User’sManualAXRTwo-wire Magnetic FlowmeterIntegral Flowmeter[Style:S2]IM 01E30D01-01ENIM 01E30D01-01EN3rd Edition
<1. INTRODUCTION>1-4IM 01E30D01-01EN1.3 ATEX DocumentationThis is only applicable to the countries in European Union.GBDKIENLSFPFDSLTLVPLE
<7. OPERATION VIA BRAIN TERMINAL (BT200)>7-6IM 01E30D01-01EN7.3.1 BT200 Setting of Selection-Type Data: Flow rate unitsInthisexample,th
<7. OPERATION VIA BRAIN TERMINAL (BT200)>7-7IM 01E30D01-01EN7.3.2 BT200 Setting of Numeric-Type Data: Flow rate spanInthisexample,the
<7. OPERATION VIA BRAIN TERMINAL (BT200)>7-8IM 01E30D01-01EN7.3.3 BT200 Setting of Alphanumeric-Type Data: Tag numberInthisexample,the
<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>8-1IM 01E30D01-01EN8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)ThisChapterdescrib
<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>8-2IM 01E30D01-01EN(2) ConrmtheinstalledDDrevisioninaccordance with the procedur
<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>8-3IM 01E30D01-01EN8.4 Basic Setupn ConrmationandChangeofTagandDevice Informati
<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>8-4IM 01E30D01-01EN8.7 Self-diagnostic FunctionsTheself-diagnosticfunctionoftheAXR
<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>8-5IM 01E30D01-01ENCAUTIONThe output adjustment function can match the 4mA and 20mA outp
<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>8-6IM 01E30D01-01EN(2) Activating the multidrop mode About the procedure to call up th
<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>8-7IM 01E30D01-01ENb.ConrmthenewHARTprotocolrevisionnumberCall up the Universal
<2. HANDLING PRECAUTIONS>2-1IM 01E30D01-01EN2. HANDLING PRECAUTIONSThis instrument has been inspected carefully at the factory before ship
<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>8-8IM 01E30D01-01EN8.9 Menu Tree for DD (HART 5)1 Device Setup1 Process Variables PV %
<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>8-9IM 01E30D01-01ENRead/WriteDataRenewing(*1)4 Detailed Setup 1 Basic Setup1 Tag2 PV Dam
<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>8-10IM 01E30D01-01EN5 HART Output1 Poll addr2 Num req preams3 Burst mode4 Burst option6D
<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>8-11IM 01E30D01-01ENParameterof BRAINprotocol(*2)Read/WriteDataRenewing(*1)(*3)P20––P23R
<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>8-12IM 01E30D01-01ENReview1TagPV DampingLow MF(IEL)High MF(IEL)Low MF(IEM)High MF(IEM)Lo
<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>8-13IM 01E30D01-01EN8.10 Menu Tree for DTM (HART 5)Process VariablesPVPV % rngePV AOPV
<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>8-14IM 01E30D01-01ENRead/WriteDataRenewing(*1)CDDiag and ServiceTestLoop testTest ModeTe
<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>8-15IM 01E30D01-01ENRead/WriteDataRenewing(*1)EPulse SetTotal SetLow MF(IEL)High MF(IEL)
<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>8-16IM 01E30D01-01ENRead/WriteDataRenewing(*1)Parameterof BRAINprotocol (*2)Configuratio
<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>8-17IM 01E30D01-01ENRead/WriteDataRenewing(*1)Parameterof BRAINprotocol (*2)CalibrationF
<2. HANDLING PRECAUTIONS>2-2IM 01E30D01-01EN2.4 Installation Location PrecautionsSelect the installation location with consideration to th
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-1IM 01E30D01-01EN9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)ThisChapterdescrib
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-2IM 01E30D01-01ENCongurationTool,downloadthemfromtheofcialHART programming si
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-3IM 01E30D01-01ENNOTEBefore updating any setting, remember to always check the paramet
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-4IM 01E30D01-01EN9.7 Self-diagnostic FunctionsTheHARTcongurationtoolcanbeused
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-5IM 01E30D01-01EN• Procedure of device variable simulationStep 1 Call up the paramete
