<6. Wiring>
6-1
IM 01C25B01-01E
6. Wiring
6.1 Wiring Precautions
IMPORTANT
Lay wiring as far as possible from electrical
noise sources such as large capacity
transformers, motors, and power supplies.
Remove the electrical connection dust cap
before wiring.
All threaded parts must be treated with
waterproong sealant. (A non-hardening
silicone group sealant is recommended.)
To prevent noise pickup, do not pass signal
and power cables through the same ducts.
Explosion-protected instruments must
be wired in accordance with specic
requirements (and, in certain countries,
legal regulations) in order to preserve the
effectiveness of their explosion-protected
features.
The terminal box cover is locked by an
Allen head bolt (a shrouding bolt) on ATEX
ameproof type transmitters. When the
shrouding bolt is driven clockwise using
an Allen wrench, it goes in. The cover lock
can then be released and the cover can
be opened by hand. See subsection 8.4
“Disassembly and Reassembly” for details.
Plug and seal an unused conduit connection.
6.2 Selecting the Wiring
Materials
(a) Use stranded leadwires or cables which are
the same as or better than 600 V grade PVC
insulated wire (JIS C3307) or its equivalent.
(b) Use shielded wires in areas that are susceptible
to electrical noise.
(c) In areas with higher or lower ambient
temperatures, use appropriate wires or cables.
(d) In environment where oils, solvents, corrosive
gases or liquids may be present, use wires or
cables that are resistant to such substances.
(e) It is recommended that crimp-on solderless
terminal lugs (for 4 mm screws) with insulating
sleeves be used for leadwire ends.
6.3 Connections of External
Wiring to Terminal Box
6.3.1 Power Supply Wiring Connection
Connect the power supply wiring to the SUPPLY +
and terminals. When /AL is specied, also refer to
subsection 6.3.5.
Power supply
+
Transmitter terminal box
F0601.ai
SUPPLY
PULSE
CHECK
ALARM
Figure 6.1 Power Supply Wiring Connection
6.3.2 External Indicator Connection
Available only when /AL is not specied.
Connect wiring for external indicators to the CHECK
+ and terminals.
(Note) Use a external indicator whose internal resistance is 10 Ω
or less.
Transmitter terminal box
External indicator
F0602.ai
Power supply
+
SUPPLY
PULSE
CHECK
ALARM
Figure 6.2 External Indicator Connection
6.3.3 Communicator Connection
Connect the BT200 or HART Communicator to the
SUPPLY + and terminals. (Use hooks.)
SUPPLY
PULSE
CHECK
ALARM
Transmitter terminal box
BT200
F0603.ai
Power supply
+
Ignore the polarity since the
BT200 is AC-coupled to the
terminal box.
Figure 6.3 BT200 Connection