Yokogawa JUXTA VJRK User Manual

Browse online or download User Manual for Sensors Yokogawa JUXTA VJRK. Yokogawa JUXTA VJRK User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 6
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Users
Manual
Model VJRK
Limit Alarm (RTD Input Type)
IM 77J01R21-01E
IM 77J01R21-01E
1st Edition : Aug. 2006 (YK)
4. MODEL AND SUFFIX CODES
VJRK-0 2 - 0/T0
Model
Number of outputs
2: 2 outputs
Power supply
6: 100-240 V AC/DC
(Operating range: 85 to 264 V)
7: 15-30 V DC
(Operating range: 12 to 36 V)
Input signal
1: Pt100 (ITS-90)
2: JPt100 (JIS'89)
3: Pt50 (JIS'81)
4: Pt100 (IPTS-68)
Output signal
T: Alarm output (2 points of relay contacts)
Optional specification
Blank: With socket
/
SN: Without socket
5. MOUNTING METHODS
5.1 Wall Mounting
Loosen the main unit-fixing screw to disconnect the main
unit from the socket. Next, anchor the socket onto the wall
with screws. Then, plug the main unit into the socket and se-
cure the main unit with the main unit-fixing screw.
Main
unit-fixing
screw
Socket
Main unit
Hole for main
unit-fixing screw
Mounting
screws
<Mounting Dimensions>
Unit: mm
29.5 or more
22±0.2
59±0.3
2-M4 or 2-ø4.5 or more
Fig.5.1
1. CAUTIONARY NOTES FOR SAFE
USE OF THE PRODUCT
This user’s manual should be carefully read before installing
and operating the product. The following symbol is used on
the product and in this manual to eusure safe use.
This symbol is displayed on the product when it is
necessary to refer to the users manual for infor-
mation on personnel and instrument safety. This
symbol is displayed in the users manual to indi-
cate precautions for avoiding danger to the opera-
tor, such as an electric shock.
The following symbols are used only in this manual.
IMPORTANT
Indicates that operating the hardware or software
in a particular manner may cause damage or result
in a system failure.
NOTE
Draws attention to essential information for under-
standing the operations and/or functions of the
product.
2.
CHECKING THE PRODUCT SPECIFICATIONS
AND THE CONTENTS OF THE
PACKAGE
(1) Model and Specifications Check
Check that the model and specifications indicated on the
nameplate attached to the side face of the main unit are as
ordered.
(2) Contents of the Package
Check that the package contains the following items:
VJRK: 1
User’s manual (this manual: IM 77J01R21-01E): 1
Accessories:
Tag number label: 1 sheet
Range label: 1 sheet
3. GENERAL
This plug-in type Limit Alarm for RTD input receives RTD sig-
nal.
Each parameter setting can be changed using a PC
(VJ77 PC-based Parameters Setting Tool) or the Handy
Terminal (JHT200 ).
Keep this manual in a safe place.
Network Solutions Business Divisiion
2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 Japan
Phone: +81-422-52-7179 Facsimile: +81-422-52-6619
Page view 0
1 2 3 4 5 6

Summary of Contents

Page 1 - Limit Alarm (RTD Input Type)

User’sManualModel VJRKLimit Alarm (RTD Input Type)IM 77J01R21-01EIM 77J01R21-01E1st Edition : Aug. 2006 (YK)4. MODEL AND SUFFIX CODESVJRK-0 2 - 0/T0M

Page 2 - AND CONNECTION OF SETTING

2All Rights Reserved. Copyright © 1999, Yokogawa M&C Corporation IM 77J01R21-01E 1st Edition : 2006.08.15-005.2 DIN Rail MountingLocate the VJR

Page 3 - 9. SETTING PARAMETERS

3IM 77J01R21-01E 1st Edition : 2006.08.15-008.2 Connecting the Setting ToolsConnect the modular jack conversion adapter (E9786WH) tothe JUXTA commu

Page 4

4All Rights Reserved. Copyright © 1999, Yokogawa M&C Corporation IM 77J01R21-01E 1st Edition : 2006.08.15-009.2.4 Alarm ON Delay and Alarm OFF

Page 5 - 11. LIST OF PARAMETERS

5IM 77J01R21-01E 1st Edition : 2006.08.15-0011. LIST OF PARAMETERS No. Item Display 01 Model MODEL 02 Tag No. TAG NO 03 Self-check result S

Page 6 - 12.1 Calibration Apparatus

6All Rights Reserved. Copyright © 1999, Yokogawa M&C Corporation IM 77J01R21-01E 1st Edition : 2006.08.15-0012. MAINTENANCEThe product enters the

Comments to this Manuals