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-6IM 01E30D01-01EN9.8.3 Burst ModeWhen the Burst mode is enabled, the transmitter cont
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-7IM 01E30D01-01EN(2) Burst mode setting procedure• Procedure to call up the displayD
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-8IM 01E30D01-01ENa. Burst CommandSelect the transmission data at Burst Command parame
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-9IM 01E30D01-01ENe. Burst ModeWhen the Burst mode is set to “Wired HART Enabled”, the
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-10IM 01E30D01-01ENb) AcknowledgeEventNoticationExecute AcknowledgeEventNoticati
<3. INSTALLATION>3-1IM 01E30D01-01EN3. INSTALLATION3.1 Piping Design PrecautionsWARNING Installationofthemagneticowmetermustbe pe
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-11IM 01E30D01-01ENTo release multidrop mode, call up the Poll addr display and set the
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-12IM 01E30D01-01EN9.9 Menu Tree for DD and DTM (HART 7)ABCDEF0905.aiProcess variables
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-13IM 01E30D01-01ENDiagnosis/ServiceTest/StatusStatusTime StampStatus group 1Status gro
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-14IM 01E30D01-01ENDetailed SetupBasic SetupTotal SetTotal UnitTotal ScaleTotal Decimal
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-15IM 01E30D01-01ENDetailed SetupFunction SetDO Function SetDO FunctionDO Active ModeFo
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-16IM 01E30D01-01ENDetailed SetupHART OutputPoll addrLoop current modeNum req preamsNum
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-17IM 01E30D01-01ENDetailed SetupDevice InformationField Device InformationManufacturer
<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>9-18IM 01E30D01-01ENReview1TagLong tagPV DampingLow MF(IEL)High MF(IEL)Low MF(IEM)High M
<10. ACTUAL OPERATION>10-1IM 01E30D01-01ENAfteryouhaveinstalledtheowtubeintotheprocess piping, wired the input/output terminals, s
<10. ACTUAL OPERATION>10-2IM 01E30D01-01EN10.1.1 Zero Adjustment Using Display Unit SwitchesThis section describes the procedure for zero a
<3. INSTALLATION>3-2IM 01E30D01-01EN(5) Precautions for Use of Liquid Sealing CompoundsIMPORTANTCare must be taken in using liquid sealing
<10. ACTUAL OPERATION>10-3IM 01E30D01-01ENSub-itemParameterSearch ModeMajor itemSub-itemselection (D)F1001.EPSM:Adjustment 21:Adjustment 2
<11. MAINTENANCE>11-1IM 01E30D01-01ENWARNING • Maintenance work must be carried out by the trained personnel having knowledge of safety st
<11. MAINTENANCE>11-2IM 01E30D01-01EN11.2 Components ReplacementWARNING • Component replacement must be carried out by the trained person
<11. MAINTENANCE>11-3IM 01E30D01-01EN(3) Assembling the Display Unit(1) Align the display unit in a straight with its connector located i
<11. MAINTENANCE>11-4IM 01E30D01-01EN11.2.2 AmplierReplacementIMPORTANTIncaseofamplierreplacement,itisnecessaryto perform the p
<11. MAINTENANCE>11-5IM 01E30D01-01EN11.3 Setting of Switches11.3.1 Setting of Burnout SwitchThe burnout function sets the direction of c
<11. MAINTENANCE>11-6IM 01E30D01-01EN11.4 Adhesion diagnostic functionThelong-termmeasurementofadhesiveuidsmayadverselyaffectthe
<11. MAINTENANCE>11-7IM 01E30D01-01EN11.4.1 Adhesion Diagnostic Using Display Unit SwitchesThis section describes the procedure for Adhesi
<11. MAINTENANCE>11-8IM 01E30D01-01ENSub-itemParameterSearch ModeMajor itemSub-itemselection (D)F1110.EPSK:Diagnosis11:Adh Status 10:Adhes
<11. MAINTENANCE>11-9IM 01E30D01-01EN11.5 Regular Inspection Items(1) Inspectionofmoisture-proonginsidetheterminal box: Once/year(2
<3. INSTALLATION>3-3IM 01E30D01-01EN• Mounting orientationIMPORTANTIf electrodes are perpendicular to the ground, air bubbles near the top
<11. MAINTENANCE>11-10IM 01E30D01-01EN11.7 TroubleshootingAlthoughmagneticowmetersrarelyrequiremaintenance,failuresmayoccurwhen
<11. MAINTENANCE>11-11IM 01E30D01-01EN11.7.2 Unstable ZeroSTARTCheck for the presence of valve leakage.● Confirm the flowmeter grounding.
