Please read through this User’s Manual before use for correct handling.
Please keep this User’s Manual for future reference.
Model MXD
Universal Computing Unit
(1-input, Isolated 1-output Type)
<with Contact I/O>
CAUTIONARY NOTES FOR SAFE USE OF THE PRODUCT
This User’s Manual should be carefully read before installing and oper-
ating the product. The following symbol is used on the product and in
this manual to ensure safe use.
This symbol is displayed on the product when it is
necessary to refer to the Users Manual for information on
personnel and instrument safety. This symbol is displayed
in the Users Manual to indicate precautions for avoiding
danger to the operator, such as an electric shock.
The following symbols are used only in this manual.
IMPORTANT
Indicates that operating the hardware or software in a
particular manner may cause damage or result in a system
failure.
NOTE
Draws attention to essential information for understanding
the operations and/or functions of the product.
CHECKING PRODUCT SPECIFICATIONS AND PACKAGED ITEMS
(1) Checking the Model and Product Specifications
Check that the model and specifications indicated on the nameplate
attached to the main unit are as ordered.
(2) Packaged Items
Check that the package contains the following items:
MXD: 1
Range label: 1
Spacer: 1
Receiving resistor (for current input): 1
User’s Manual (this manual: IM 77J04X12-01E): 1
* When the optional specification “/R250” is specified, the 250
receiving resistor is attached. When the optional specification
“/R250” is not specified, the 100 receiving resistor is attached.
GENERAL
This plug-in type universal computing unit receives DC current or DC
voltage signals, applies various computing functions to them, and then
converts them into isolated DC current or DC voltage signals.
IM 77J04X12-01E
1st Edition Aug. 2005 (YK)
MODEL AND SUFFIX CODES
Model
Function
A: Free program
L: Analog memory
M
: Peak holder
N: Bottom holder
P: Program setter (Note 1)
Q
: Integrated pulse output
Input signal
A: 0 to 50 mA DC Span is 1 mA or more
B: 0 to 10 mA DC
Span is 0.1 mA or more
1: 10 to +10 V DC Span is 0.1 V or more
2: 2 to +2 V DC Span is 10 mV or more
N: No analog input (Note 1)
Output signal
A: 0 to 20 mA DC Span is 2 mA or more
B: 0 to 5 mA DC Span is 1 mA or more
1: 0 to 10 V DC Span is 0.1 V or more
2: 0 to 100 mV DC Span is 10 mV or more
3: 10 to +10 V DC Span is 0.2 V or more
4:
100 to +100 mV DC Span is 20 mV or more
Power supply
1: 15-40 V DC (Operating range: 12 to 48 V DC)
2: 100-240 V AC (Operating range: 85 to 264 V AC)
Optional specification
/R250: With 250 receiving resistor
Note 1: The input signal suffix code N is fixed when the program
setter is selected.
However, the analog input is adjusted and inspected by 1 to
5 V DC of the input signal suffix code 1 before shipment.
MXD- N - *B/
IM 77J04X12-01E
Page view 0
1 2 3 4 5 6

Summary of Contents

Page 1 - IM 77J04X12-01E

User’sManualNetwork Solutions Business Division2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 JapanPhone: +81-422-52-7179 Facsimile: +81-422-52-6793Pl

Page 2 - 3. EXTERNAL WIRING

2IM 77J04X12-01E 1st Edition Aug 31,2005-001. MOUNTING METHODNOTEPlug/disconnect the main unit into/from the socketvertically to the socket face. Oth

Page 3 - 5. SETTING PARAMETERS

3IM 77J04X12-01E 1st Edition Aug 31,2005-00Power Supply and IsolationPower supply rated voltage:15-40 V DC or 100-240 V AC 50/60 HzPower supply i

Page 4 - 6. COMPUTING FUNCTIONS

4IM 77J04X12-01E 1st Edition Aug 31,2005-006. COMPUTING FUNCTIONS6.1 MXD-A Free ProgramThis computing unit is used to meet individual applications by

Page 5 - 7. LIST OF PARAMETERS

5IM 77J04X12-01E 1st Edition Aug 31,2005-007. LIST OF PARAMETERS7.1 MXD (except for the function suffix code “A”)•••••••••MODELTAG NOSELF CHKDISPLAY1I

Page 6 - 8. MAINTENANCE

6IM 77J04X12-01E 1st Edition Aug 31,2005-008. MAINTENANCEThe product starts running immediately when the power is turned on;however, it needs 10 to 15

Comments to this Manuals