Yokogawa EXA PH202 2-Wire pH/ORP Analyzer User Manual Page 28

  • Download
  • Add to my manuals
  • Print
  • Page
    / 138
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 27
IM 12B07D02-01E
Specification 2-15
WARNING
- Substitution of components may impair Intrinsic Safety
- To prevent ignition of flammable or combustible atmospheres, disconnect power
before servicing or read, understand and adhere to the manufacturer’s live
maintenance procedures.
x The cable used to interconnect the devices needs to comply with the following
parameters:
Loop resistance R’: 15 … 150 /km; Inductance per unit length L: 0,4 … 1 mH/km
Capacitance per unit length C’: 80 … 200 nF/km
(C’ = C’ line/line + 0,5 C’ line/screen if both line are floating)
(C’ = C’ line/line + C’ line/screen if the screen is connected to one line)
Length of spur cable: max. 30 m
Length of trunk cable: max. 1 km
Length of splice : max. 1 m
WARNING
- Substitution of components may impair Intrinsic Safety
- To prevent ignition of flammable or combustible atmospheres, disconnect power before
servicing or read, understand and adhere to the manufacturer’s live maintenance
procedures.
Application Doc. No.: IKE025-A10 P.4 to P.5
Page view 27
1 2 ... 23 24 25 26 27 28 29 30 31 32 33 ... 137 138

Comments to this Manuals

No comments