<11. MAINTENANCE>11-12IM 01E30D01-01EN11.7.3 Disagreement Between Indication and Actual FlowNONONOYESNONOYESYESYESNOYESNONOYESSet the para
12-1IM 01E30D01-01EN <12. OUTLINE>n STANDARD SPECIFICATIONS ConverterThe contents of (*1) and (*2) described in the converterspecications
12-2IM 01E30D01-01EN <12. OUTLINE>HARTCommunication Signal:BRAIN or HART communication signal (superim-posed on 4 to 20 mA DC signals)Note:
12-3IM 01E30D01-01EN <12. OUTLINE>Totalizer Display Function (*2):Theowrateiscountedonecountatatimeaccord-ing to the setting of t
12-4IM 01E30D01-01EN <12. OUTLINE>Zero Adjustment Function (*2):By using the parameter setting, zero adjustment is carriedouttoensuretha
12-5IM 01E30D01-01EN <12. OUTLINE>GroundingRing/GroundingElectrode;• Grounding Ring (plate type) Stainless steel-JIS SUS316 (AISI 316 SS/E
12-6IM 01E30D01-01EN <12. OUTLINE>n STANDARD PERFORMANCEAccuracy:General-Purpose Use; Vs: Span setting value (m/s)Size in mm (in.)Spaninm
12-7IM 01E30D01-01EN <12. OUTLINE>Accuracy for Multi-drop of HART (generally accepted values)Vs: Span setting value (m/s)Size in mm (in.)Spa
<3. INSTALLATION>3-4IM 01E30D01-01EN(4) Terminal Box CoverIMPORTANTAs it is possible that the insulation will deteriorate, do not open the
12-8IM 01E30D01-01EN <12. OUTLINE>n NORMAL OPERATING CONDITIONSAmbient Temperature: General-purpose Use:–40 to +55°C (–40 to +131°F)Explosio
12-9IM 01E30D01-01EN <12. OUTLINE>n MODEL AND SUFFIX CODE●WaferTypeModel SufxCode Description Applicable ModelAXR025AXR040AXR050AXR065AX
12-10IM 01E30D01-01EN <12. OUTLINE>*5: Allowableuidpressureshouldalsobelimitedaccordingtouidtemperatureandpressure.*6: Even
12-11IM 01E30D01-01EN <12. OUTLINE>●FlangeTypeModel SufxCode Description Applicable ModelAXR025AXR040AXR050AXR065AXR080AXR100AXR150AXR20
12-12IM 01E30D01-01EN <12. OUTLINE>*1: Forexplosionprooftypes,specifytypesofexplosionproofcerticationusingtheoptionalcodes.
