevels. Certain types of alarm m
IM 01E20C02-01E6-376. PARAMETER DESCRIPTION(3) Display and output condition for setting alarm occurrences50Span > 10m/s51Span < 0.1m/s52TTL>
IM 01E20C02-01E6-386. PARAMETER DESCRIPTION6.5.3 Alarms & Warning MessagesSystem Alarms (Device breakdown or inability to obtain correct measurem
IM 01E20C02-01E6-396. PARAMETER DESCRIPTIONSetting Alarms (Device is normal but errors have been made in the setting of parameters.)Display unit/BRAI
IM 01E20C02-01E6-406. PARAMETER DESCRIPTION6.6 Precautions for theAXF Integral Flow-meterAlthough the AXF integral flowmeter’s softwareconfigurations
IM 01E20C02-01E1-31. INTRODUCTION• Care should be taken to prevent the build up ofdirt, dust or other substances on the displaypanel glass or data pl
IM 01E20C02-01E7-17. OPERATION VIA BRAIN TERMINAL (BT200)7.OPERATION VIA BRAIN TERMINAL (BT200)NOTEThis chapter describes the AXFA14 converter asan e
IM 01E20C02-01E7-27. OPERATION VIA BRAIN TERMINAL (BT200)Use the function key [F2] CAPS to select betweenuppercase and lowercase (for letters only).
IM 01E20C02-01E7-37. OPERATION VIA BRAIN TERMINAL (BT200)7.2 AXFA14 OperationUsing a BT200This section describes procedures for setting parametersusi
IM 01E20C02-01E7-47. OPERATION VIA BRAIN TERMINAL (BT200)(2) Upload/download function of BT200Upload function is used when the parameters of oneAXFA1
IM 01E20C02-01E7-57. OPERATION VIA BRAIN TERMINAL (BT200)7.3.1 BT200 Setting of Selection-Type Data: Flow rate unitsIn this example, the flow rate un
IM 01E20C02-01E7-67. OPERATION VIA BRAIN TERMINAL (BT200)7.3.2 BT200 Setting of Numeric-Type Data: Flow rate spanIn this example, the flow rate span
IM 01E20C02-01E7-77. OPERATION VIA BRAIN TERMINAL (BT200)7.3.3 BT200 Setting of Alphanumeric-Type Data: Tag numberIn this example, the tag number spe
IM 01E20C02-01E8-18. OPERATION VIA HART COMMUNICATOR8.OPERATION VIA HART COMMUNICATORNOTEThis chapter describes the AXFA14 as anexample.Note: HART is
IM 01E20C02-01E8-28. OPERATION VIA HART COMMUNICATOR8.2 Interconnection between AXFA14 and HARTConfiguration ToolThe HART Configuration Tool can inte
IM 01E20C02-01E8-38. OPERATION VIA HART COMMUNICATOR8.3 Basic Setup Tag and Device InformationThe tag number and device information can be checkedas
IM 01E20C02-01E1-41. INTRODUCTION1.4 ATEX DocumentationThis procedure is only applicable to the countries inEuropean Union.GBAll instruction manuals
IM 01E20C02-01E8-48. OPERATION VIA HART COMMUNICATOR8.4.3 Self-diagnosticThe self-diagnostic function of the AXFA14 is ex-plained in Section 6.5 “Ala
IM 01E20C02-01E8-58. OPERATION VIA HART COMMUNICATORIMPORTANTThe D/A trim should be executed only at singlerange mode. If the D/A trim is executed at
IM 01E20C02-01E8-68. OPERATION VIA HART COMMUNICATOR(2) Activating the multidrop modeAbout the procedure to call up the Polling display,please refer
IM 01E20C02-01E8-78. OPERATION VIA HART COMMUNICATOR8.4.6 Menu Tree for DD (HART 5)1 Device setup1 Process Variables PV % rngePVPV AOTotlReverse Totl
IM 01E20C02-01E8-88. OPERATION VIA HART COMMUNICATORData(*1)Parameterof BRAIN protocol Read/Write 4 Detailed Setup 1 Basic Setup1 Tag2 PV Damping3 MF
IM 01E20C02-01E8-98. OPERATION VIA HART COMMUNICATORParameterof BRAIN protocolData(*1) Read/Write 5 HART output1 Poll addr2 Num req preams3 Burst mod
IM 01E20C02-01E8-108. OPERATION VIA HART COMMUNICATORData(*1)RRRR––––––––Parameterof BRAIN protocol Read/Write P20P21P22P23P–––u/dRWWRB23/C42W5 Revie
IM 01E20C02-01E8-118. OPERATION VIA HART COMMUNICATORReview 1Ta gPV DampingMeasure ModeLow MFHigh MFLow MF(EDF)High MF(EDF)Nominal Size unitNominal S
IM 01E20C02-01E8-128. OPERATION VIA HART COMMUNICATOR8.4.7 Menu Tree for DTM (HART 5)Process VariablesPVPV % rngePV AOPV SpanPV DampingTotlReverse To
IM 01E20C02-01E8-138. OPERATION VIA HART COMMUNICATOR Read/Write DataRenewing(*1)Parameterof BRAINprotocolCDDiag and ServiceOutput TestLoop testTest
IM 01E20C02-01E1-51. INTRODUCTIONLTLVPLESTSLOHBGROMCZSK
IM 01E20C02-01E8-148. OPERATION VIA HART COMMUNICATOR Read/Write DataRenewing(*1)Parameterof BRAINprotocolEPulse SetTotal SetNominal Size UnitNominal
IM 01E20C02-01E8-158. OPERATION VIA HART COMMUNICATOR Read/Write DataRenewing(*1)Parameterof BRAINprotocolConfigurationAux4-20mA Low Cut4-20mA Low Lm
IM 01E20C02-01E8-168. OPERATION VIA HART COMMUNICATOR Read/Write DataRenewing(*1)Parameterof BRAINprotocolCalibrationFWrite ProtectGAuto Zero ExeMagf
IM 01E20C02-01E9-19. ACTUAL OPERATION9. ACTUAL OPERATIONAfter you have installed the flowtube into the processpiping, wired the input/output terminal
IM 01E20C02-01E9-29. ACTUAL OPERATION9.1.1 Zero Adjustment Using Display Unit SwitchesThis section describes the procedure for zero adjustment using
IM 01E20C02-01E9-39. ACTUAL OPERATIONAuto zero adjustment function is being executed(about 30 seconds).When zero adjustment function has been complet
IM 01E20C02-01E9-49. ACTUAL OPERATIONTouch the switch twelve times to move thecursor to “Ext Auto Zero (I)”.Touch the switch to select “Ext Auto Z
IM 01E20C02-01E10-110. MAINTENANCE10. MAINTENANCE10.1 MaintenanceWARNING• Maintenance work must be carried out by thetrained personnel having knowled
IM 01E20C02-01E10-210. MAINTENANCE10.1.2.2 Changing the Display Unit Direction90 Degrees(1) Hold the display unit with your hand and removethe two mo
IM 01E20C02-01E10-310. MAINTENANCE10.2 Setting of SwitchesIMPORTANT•Removing and installing cover are necessaryfor setting switches. Perform removing