12-13IM 01E30D01-01EN <12. OUTLINE>n OPTIONAL SPECIFICATIONS ○Available – : Not availableItem SpecicationsApplicable ModelCodeGeneralExpl
12-14IM 01E30D01-01EN <12. OUTLINE>Item SpecicationsApplicable ModelCodeGeneralExplosion proofAXR***GAXR***CBolts, Nuts, and Gaskets (*2)Bo
12-15IM 01E30D01-01EN <12. OUTLINE>Item SpecicationsApplicable ModelCodeGeneralExplosion proofAXR***GAXR***CFive-point Calibration in User
12-16IM 01E30D01-01EN <12. OUTLINE>n EXTERNAL DIMENSIONS●LayLengthCode1,AXR080-AXR100,WaferTypeF1212.ai*1: When indicator code N is s
12-17IM 01E30D01-01EN <12. OUTLINE>●LayLengthCode2,AXR025,WaferTypeF1214.ai*1: When indicator code N is selected, subtract 5 mm (0.2
<3. INSTALLATION>3-5IM 01E30D01-01EN3.3 Mounting ProceduresNOTE• The tightening torque value to which gaskets must be tightened varies d
12-18IM 01E30D01-01EN <12. OUTLINE>●LayLengthCode2,AXR080-AXR100,WaferTypeUnit: mm (approx. inch)F1216.ai*1: When indicator code N i
12-19IM 01E30D01-01EN <12. OUTLINE>●LayLengthCode1,AXR025,JIS/ANSI/DINFlangeTypeF1218.ai*1: When indicator code N is selected, subt
12-20IM 01E30D01-01EN <12. OUTLINE>●LayLengthCode1,AXR040-AXR065,JIS/ANSI/DINFlangeTypeF1219.ai*1: When indicator code N is selecte
12-21IM 01E30D01-01EN <12. OUTLINE>●LayLengthCode1,AXR080-AXR100,JIS/ANSI/DINFlangeTypeF1220.aiUnit: mm (approx. inch)AXR080AXR100GC
12-22IM 01E30D01-01EN <12. OUTLINE>●LayLengthCode1,AXR150-AXR200,JIS/ANSI/DINFlangeTypeF1221.aiUnit: mm (approx. inch)AXR150AXR200G1
12-23IM 01E30D01-01EN <12. OUTLINE>●FlameproofPackingAdapterforTIISFlameproofType(OptionalcodeG11orG32)T1T2L18(0.71)GFAdapter bo
12-24IM 01E30D01-01EN <12. OUTLINE>nSIZINGDATA(Measurableowvelocityisfrom0m/s.)General-purpose Use;Flow velocitym/s*Measurable flo
<13. PED (PRESSURE EQUIPMENT DIRECTIVE)>13-1IM 01E30D01-01ENThis chapter describes further requirements and notices concerning the PED (Pre
<14. EXPLOSION PROTECTED TYPE INSTRUMENT>14-1IM 01E30D01-01EN14. EXPLOSION PROTECTED TYPE INSTRUMENTIn this section, further requirements
<14. EXPLOSION PROTECTED TYPE INSTRUMENT>14-2IM 01E30D01-01ENDigital Output: ON; 2Vdc, 120mA max., OFF; 30Vdcmax.,4mA,Um=250VExcitation
<3. INSTALLATION>3-6IM 01E30D01-01ENF0308a.ai *Nut (eight units)*Through-bolt (four units)*: These items can be ordered optionally. If
<14. EXPLOSION PROTECTED TYPE INSTRUMENT>14-3IM 01E30D01-01EN(6) Data PlateMODEL:SpeciedmodelcodeSUFFIX:Sufxcodesofthemodelcode
<14. EXPLOSION PROTECTED TYPE INSTRUMENT>14-4IM 01E30D01-01EN(3) Operation WARNING • “OPEN CIRCUIT BEFORE REMOVING COVERS.”• “SEALS ALL
<14. EXPLOSION PROTECTED TYPE INSTRUMENT>14-5IM 01E30D01-01ENWARNING IftheAXRismountedinanareawheretheuse of EPL Db equipment is
<14. EXPLOSION PROTECTED TYPE INSTRUMENT>14-6IM 01E30D01-01EN(6) Data PlateMODEL:SpeciedmodelcodeSUFFIX:Sufxcodesofthemodelcode
<14. EXPLOSION PROTECTED TYPE INSTRUMENT>14-7IM 01E30D01-01EN Intrinsically safety circuit• Maximum Voltage (Uo): 14 V• Maximum Current
<14. EXPLOSION PROTECTED TYPE INSTRUMENT>14-8IM 01E30D01-01EN(e) Insert the cable through the union cover, the union coupling, the clamp n
<Appendix1. Safety Instrumented Systems Installation>A1-1IM 01E30D01-01ENAppendix 1. Safety Instrumented Systems InstallationWARNING The c
<Appendix1. Safety Instrumented Systems Installation>A1-2IM 01E30D01-01ENTable A1.2 Proof TestingTesting method Tools required Expected ou
<Appendix1. Safety Instrumented Systems Installation>A1-3IM 01E30D01-01ENA1.2.10 Lifetime LimitsTheexpectedlifetimeoftheAXRis10yea
<Appendix1. Safety Instrumented Systems Installation>A1-4IM 01E30D01-01ENA1.3.2 AbbreviationsFMEDA Failure Mode, Effects and Diagnostic A
<3. INSTALLATION>3-7IM 01E30D01-01ENTable 3.3.3 Wafer Type Tightening Torque Values for Metal Piping and Permeable FluidsTighteningtorque
IM 01E30D01-01EN1IM 01E30D01-01EN<INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROOF EQUIPMENT>INSTALLATION AND OPERATING PRECAUTIONS FO
IM 01E30D01-01EN2IM 01E30D01-01EN<INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROOF EQUIPMENT>(4) Path length of joint surfaceOn a joi
IM 01E30D01-01EN3IM 01E30D01-01EN<INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROOF EQUIPMENT>(2) Flameproof Metal Conduit Wiring• Fo
IM 01E30D01-01EN4IM 01E30D01-01EN<INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROOF EQUIPMENT>CAUTIONDo not attempt to re-process threa
iIM 01E30D01-01ENRevision Information Title : AXRMagneticFlowmeterIntegralFlowmeter Manual No. : IM 01E30D01-01ENEdition Data Page Revised I
iIM 01E30D01-01ENAXR Two-wire Magnetic FlowmeterIntegral FlowmeterIM 01E30D01-01EN 3rd Edition3rd Edition: Aug. 2012 (KP)All Rights Reserved, Copyrig
<3. INSTALLATION>3-8IM 01E30D01-01EN(4) Tightening NutsTighten the nuts according to the torque values for metal piping in Table 3.3.4. Fo
<3. INSTALLATION>3-9IM 01E30D01-01ENTable 3.3.5 Wafer Type Tightening Torque Values for PVC PipingTightening torque values for PFA lining
<3. INSTALLATION>3-10IM 01E30D01-01ENTable3.3.8 CenteringDeviceIdentication(AXRLaylengthcode2,PFAlining)Flangeratings Size mm (
<3. INSTALLATION>3-11IM 01E30D01-01ENCAUTIONForaowmeterwithuorocarbonPFAlining,it is possible that the nuts may loosen as time pas
<3. INSTALLATION>3-12IM 01E30D01-01ENTable 3.3.11 Flange Type Tightening Torque Values for PVC PipingTightening torque values for PFA lini
<4. WIRING>4-1IM 01E30D01-01EN4. WIRINGThis section describes the wiring of the integral owmeter.WARNING Thewiringofthemagneticowme
<4. WIRING>4-2IM 01E30D01-01EN4.2 TerminalCongurationandTerminal WiringF0401.aiTerminalSymbolsFunctional groundingDescriptionPower sup
<4. WIRING>4-3IM 01E30D01-01ENForworkingontheelectricwiretubesortheexibletubes (PF1/2), remove the waterproof gland and attach t
<4. WIRING>4-4IM 01E30D01-01EN4.4 Grounding ConnectionIMPORTANTGroundingresistanceof100Ωorlessisnecessary. When the optional code
<4. WIRING>4-5IM 01E30D01-01ENF0410.aiIn case grounding rings are used.HazardrousareaGrounding ringNon-hazardrousareaClass A groundingIn ca
iiIM 01E30D01-01EN5.3 Parameter Setting Procedure ... 5-55.3.1 Setting Exampl
<4. WIRING>4-6IM 01E30D01-01ENThe description of the terminal symbols is shown in Table 4.5.1.Table 4.5.1 Terminal SymbolsNo. Terminal Sym
<4. WIRING>4-7IM 01E30D01-01ENF0415.aiSUPPLYDOPower supplycableFigure 4.6.2 Electric Cable Wiring (TIIS Explosion Proof Type)IMPORTANT• C
<4. WIRING>4-8IM 01E30D01-01EN60025014.7 20.6 28.9 42Power supply voltage E (V DC)R=0.0236E−14.7F0416.aiDigitalCommunicationRange(BRAIN or
<4. WIRING>4-9IM 01E30D01-01ENIMPORTANTPrecaution for Pulse Output• As this is a transistor contact (insulated type), give attention to pr
<4. WIRING>4-10IM 01E30D01-01ENn WiringExamples(General-purposeUse/ExplosionProofTypeexceptTIIS)Table4.6.2 General-purposeUs
<4. WIRING>4-11IM 01E30D01-01ENTable4.6.3 General-purposeUse/ExplosionProofTypeexceptTIISWiringExamples(SimultaneousCurrent-Pu
<4. WIRING>4-12IM 01E30D01-01ENTable4.6.4 General-purposeUse/ExplosionProofTypeexceptTIISWiringExamples(DigitalExternalIndica
<4. WIRING>4-13IM 01E30D01-01ENn WIRING EXAMPLE (TIIS Explosion Proof Type)Table 4.6.5 TIIS Explosion Proof Type Wiring Examples (Current
<4. WIRING>4-14IM 01E30D01-01ENTable 4.6.6 TIIS Explosion Proof Type Wiring Examples (Simultaneous Current-Pulse Output)Connection Descrip
<4. WIRING>4-15IM 01E30D01-01ENTable 4.6.7 TIIS Explosion Type Wiring Examples (Digital External Indicator Using Current Output)Connection
iiiIM 01E30D01-01EN8.8 HARTSpecicFunctions ... 8-48.8.1 Trim Analog
<5. BASIC OPERATING PROCEDURES (USING THE DISPLAY UNIT)>5-1IM 01E30D01-01EN5. BASIC OPERATING PROCEDURES (USING THE DISPLAY UNIT)Both of fo
<5. BASIC OPERATING PROCEDURES (USING THE DISPLAY UNIT)>5-2IM 01E30D01-01EN5.1 Operating Panel CongurationandFunctionsF0501.EPS(4) Reve
<5. BASIC OPERATING PROCEDURES (USING THE DISPLAY UNIT)>5-3IM 01E30D01-01EN5.2 Display Unit Setting MethodsNOTEBefore changing any setting
<5. BASIC OPERATING PROCEDURES (USING THE DISPLAY UNIT)>5-4IM 01E30D01-01ENF0503-2.aiEntry Mode(*1)The reversed-character (i.e. the cursor
<5. BASIC OPERATING PROCEDURES (USING THE DISPLAY UNIT)>5-5IM 01E30D01-01EN5.2.2 Setting ModeWhen the Setting Mode has been activated usin
<5. BASIC OPERATING PROCEDURES (USING THE DISPLAY UNIT)>5-6IM 01E30D01-01ENF0504-2.EPSMajor itemSub-itemselection (A)Sub-itemCurrent unit s
<5. BASIC OPERATING PROCEDURES (USING THE DISPLAY UNIT)>5-7IM 01E30D01-01EN5.3.2 Setting Example for Numeric-Type Data: Flow rate spanThis
<5. BASIC OPERATING PROCEDURES (USING THE DISPLAY UNIT)>5-8IM 01E30D01-01ENF0505-2.aiMajor itemSub-itemselection (B)Incorrect setting: Inco
<5. BASIC OPERATING PROCEDURES (USING THE DISPLAY UNIT)>5-9IM 01E30D01-01ENSelection of the appropriate parameterC:Basic Setup49:Flow User
<6. PARAMETER DESCRIPTION>6-1IM 01E30D01-01EN6. PARAMETER DESCRIPTION6.1 ParametersWith the exception of parameters that were speciedby
ivIM 01E30D01-01EN11.5 Regular Inspection Items ... 11-911.6 Insulation
<6. PARAMETER DESCRIPTION>6-2IM 01E30D01-01EN6.3 Parameter List Overview(1) Item A (Menu A): Display itemsMenuAcontainstheinstantaneo
<6. PARAMETER DESCRIPTION>6-3IM 01E30D01-01ENItem Name R/WData range Units Position of decimal point Default value (*): Indicated item Des
<6. PARAMETER DESCRIPTION>6-4IM 01E30D01-01EN(3) Item C (Menu C): Basic Setting itemsMenuCprincipallycontainsthebasicsettingitemsf
<6. PARAMETER DESCRIPTION>6-5IM 01E30D01-01ENItem Name R/WData range Units Position of decimal point Default value (*): Indicated item Des
<6. PARAMETER DESCRIPTION>6-6IM 01E30D01-01EN(4) Item D (Menu D): Total Setting itemsMenu D contains setting items such as the totalizatio
<6. PARAMETER DESCRIPTION>6-7IM 01E30D01-01EN(5) Item E (Menu E): Pulse Setting itemsMenu E contains items relevant to pulse output. This
<6. PARAMETER DESCRIPTION>6-8IM 01E30D01-01EN(6) Item F (Menu F): Status Functions Setting itemsMenu F contains items relevant to multiple
<6. PARAMETER DESCRIPTION>6-9IM 01E30D01-01EN(7) Item G (Menu G): Alarm Setting itemsMenu G contains setting items relevant to alarm outpu
<6. PARAMETER DESCRIPTION>6-10IM 01E30D01-01ENItem Name R/WData range Units Position of decimal point Default value (*): Indicated item De
<6. PARAMETER DESCRIPTION>6-11IM 01E30D01-01EN(8) Item H (Menu H): Display Setting itemsMenu H contains setting items that are relevant to
vIM 01E30D01-01ENINSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROOF EQUIPMENT ...
<6. PARAMETER DESCRIPTION>6-12IM 01E30D01-01EN(9) Item J (Menu J): Auxiliary Function Setting itemsMenuJcontainssettingitemssuchast
<6. PARAMETER DESCRIPTION>6-13IM 01E30D01-01EN(10) Item K (Menu K): Diagnostic Function Setting itemsMenu K contains items that are relevan
<6. PARAMETER DESCRIPTION>6-14IM 01E30D01-01EN(11) Item M (Menu M): Automatic Zero-Adjustment Function Setting itemsMenu M contains items t
<6. PARAMETER DESCRIPTION>6-15IM 01E30D01-01EN(13) Item P (Menu P): Parameter Protection itemsMenu P contains items that are relevant to wr
<6. PARAMETER DESCRIPTION>6-16IM 01E30D01-01EN6.4 Parameter DescriptionIMPORTANTOne output can be selected from pulse, alarm, or status th
<6. PARAMETER DESCRIPTION>6-17IM 01E30D01-01ENNOTEIftheowrateunits,timeunits,andowratespanarespecieduponordering,thesepa
<6. PARAMETER DESCRIPTION>6-18IM 01E30D01-01EN[B30: Total Unit] Setting of units for totalization scale →Thissettingislinkedwiththat
<6. PARAMETER DESCRIPTION>6-19IM 01E30D01-01EN[B33: Pulse Scale] Setting of pulse scale→ This setting is linked with that of parameter E11.
<6. PARAMETER DESCRIPTION>6-20IM 01E30D01-01EN(2) Menu C: Basic Setting itemsMenu C principally contains the basic setting items forthe
<6. PARAMETER DESCRIPTION>6-21IM 01E30D01-01EN[C41: Base Time Unit] Selection of time units for theowratespan→ Refer to the description
<1. INTRODUCTION>1-1IM 01E30D01-01EN1. INTRODUCTIONThis instrument has been adjusted at the factory before shipment. To ensure correct us
<6. PARAMETER DESCRIPTION>6-22IM 01E30D01-01EN(3) Menu D: Total Setting itemsMenu D contains parameters that are relevant to totalization
<6. PARAMETER DESCRIPTION>6-23IM 01E30D01-01EN[D22: Ttl Set Val Upper] Setting of the totalization preset value (upper 2 digits)This parame
<6. PARAMETER DESCRIPTION>6-24IM 01E30D01-01ENData RangeSetting Pulse Rate (pps) Maximum Value Minimum Value (0) 50% Duty 11000 0.0001 (
<6. PARAMETER DESCRIPTION>6-25IM 01E30D01-01EN(5) Menu F: Status Function Setting itemsMenu F contains setting items relevant to status Ou
<6. PARAMETER DESCRIPTION>6-26IM 01E30D01-01ENNOTEMultiple ranges settingParameters from F20 to F31 are used with the automatic multiple ra
<6. PARAMETER DESCRIPTION>6-27IM 01E30D01-01ENNOTEFor more details regarding the setting of hysteresis width, refer to the description of s
<6. PARAMETER DESCRIPTION>6-28IM 01E30D01-01ENOutput Example 2Thehighalarm(H)issetto80%ormoreoftheowrate span only without lo
<6. PARAMETER DESCRIPTION>6-29IM 01E30D01-01EN[G25: 4-20mA Process Alarm] Selection of the current output during a process alarm occurrence
<6. PARAMETER DESCRIPTION>6-30IM 01E30D01-01EN[G31: Alarm setting] Selection of the alarm output during a setting error occurrenceThispara
<6. PARAMETER DESCRIPTION>6-31IM 01E30D01-01EN[G42: Alm Record Time1] Display the operation time of alarm record1This parameter is used to
<1. INTRODUCTION>1-2IM 01E30D01-01ENNOTEA NOTE sign denotes information necessary for essential understanding of operation and features. C
<6. PARAMETER DESCRIPTION>6-32IM 01E30D01-01EN(8) Menu J: Auxiliary Function Setting itemsMenuJcontainssettingitemssuchastheowdi
<6. PARAMETER DESCRIPTION>6-33IM 01E30D01-01ENNOTE• If the setting value for the low limit is not less than the high limit value (as set u
<6. PARAMETER DESCRIPTION>6-34IM 01E30D01-01EN[J22: Dead Time] Setting of dead timeThis parameter sets the time for application of the rate
<6. PARAMETER DESCRIPTION>6-35IM 01E30D01-01EN[J30: Basic Frequency] Selection of the basic frequencyThis parameter is changed from default
<6. PARAMETER DESCRIPTION>6-36IM 01E30D01-01ENIMPORTANT• Parameters cannot be set during execution (approximately 5 minutes).• Adhesion d
<6. PARAMETER DESCRIPTION>6-37IM 01E30D01-01ENIMPORTANT• Ifthepipeisempty,theoutputuctuatesortheProcessAlarm(SignalOverow)
<6. PARAMETER DESCRIPTION>6-38IM 01E30D01-01EN[M13: Flow Zero(IEM)] Display of the result of automatic zero adjustment (excitation current
<6. PARAMETER DESCRIPTION>6-39IM 01E30D01-01EN[N15: Test Time] Selection of the holding time of test modeThis parameter is used to select t
<6. PARAMETER DESCRIPTION>6-40IM 01E30D01-01EN[P20: Write Protect] Setting of password to release the write protection functionThis paramet
<6. PARAMETER DESCRIPTION>6-41IM 01E30D01-01EN6.5 Alarm Functions6.5.1 Alarm LevelsAlarmsareclassiedintothefollowingfourdifferent
<1. INTRODUCTION>1-3IM 01E30D01-01EN(4) Maintenance• Maintenanceofthemagneticowmetershould be performed by the trained personnel hav
<6. PARAMETER DESCRIPTION>6-42IM 01E30D01-01EN(1) Display and output condition for system alarmsAlarm descriptionAlarm Output4-20mA output
<6. PARAMETER DESCRIPTION>6-43IM 01E30D01-01EN(3) Display and output condition for setting alarm occurrencesAlarm description Selection (p
<6. PARAMETER DESCRIPTION>6-44IM 01E30D01-01EN6.5.3 Alarms & Warning MessagesSystem Alarms (Device breakdown or inability to obtain c
<6. PARAMETER DESCRIPTION>6-45IM 01E30D01-01ENSetting Alarm (Device is normal but errors have been made in the setting of parameters.)Displ
<6. PARAMETER DESCRIPTION>6-46IM 01E30D01-01ENSetting Alarms (Device and measurements are normal but a warning is issued.) Displayunit/BRA
<7. OPERATION VIA BRAIN TERMINAL (BT200)>7-1IM 01E30D01-01EN7. OPERATION VIA BRAIN TERMINAL (BT200)NOTEThischapterdescribestheAXRasan
<7. OPERATION VIA BRAIN TERMINAL (BT200)>7-2IM 01E30D01-01ENUse the function key [F2] CAPS to select between uppercase and lowercase (for l
<7. OPERATION VIA BRAIN TERMINAL (BT200)>7-3IM 01E30D01-01EN7.2 AXR Operation Using a BT200This section describes procedures for setting p
<7. OPERATION VIA BRAIN TERMINAL (BT200)>7-4IM 01E30D01-01EN7.2.2 Thedataupdateandupload/download function of BT200 (1) The data upda
<7. OPERATION VIA BRAIN TERMINAL (BT200)>7-5IM 01E30D01-01EN7.3 Parameter Setting Using a BT200This section describes the procedure for se